22
GOSSEN METRAWATT GMBH
Controller Sorts
Parameters:
Code
Controller Sort
Comment
Limit transducer
Switching output I is active where actual value < current setpoint, and switching output II is
active where actual value > current se
dbnd
. Switching hysteresis is equal to
HYST
.
Switching status changes are possible once per
tc
.
Actuator
Read-out of a constant actuating signal to switching output I where
YST
> 0, or switching
output II where
YST
< 0. The actuating cycle is equal to at least
tc
. No alarm functions.
2-step controller, “heat”
A harmonic-free PDPI control algorithm regulates switching output I in order to increase /
decrease the actual value. The actuating cycle is equal to at least
tc
.
2-step controller, “cooling”
3-step controller
A harmonic-free PDPI control algorithm regulates switching output I in order to increase the
actual value, or switching output II in order to decrease the actual value. The actuating cycle
is equal to at least
tc
.
The dead band
dbnd
suppresses switching back and forth between “heating” and “cooling”
if no lasting deviation occurs.
3-step controller, water
cooling
The manipulating factor at switching output II is adapted to the non-linear performance char-
acteristics of a water cooler. The actuating cycle is equal to
tc
.
Step-action controller
A harmonic-free PDPI control algorithm regulates switching output I or II in order to increase
or decrease the actual value. The duration of the actuating impulse is equal to
tc
. The dead
band
dbnd
is symmetric to the setpoint.