Goslyn – Oil Recovery Program
Page
16
troubleshoot your system
…
goslyn™ Low Drain Pump System
•
Reservoir Tank is overflowing
o
Tank is full and the sensor light is green
§
Clean off the sensor lens (bottom of blue sensor) in order for it to properly
sense the full tank
o
Tank is full and the sensor light is yellow
§
If pump is running but not pumping effluent, prime the pump by unscrewing
the small bolt located on the top of the pump and pouring in water. Make
sure you unplug the Control Box before priming the pump.
§
If priming pump does not work, contact your plumber to ensure that no
debris is stuck in the pump.
goslyn™ Oil Recovery Device
•
Unit is surcharging at the inlet
o
The strainer basket needs to be emptied
o
Open the silt valve and flush out the silts for 10 to 15 seconds with the oven water
turned on
•
Effluent is collecting in the center compartment
o
Make sure the strainer basket has been emptied.
o
Ensure that the oil valve is clean to allow normal flow of discharged oil
•
Unit is surcharging at the outlet
o
Make sure outlet pipe is free of debris