Operating Altitude(m
)
User
Interface
Communication
Size Width
*
Height
*
Depth
mm
(
)
self
≤
4000
al
LCD&LED
VDE-AR-N 4105,
VDE0126-1-1
EN50438(PL),
EN50438(SW),G83,
IEC61727,AS4777.2
IEC62116
EN6100-6-1,EN61000-6-2,EN61000-6-3,EN61000-6-4
Technical Data
14
347*432*145mm
VDE-AR-N 4105
VDE0126-1-1
EN50438(PL),
EN50438(SW),G59,
IEC61727,AS4777.2
IEC62116
VDE-AR-N 4105
VDE0126-1-1
EN50438(PL),
EN50438(SW),G59,
IEC61727,AS4777.2
IEC62116,MEA,PEA
Moisture location category
4K4H
Environment category
Outdoor
&
Indoor
External environment pollution degree
Grade1
、
2
、
3
GW5KD-NS
AS4777.2
IEC62109-2 VDE0126-1-1
Special Adjustable Setpoints
The inverter has field adjustable function,such as trip points,trip times, reconnect times,active and invalid of QU curve,PU
curve.
It is adjustable through special software ,if you want to use it ,plaese contact with after sales.
The methods document of using the software can download from goodwe website or contact with after sales.
8 Maintenance
Insulation Resistor Detection
Residual Current Monitoring Unit
Output Over Current Protection
Output Short Protection
Output Over Voltage Protection
Operating Temperature Range(
℃
)
Anti-islanding Protection
Input Reverse Polarity Protection
Integrated (AFD)
Storage Temperature (
℃
)
-
30~65
High Frequency Isolation
Note
Overvoltage category definition
Category I: applies to equipment connected to a circuit where measures have been taken to reduce transient overvoltage to a
low level.
Category II: applies to equipment not permanently connected to the installation. Examples are appliances, portable tools and
other plug-connected equipment;
Category III: applies to fixed equipment downstream of and including, the main distribution board. Examples are switchgear and
other equipment in an industrial installation;
Category IV: applies to equipment permanently connected at the origin of an installation (upstream of the main distribution board)
Example are electricity meters, primary overcurrent protection equipment and other equipment connected directly to
outdoor open lines.
Moisture location category definition
Moisture parameters
Temperature Range
Humidity Range
3K3
0~+40
℃
5
%~
85
%
4K2
-
33~+40
℃
15
%~
100
%
4K4
H
-
20~+55
℃
4
%~
100
%
Level
Environment category definition
Outdoor : the ambient air temperature is -20~50
, Relative humidity range is 4%to 100%
,
applied to PD3
Indoor unconditioned: the ambient air temperature is -20~50
, Relative humidity range is 5%to 95%,applied to PD3
Indoor conditioned: the ambient air temperature is 0~40
, Relative humidity range is 5%to 85%,applied to PD2
℃
℃
℃
Pollution degree definition
Pollution degree 1: No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by
condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or, dry, non-conductive pollution occurs which becomes conductive due to
condensation which is expected.
Pollution degree 4: Persistent conductive pollution occurs, for example, the pollution cause by conductive dust, rain and snow.
**:
Please make sure the voltage of PV string will not exceed the Max. DC voltage.