The inverter complies with IEC62109-2 chapter 13.9. When earth fault occurs,the fault indicator LED on front cover will 

light up, and,  for wifi inverter, it will email the fault information to customer, for non wifi inverter ,the buzzer in inverter 

will keep ringing 1 minute and ring again after half an hour unless the fault is resolved(This function is only available to 

Australia/ New Zealand).

3.4.7 Wi-Fi Communication

The Wi-Fi communication function is only applied to WiFi BOX, the detailed configuration instruction can be referred to Wi-Fi 

Configuration in the accessory box.

After configuration, please browse http://www.goodwe-power.com to create PV station.

3.4.8 Power Limiting Device & DRED Installation

Connection method of Power Limiting device CT please refer to Figure 3.4.8-1.

NOTE:

2-pin terminal is used to make connection to CT device.You can find it in accessory bag.

6-pin terminal is used to make connection to DRED device. If DRED device is not available, please keep it not connected.

Connection Procedure:

   Put the cable through the components in this order: screw cap, one-hole sealing ring, insulation body and sheet metal parts.    

   Pull out the 6-pin terminal from the socket in the cabinet and take off the resistor which is fixed in it.Cable should be 

connected as Figure 3.4.8-2.

   Insert the green terminal into the corresponding interior terminal of the inverter. Pull cable softly to maintain the cable not 

to be pulled out.   

   Lock the sheet metal parts onto the box and tighten the screw cap.

1.DRED connection is only available forAustralia and New Zealand.

2.Supported DRM command: DRM0,DRM5,DRM6,DRM7,DRM8.

3.After installation is completed, please set up power limiting function referring to section 4.2(6).

4.Pay attention to the direction of CT when wiring. CT clip should be locked tight. White /Black cable should connect Line 2,

black cable should connect Line 1. Tighten them with screwdriver. Make sure CT cables connected to the right output phase lines 

of inverter when in use.

5.Without connection of CT, inverter will show "CT Disconnect". If CT is connected reversely, inverter will show" CT Reverse 

"when it enters into on-grid status.

3.4.9 Earth Fault Alarm

Summary of Contents for GW-6000D-NS

Page 1: ...om cn www goodwe com cn www goodwe com cn service au goodwe com cn GoodWe Australia www goodwe com cn service nl goodwe com cn GoodWe Netherlands GoodWe UK www goodwe co uk enquiries goodwe co uk Note The information above is subject to change without prior notice details refer to www goodwe com cn SOLAR INVERTER NS DNS SERIES USER MANUAL ...

Page 2: ...nance 3 1 Mounting Instructions 3 2 Inverter Overview and Package 3 3 Inverter Installation 3 4 Electrical Connection 4 1 Indicator Lights 4 2 User Interface and Use of the Display 4 3 Error Code 4 4 WiFi Reset and Reload to Factory Setting 4 5 Special Adjustable Setpoints 01 02 02 03 05 13 13 16 17 01 17 18 22 17 22 ...

Page 3: ...60 during operation To avoid being burnt do not touch the inverter during operation Let it cool before touching it Keep children away from inverter Do not open the front cover of the inverter Apart from performing work at the wiring terminal as instructed in this manual touching or changing components without authorization may cause injury to people damage to inverters and annulment of the warrant...

Page 4: ... method must be appropriate for the inverter s weight and dimensions The location must be well ventilated and sheltered from direct sunlight The inverter must be installed vertical or with a backward tilt less than 15 No sideways tilt is allowed The connection area must point downwards Refer to Figure 3 3 1 1 To allow dissipation of heat and for convenience of dismantling clearances around the inv...

Page 5: ...e are two AC connector brands for inverter VACONN and WIELAND Please refer to Figure 3 4 1 1 6 The AC line construction shall be such that if the cord should slip in its anchorage placing a strain on conductors the protective earthing conductor will be the last to take the strain such as the PE line is longger than L and N Installation instruction of VACONN series please refer to Figure 3 4 1 2 fa...

Page 6: ... the detected leakage current exceeds the limit value inverter will quickly disconnect with the grid If the leakage current protection device is installed externally the action current should be 300mA or higher 3 4 3 DC Side Connection permanently damage the unit 2 The open circuit voltage of the PV strings cannot exceed the maximum input voltage of the inverter 3 Only DC connectors provided by us...

Page 7: ...ication This function is only applied to inverters with RS485 The RS485 interface is used to connect EzLogger Pro and the maximum total length of all connecting cables should not exceed 800m RS485 connection is referred to 3 4 6 1 1 Connection Procedure Put the cable through the components in this order screw cap one hole sealing ring insulation body and sheet metal parts Take the green terminal o...

Page 8: ...t not connected Connection Procedure Put the cable through the components in this order screw cap one hole sealing ring insulation body and sheet metal parts Pull out the 6 pin terminal from the socket in the cabinet and take off the resistor which is fixed in it Cable should be connected as Figure 3 4 8 2 Insert the green terminal into the corresponding interior terminal of the inverter Pull cabl...

Page 9: ...it X X Set Power Limit XX Short press to select number 0 9 Short press to select number 0 9 Short press to select number 0 1 Long press 2S Long press 2S Long press 2S Long press 2S Or Set Modbus Addr Pac 2595 5W Short press Long press 2S Set Addr XXX Set Addr X X X Set Addr XXX Short press to select number 0 9 Short press to select number 0 2 Long press 2S Long press 2S Long press 2S Short press t...

Page 10: ......

Page 11: ...ite or contact with after sales PV Backfeed Current A 0 18 4 4 Wi Fi Reset Wi Fi Reload The two functions are only available for Wi Fi model inverters Wi Fi reload function is used to change the Wi Fi configuration to default value Please configure the Wi Fi again as 3 4 5 after using the function Press the key until the LCD displays Wi Fi Reset then long press 2S until the LCD displays Wi Fi Rese...

Page 12: ... 220 230 220 230 220 230 220 230 Nominal Output Frequency Hz Max Output Current A Output Power Factor Output THDi Nomina Output 50 60 50 60 50 60 50 60 13 6 16 19 22 8 1 Adjustable from 0 8 leading to 0 8 lagging Europe efficiency 97 8 580 80 550 120 580 580 580 80 550 80 550 80 550 120 120 120 11 11 11 11 11 11 13 8 13 8 13 8 13 8 13 8 13 8 2 2 2 3000 3680 4200 5000 3000 3680 4200 5000 97 5 AC ov...

Page 13: ...ly connected to the installation Examples are appliances portable tools and other plug connected equipment Category III applies to fixed equipment downstream of and including the main distribution board Examples are switchgear and other equipment in an industrial installation Category IV applies to equipment permanently connected at the origin of an installation upstream of the main distribution b...

Reviews: