The inverter can exclude the possibility of DC residual currents to 6mA in the system,Where an external RCD is required in addition 
to the built-in RCMU, type A can be used, type B or type A must be used to avoid tripping

(6) Positive shall be red, negative shall be black .

(7) The minimum insulation resistance to ground of the PV panels for NS series must exceed 16.7k

Ω

(R = 500/30 mA) the 

minimum insulation resistance to ground of the PV panels for DNS series must exceed 19.3k

Ω

(R = 580/30 mA)

there is a 

risk of shock hazard if the requirement of minimum resistance is not met.

3.4.2 AC circuit breaker and leakage current protection device

In order to ensure that the inverter can be safe and reliable to disconnect from the power grid, please install an

independent two pole circuit breaker to protect the inverter.

Inverter model

GW1000-NS/GW1500-NS/GW2000-NS/GW2500-NS

GW3000-NS/GW3000D-NS/GW3600-NS/GW3600D-NS

GW4200-NS/GW4200D-NS/GW5000-NS/GW5000D-NS

Recommended circuit breaker specifications

Note: Multiple inverters are not allowed to share a circuit breaker.

The integrated leakage current detection device of the inverter can detect external leakage current in real time. When the

detected leakage current exceeds the limit value, inverter will quickly disconnect with the grid, If the leakage current

protection device is installed externally, the action current should be 300mA or higher.

3.4.3 DC Side Connection

(

permanently damage the unit.

(2)The open circuit voltage of the PV strings cannot exceed the maximum input voltage of the inverter.

(3)Only DC connectors provided by us are permitted to use.

(4)The positive and negative pole is forbid to connect PE wire (Ground wire), otherwise, it will damage the unit.

(5)Don't connect positive or negative pole of PV string to PE wire. Otherwise, it will cause damage to inverter.

1)Before connecting the PV strings, please ensure the plug connectors have the correct polarity. Incorrect polarity could 

There are three types of DC connectors, SUNCLIX / MC4 and AMPHENDL H4 series. Please refer to Figure 3.4.3-1.

DC Cable specification is showed as Figure 3.4.2-2.

Conductor Material

Sectional Area

O.D.

A

Bare Wire Length

C

Grade    Description

Value

7mm around

DC Cable should be use dedicated PV cable
(Suggest using 4mm  PV1-F wire)

2

Installation instruction of SUNCLIX please refer to Figure 3.4.3-3.

Installation instruction of MC4 and H4 Series please refer to Figure 3.4.3-4.

Negative connector

Positive connector

Negative connector

Positive connector

Limit buckle can't

crimping the wire

Special tools are used to stitching

Summary of Contents for GW-6000D-NS

Page 1: ...om cn www goodwe com cn www goodwe com cn service au goodwe com cn GoodWe Australia www goodwe com cn service nl goodwe com cn GoodWe Netherlands GoodWe UK www goodwe co uk enquiries goodwe co uk Note The information above is subject to change without prior notice details refer to www goodwe com cn SOLAR INVERTER NS DNS SERIES USER MANUAL ...

Page 2: ...nance 3 1 Mounting Instructions 3 2 Inverter Overview and Package 3 3 Inverter Installation 3 4 Electrical Connection 4 1 Indicator Lights 4 2 User Interface and Use of the Display 4 3 Error Code 4 4 WiFi Reset and Reload to Factory Setting 4 5 Special Adjustable Setpoints 01 02 02 03 05 13 13 16 17 01 17 18 22 17 22 ...

Page 3: ...60 during operation To avoid being burnt do not touch the inverter during operation Let it cool before touching it Keep children away from inverter Do not open the front cover of the inverter Apart from performing work at the wiring terminal as instructed in this manual touching or changing components without authorization may cause injury to people damage to inverters and annulment of the warrant...

Page 4: ... method must be appropriate for the inverter s weight and dimensions The location must be well ventilated and sheltered from direct sunlight The inverter must be installed vertical or with a backward tilt less than 15 No sideways tilt is allowed The connection area must point downwards Refer to Figure 3 3 1 1 To allow dissipation of heat and for convenience of dismantling clearances around the inv...

Page 5: ...e are two AC connector brands for inverter VACONN and WIELAND Please refer to Figure 3 4 1 1 6 The AC line construction shall be such that if the cord should slip in its anchorage placing a strain on conductors the protective earthing conductor will be the last to take the strain such as the PE line is longger than L and N Installation instruction of VACONN series please refer to Figure 3 4 1 2 fa...

Page 6: ... the detected leakage current exceeds the limit value inverter will quickly disconnect with the grid If the leakage current protection device is installed externally the action current should be 300mA or higher 3 4 3 DC Side Connection permanently damage the unit 2 The open circuit voltage of the PV strings cannot exceed the maximum input voltage of the inverter 3 Only DC connectors provided by us...

Page 7: ...ication This function is only applied to inverters with RS485 The RS485 interface is used to connect EzLogger Pro and the maximum total length of all connecting cables should not exceed 800m RS485 connection is referred to 3 4 6 1 1 Connection Procedure Put the cable through the components in this order screw cap one hole sealing ring insulation body and sheet metal parts Take the green terminal o...

Page 8: ...t not connected Connection Procedure Put the cable through the components in this order screw cap one hole sealing ring insulation body and sheet metal parts Pull out the 6 pin terminal from the socket in the cabinet and take off the resistor which is fixed in it Cable should be connected as Figure 3 4 8 2 Insert the green terminal into the corresponding interior terminal of the inverter Pull cabl...

Page 9: ...it X X Set Power Limit XX Short press to select number 0 9 Short press to select number 0 9 Short press to select number 0 1 Long press 2S Long press 2S Long press 2S Long press 2S Or Set Modbus Addr Pac 2595 5W Short press Long press 2S Set Addr XXX Set Addr X X X Set Addr XXX Short press to select number 0 9 Short press to select number 0 2 Long press 2S Long press 2S Long press 2S Short press t...

Page 10: ......

Page 11: ...ite or contact with after sales PV Backfeed Current A 0 18 4 4 Wi Fi Reset Wi Fi Reload The two functions are only available for Wi Fi model inverters Wi Fi reload function is used to change the Wi Fi configuration to default value Please configure the Wi Fi again as 3 4 5 after using the function Press the key until the LCD displays Wi Fi Reset then long press 2S until the LCD displays Wi Fi Rese...

Page 12: ... 220 230 220 230 220 230 220 230 Nominal Output Frequency Hz Max Output Current A Output Power Factor Output THDi Nomina Output 50 60 50 60 50 60 50 60 13 6 16 19 22 8 1 Adjustable from 0 8 leading to 0 8 lagging Europe efficiency 97 8 580 80 550 120 580 580 580 80 550 80 550 80 550 120 120 120 11 11 11 11 11 11 13 8 13 8 13 8 13 8 13 8 13 8 2 2 2 3000 3680 4200 5000 3000 3680 4200 5000 97 5 AC ov...

Page 13: ...ly connected to the installation Examples are appliances portable tools and other plug connected equipment Category III applies to fixed equipment downstream of and including the main distribution board Examples are switchgear and other equipment in an industrial installation Category IV applies to equipment permanently connected at the origin of an installation upstream of the main distribution b...

Reviews: