Correction for step-action controllers in the event that T
I
or T
II
is smaller than
tY
:
tY
•
tY
tY
•
tY
Multiply
Pb 1
by
, if T
I
is smaller, or by
, if T
II
is smaller.
T
I
•
T
I
T
II
•
T
II
The value for
tu
is very inaccurate in this case. It should be optimized in the closed loop control mode.
Closed Loop Control Mode
The closed loop control mode is started after self-tuning has been completed:
–
Configure the desired control algorithm with
controller sort
.
–
Adjust the
setpoint
to the required value.
–
The dead band can be increased from
dbnd
=
0
for 3-step, split range and step-action controllers if con-
trol of switching output I (or the continuous output) and II changes too rapidly, for example due to an
unsteady actual value.
Setpoint Ramps
Function
Parameters
SPuP
and
SPdn
cause a gradual temperature change
(rising / falling) in degrees per minute.
Activation
– When auxiliary power is switched on
– When the current setpoint is changed
– When setpoint 2 is activated
– After switching from manual to automatic operation
Setpoint display
The targeted setpoint is displayed (not the currently valid setpoint) with a blinking
r
at
the left-hand digit.
Limit values
Relative
limit values make reference to the ramp, not the targeted setpoint. As a rule, no
alarm is triggered for this reason.