heat pump operates in the reserve mode (symbol no. 

14

 is displayed). The possibility of switching to normal mode 

is checked cyclically. If the temperature of inlet air is higher than -7 °C, the heat pump switches to normal mode of 
operation (symbols 

16

 and 

20 

are displayed). The heater switches off. The heat pump is on and the screen 

remains unlit and inactive. 
 
At lower air temperatures, the evaporator defrosting cycle is started in the outdoor unit if necessary. Symbol no. 

19 

is displayed on the screen. The fields 

2

4

6

11

13

 and 

15

 remain inactive. Defrosting continues until the 

conditions for normal operation of the heat pump are achieved. 
After successful defrosting, the heat pump returns to normal operation (symbols 

16

 and 

20 

are displayed). 

If defrosting is unsuccessful, the controlling unit displays an error message. Field no. 

4

 starts flashing, 

accompanied by warning beeps. Error code 

E247

 appears in field no. 

12

 and the pump switches automatically to 

heating with the electric heater. The screen displays symbol no. 

14

. The error code can be deleted at any time by 

pressing field no. 

4

. Field no. 

12

 resumes to displaying time. 

 

Setting the clock and day of the week

 

 

 

Hold field no. 

12

, until field no. 

7

 shows a flashing number of the day of the week. 

 

By pressing 

+

 or 

 you can set the number of the day of the week 

(1 – Monday, …, 7 – Sunday). 

 

Press field no. 

12

 again (flashing hour setting is displayed). 

 

By pressing 

+

 or 

 set the hour (by holding 

+

 or 

 you can speed up the setting). 

 

Press field no. 

12

 again. 

 

Flashing minute setting is displayed. 

 

By pressing 

+

 or 

 set the minutes (by holding 

+

 or 

 you can speed up the setting). 

 

The setting is stored when you press field no. 

12

, or when the field stops flashing.  

 

Setting the temperature 

 

Press field no. 

5

 (the set temperature starts blinking). 

 

By pressing 

+

 or 

 you can change the temperature setting from 10 °C to 75 °C (pre-set to economic 

temperature of 55 °C). 

 

The setting is stored by pressing field no. 

5

 again, or when field no. 

5

 stops flashing. After a few seconds, the 

display shows the actual temperature.  

 

In case of power failure, the last stored value is restored.  

 

Switching on the "TURBO" mode 

 

If you need more warm water than the heat pump can heat up in a short period of time, press field no. 

13 

(switches on the "TURBO" mode). The heat pump and heater work simultaneously. The screen shows symbols 
no. 

14

16

 in 

20

. When the temperature reaches 55 °C the heat pump returns to the mode used before the 

"TURBO" mode. 

 

Switching on the "HOT" mode 

 

If you want to heat the water to the maximum temperature of 75 °C, press field no. 

15

. The heat pump will heat 

the water to 55 °C. The screen displays symbols no. 

16

 in 

20

. When the temperature in the boiler reaches 55 °C 

the electric heater turns on to heat the temperature up to 75 °C. The screen displays the symbol no. 

14

. When 

the temperature reaches 75 °C the heat pump returns to the mode used before the "HOT" mode.  

 

Display of the quantity of water in the heat pump 

The display shows the symbol: 

 - no warm water 

   

 

 

 

 

 - low quantity of warm water 

 
   

 

 

 

 

 - high quantity of warm water 

 

Setting the vacation mode 

In the vacation mode, you can set the number of days (maximally 100), when the heat pump shall maintain the 
minimum temperature of water (approximately 10 °C). 

 

Hold field no. 

6

 for a while (fields 

5

 and 

6

 start to flash). 

 

By pressing fields 

+

 or 

 you can set the number of vacation days shown in field no. 

5

 

By pressing field no. 

6

 again, or when field no. 

6

 stops flashing, the set number of days is stored.  

 

If you set the value to 000, then the heat pump will resume its normal operating mode after confirming the 
setting, and illumination of field no. 

6

 will turn off. 

 

After the set number of days has elapsed, the heat pump returns to the normal mode and illumination of field no. 

6

 turns off.  

 
 

Summary of Contents for TC120SNE

Page 1: ...SL EN NAVODILA ZA UPORABO INSTRUCTIONS FOR USE TC 120 150 SPLIT...

Page 2: ...2...

Page 3: ...i name en v smeri navzdol in v obmo ju kjer ne zamrzuje Za pravilno delovanje varnostnega ventila morate sami izvajati redne kontrole po potrebi odstraniti vodni kamen in preveriti da varnostni ventil...

Page 4: ...r ga boste obesili primerno oja iti Zaradi la je kontrole in menjave magnezijeve anode vam priporo amo da pod aparatom in tlemi pustite zadosti prostora glejte namestitev V nasprotnem primeru bo ob se...

Page 5: ...na trdnost stene da lahko prena a te o vklju no z vodo v kotlu Priporo amo namestitev ki omogo a im kraj e plinske povezave Pri postavitvi upo tevajte minimalne odmike aparata od stene tal in stropa g...

Page 6: ...in pritrditve primeren za namestitev naprave Ob monta i na streho upo tevajte lokalne predpise Sl 2 Monta ne mere zunanje enote agregata Namestitev odto nega nastavka V odvodno koleno dajte tesnilo po...

Page 7: ...ami izvajati redne kontrole da se odstrani vodni kamen in da se preveri da varnostni ventil ni blokiran Ob preverjanju morate s premikom ro ke ali odvitjem matice ventila odvisno od tipa ventila odpre...

Page 8: ...enoto kotlom in zunanjo enoto agregatom Cev z namenskim orodjem odre ite malo dalj o kot je izmerjena razdalja Povezovalni kabli naj bodo cca 1 0 m dalj i od dol ine cevi Sl 5 Priprava cevi Raziglevan...

Page 9: ...rivijte matice z zavihkom potem jih privijte s klju em in momentnim klju em kot je prikazano na sliki Sl 9 Privijanje priklju ka Opozorilo Prekomerni pritezni moment lahko prelomi matico odvisno od po...

Page 10: ...restavite zunanjo enoto agregat na drugo mesto praznjenje opravite z napravo za zajemanje hladilnega sredstva Preverite da je hladilno sredstvo dodano v hladilni sistem v vsakem primeru v teko em stan...

Page 11: ...jo v elektri no omre je je potrebno v notranjo enoto kotlom vgraditi priklju no vrvico minimalnega preseka vsaj 1 5 mm2 H05VV F 3G 1 5 mm2 Da to lahko storite morate s toplotne rpalke odstraniti za it...

Page 12: ...agregatom ni prilo en Kabel mora zado ati minimalni kakovosti H05RN F s presekom od 1 0 do 1 5 mm2 Na zunanji strani naj bodo povezovalni kabli dodatno za iteni pred atmosferskimi vplivi in drugimi p...

Page 13: ...emljitve 3 Preizkus odvodnih tokov izvedeno med preizkusnim delovanjem Med preizkusnim delovanjem ko kon ate z monta o lahko serviser uporabi tipalo napetosti in multimeter da izvede preizkus odvodnih...

Page 14: ...zpadu elektri ne energije V primeru izpada elektri ne energije ostanejo podatki o nastavitvah shranjeni nekaj ur Po ponovnem zagonu deluje toplotna rpalka v enakem re imu kot je bil pred prekinitvijo...

Page 15: ...zaslonu se ez nekaj sekund prika e dejanska temperatura Ob izpadu omre ne napetosti se ohrani zadnja shranjena vrednost Vklop na ina delovanja TURBO V kolikor v kratkem asu potrebujete ve tople vode...

Page 16: ...tednu oz za obdobje od ponedeljka do petka in od sobote do nedelje je potrebno nastaviti vse 3 asovne periode po zgoraj opisanem postopku b Vklop izklop asovnika S pritiskom na polje 11 vklopite nasta...

Page 17: ...r na toplotni rpalki ne popravljate sami ampak o njih obvestite najbli jo poobla eno servisno slu bo MOTNJE V DELOVANJU Kljub skrbni proizvodnji in kontroli lahko pride pri delovanju toplotne rpalke d...

Page 18: ...2 l 151 199 Nazivni tlak MPa bar 0 6 6 0 9 9 Masa kotla napolnjen z vodo kg 51 169 59 206 Masa zunanje enote prazna kg 29 Protikorozijska za ita kotla Emajlirano Mg anoda Debelina izolacije mm 40 85...

Page 19: ...ric pressure The outlet of the safety valve should be installed facing downwards and in a non freezing area To ensure proper functioning of the safety valve the user should perform regular controls to...

Page 20: ...ong enough We recommend leaving enough space between the floor and the unit as to provide easy access to the Mg anode se Installation If not the unit will need to be dismounted from the wall before se...

Page 21: ...ith the weight of the water inside the boiler It is recommended to choose a place that enables installation with minimum gas pipeline length During installation please bear in mind the minimum distanc...

Page 22: ...ructure and anchoring method are appropriate for the unit When mounting the unit on the roof please take into account the local regulations Fig 2 installation dimensions of the outdoor unit the aggreg...

Page 23: ...correct operation of the safety valve the valve must be regularly checked to remove limescale and check if the safety valve is blocked When checking the valve push the lever or unscrew the nut of the...

Page 24: ...e aggregate With appropriate tools cut the pipe a little longer than the measured distance Connecting cables should be about 1 0 m longer than the pipe length Fig 5 Pipe preparation Deburring Complete...

Page 25: ...ficiently tighten the flare nuts with your fingers and then tighten them with a spanner and torque wrench as shown Fig 9 Tightening the connection Warning Excessive torque can break the nut depending...

Page 26: ...evacuation using a refrigerant pumping device Make sure the refrigerant added into the air conditioner is in the liquid form The adding of a refrigerant should be carried out on a low pressure servic...

Page 27: ...minimum cross sectional area of at least 1 5 mm2 H05VV F 3G 1 5 mm2 should be installed in the indoor unit To do that the protective cover must be removed from the heat pump The connection of the heat...

Page 28: ...e must comply with the minimum quality standard H05RN F with a cross sectional area of 1 0 to 1 5 mm2 On the outdoor side the connecting cables must be additionally protected from the elements and oth...

Page 29: ...by visual detection and grounding resistance tester 3 Electrical leakage check performing during test running During test operation after finishing installation the serviceman can use the electro pro...

Page 30: ...the screen is field no 9 If you switch off the heat pump for a longer period of time the water must be drained from the pump if there is any danger of freezing Power failure protection In case of powe...

Page 31: ...nking By pressing or you can change the temperature setting from 10 C to 75 C pre set to economic temperature of 55 C The setting is stored by pressing field no 5 again or when field no 5 stops flashi...

Page 32: ...by pressing field no 11 or wait for field no 12 to stop flashing and the setting to be saved automatically To set the timer operating mode for each day of the week or for the period from Monday to Fr...

Page 33: ...bient temperature too low Can you hear the operation of the compressor and fan Please do not try to eliminate malfunctions by yourself call your nearest authorized service company OPERATION ERRORS Des...

Page 34: ...essure MPa bar 0 6 6 0 9 9 Weight of boiler filled with water kg 51 169 59 206 Weight of outdoor unit empty kg 29 Anti corrosion protection of tank Enamelled Mg anode Insulation thickness mm 40 85 Deg...

Page 35: ...35...

Page 36: ...05 2017 561331...

Reviews: