42
English
5.4 Files
Description for the installation tools:
DME400.XIF
External Interface File
The files used for the installation tools are:
CB_UC01.TYP
Binary definitions of user types
CB_UC01.ENM
Binary definitions of user
enumerations
CB_UC01.FMT
ASCII definition of user formats
5.5 User-defined configuration parameter types (UCPT’s)
(Table 3)
Configuration Name
Range
Description
UCPT
Property
Index
date of
UCPT_time_stamp
equivalent SNVT-type: SNVT_time_stamp
1
configuration
rated
UCTP_freq_hz
16.6 Hz
equivalent SNVT-type: SNVT_freq_hz
2
frequency
50 Hz
60 Hz
user
UCPT_char_ascii
0 .. 255
equivalent SNVT-type: SNVT_char_ascii
3
information
system
UCPT_sys_appl
0: ONE_PHASE_SYSTEM
one-phase-system
4
application
1: THREE_WIRE_BAL
three-wire, three-phase system, balanced load
2: FOUR_WIRE_BAL
four-wire, three-phase system, balanced load
3: FOUR_WIRE_OPEN_Y
four-wire, three-phase system,
unbalanced load, Open-Y
4: THREE_WIRE_UNBAL
three-wire, three-phase system,
unbalanced load
5: FOUR_WIRE_UNBAL
four-wire, three-phase system,
unbalanced load
6: THREE_WIRE_BAL12
three-wire, three-phase system, balanced load
The voltage is measured between L1 and L2
7: THREE_WIRE_BAL23
three-wire, three-phase system, balanced load
The voltage is measured between L1 and L3
8: THREE_WIRE_BAL31
three-wire, three-phase system, balanced load
The voltage is measured between L3 and L1
frequency
UCPT_freq_source 0: VOLT_CIRCUIT
frequency measurement via the voltage circuit
5
measurement
1: AMP_CIRCUIT
frequency measurement via the current circuit
via
voltage or
current
circuit
energy
UCPT_energy_Ind
9: AMP_SY_IN
energy of the incoming system current
6
index
10: AMP_01_IN
energy of the incoming AC current on outer
conductor 1
11: AMP_02_IN
energy of the incoming AC current on outer
conductor 2
12: AMP_03_IN
energy of the incoming AC current on outer
conductor 3
24: TRUESY_PWR_IN
energy of the incoming active power of the
system
25: TRUE01_PWR_IN
energy of the incoming active power of phase 1
26: TRUE02_PWR_IN
energy of the incoming active power of phase 2
27: TRUE03_PWR_IN
energy of the incoming active power of phase 3
32: REACTSY_PWR_IND energy of the inductive reactive power of the
system
33: REACT01_PWR_IND
energy of the inductive reactive power
of phase 1
34: REACT02_PWR_IND
energy of the inductive reactive power
of phase 2
35: REACT03_PWR_IND
energy of the inductive reactive power
of phase 3
Table 3 continued on next page.