34
GOSSEN METRAWATT GMBH
Error Messages
Responses in the event of an error:
1.
Alarm output A1 is activated, output performance is determined by the “alarm 1” configuration digit
(see Configuration on page 18).
In the case of designation D0 and configuration as a 2-step controller, read-out takes place at switching
output II. The LED lights up when relay contact II is closed and/or transistor output II is active.
2.
LED A1 blinks at all levels. The (blinking) error message only appears at the operating level: in the event of
faulty measured values at the display, at which the error-free measured value is otherwise displayed (
SE H
,
SEL
,
CE
and
YE
) when other error messages appear in the upper display.
3.
The display is switched to the operating level 30 seconds after value selection has been completed during
configuration or parameter setting.
4.
Exceptions and additional information are included in the following table:
Display
Error Message Source
Response
Remedy
sensor error
high
Broken sensor or actual
value greater than up-
per range limit
1
sensor error low
Sensor polarity reversed
or actual value less than
lower range limit
current error
Current transformer has
reversed polarity, is un-
suitable or defective
Same as heating current monitoring alarm
Continues to control temperature
2
y error
Position ackn. incorrectly
calibrated,
Y100
≤
Y0
No response to error
3
no tune
Self-tuning cannot be
started (controller sort:
“actuator” or “limit
transducer”)
No response to error
Error message is not cleared until key is pressed
–
Ctr. Sort
Manipulating Factor Read-Out
2 or 3-step
YSE
= –100/0/100%
YSE
≠
–100/0/100%
–100/0/100%
If the controller has settled in:
last “plausible” manipulating
factor, if not:
YSE
Step
YSE
On/off ctr.
Actuator
No response to error