PRODUCT DESIGN

4

SSZ16 models are available in 2, 3, 4 and 5 ton sizes and
use R-410A refrigerant. They are designed for 208/230 volt
single phase applications.

The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then dis-
charged out of the top of the cabinet.

These units are designed for free air discharge, so no addi-
tional resistance like duct work shall be attached.

The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type cop-
per. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal in-
stallation is factory installed in the condensing unit. SSZ units
are charged for the matching evaporator coil and a 15 foot
refrigerant line set.

Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Condi-
tioning Contractors Association (ACCA) or equivalent.  It is
the contractors responsibility to ensure the system has ad-
equate capacity to heat or cool the conditioned space.

SSZ16 models use high-efficiency Copeland

®

 Scroll

"Ultratech" compressors which are specifically designed for
R-410A refrigerant. There are a number of design character-
istics which are different from the scroll compared to the tra-
ditional reciprocating compressor.

"Ultratech" Series scroll compressors will not have a dis-
charge thermostat, some of the early model scroll compres-
sors required discharge thermostats.

Due to their design Scroll compressors are inherently more
tolerant of small quantities of liquid refrigerant.

NOTE: 

 Even though the compressor section of a Scroll com-

pressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.

"Ultratech" Series scroll compressors use "POE" or
polyolester oil  which is 

NOT

 compatible with mineral oil based

lubricants like 3GS.  "POE"  oil must be used if additional oil
is required.

WARNING

To avoid possible injury, explosion or death, practice
safe handling of refrigerants.

Operating pressures and amp draws may differ from stan-
dard reciprocating and/or scroll compressors.  This informa-
tion may be found in the "Cooling Performance Data" sec-
tion.

This unit is for outdoor installation only. Refer to minimum
figure for clearances from the sides of the unit to full walls
and other objects.

NOTE:

 This unit cannot be completely enclosed. At least

one side must be unrestricted.

These clearances will help avoid air recirculation. If installing
two or more units at the same location, allow at least 24
inches between units. If only one side is restricted (for ex-
ample, against the outside wall of a house), the unit may be
placed as close as 8" to that one wall.

DO 

NOT

 locate the unit:

* Directly under a vent termination for a gas appliance.

* Within 3 feet of a clothes drier vent

* Where the refreezing of defrost water would create

a hazard

* Where water may rise into the unit.

OK!

OK!

AA

AA

A

A

C

C

C

C

OK!

OK!

OK!

OK!

NOT

RECOMMENDED

AA

AA

AA

AA

AA

B

B

B

B

Model Type

A

B

C

AA

Residential

10"

10"

18"

20"

Light Commercial

12'

12"

18"

24"

Model

Dimensions - W x D x  H

SSZ160241A*

29 x 29 x 38¼

SSZ160361A*

35½ x 35½ x 38¼

SSZ160481A*

35½ x 35½ x 38¼

SSZ160601A/B*

35½ x 35½ x 38¼

Summary of Contents for SSZ 16 SEER

Page 1: ...tion Models listed on page 3 RT6214002r10 February2014 Copyright 2006 2007 2009 2010 2012 2014 Goodman Manufacturing Company L P TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL M...

Page 2: ...re servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Installation and repair of this unit should be performed...

Page 3: ...Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise contact your local E...

Page 4: ...ompressors are inherently more tolerant of small quantities of liquid refrigerant NOTE Even though the compressor section of a Scroll com pressor is more tolerant of liquid refrigerant continued flood...

Page 5: ...ns 3 ton unit Unit is charged with refrigerant for 15 of 3 8 liquid line System charge must be adjusted per Installation Instructions Final Charge Procedure Installation of these units requires the sp...

Page 6: ...connections 4 5 ton units Installer will need to supply 3 4 to 7 8 adapters for suction line connections 3 ton unit Unit is charged with refrigerant for 15 of 3 8 liquid line System charge must be ad...

Page 7: ...0 82 0 73 0 55 0 36 0 85 0 76 0 57 0 37 0 87 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 93 0 83 0 63 0 41 0 94 0 84 0 64 0 41 Del t a T 21 19 16 11 21 20 16 11 21 20 16 11 21 20 16 11 21 19 16 11 20 18 15...

Page 8: ...263 278 289 278 299 316 329 316 340 360 375 356 383 404 422 393 423 447 466 LO PR 114 121 132 141 120 128 140 149 125 133 145 155 131 140 152 162 138 146 160 170 142 151 165 176 MBh 22 2 22 6 23 7 25...

Page 9: ...4 32 7 25 3 26 0 28 2 30 3 S T 0 79 0 71 0 54 0 35 0 82 0 74 0 56 0 36 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 90 0 81 0 61 0 39 0 91 0 81 0 62 0 40 Delta T 21 20 16 11 22 20 16 11 22 20 16 11 22 20...

Page 10: ...282 303 320 334 321 346 365 381 361 389 411 428 399 430 454 473 LO PR 110 117 128 137 117 124 135 144 121 129 141 150 127 135 148 157 133 142 155 165 138 147 160 171 MBh 32 0 32 6 34 2 36 4 31 3 31 9...

Page 11: ...8 34 7 35 8 38 7 41 5 S T 0 81 0 72 0 55 0 35 0 84 0 75 0 57 0 36 0 86 0 77 0 58 0 37 0 89 0 79 0 60 0 39 0 92 0 82 0 62 0 40 0 93 0 83 0 63 0 40 DeltaT 23 21 18 12 23 22 18 12 24 22 18 12 24 22 18 1...

Page 12: ...4 262 277 289 277 298 315 328 316 340 359 374 355 382 403 421 392 422 446 465 LO PR 112 119 130 139 118 126 138 147 123 131 143 152 129 138 150 160 136 144 157 168 140 149 163 173 MBh 43 9 44 8 46 9 5...

Page 13: ...53 8 41 7 42 9 46 4 49 8 S T 0 77 0 69 0 52 0 34 0 80 0 72 0 54 0 35 0 82 0 74 0 56 0 36 0 85 0 76 0 58 0 37 0 88 0 79 0 60 0 38 0 89 0 80 0 60 0 39 Delta T 23 21 17 12 23 21 18 12 23 21 18 12 23 22 1...

Page 14: ...263 278 290 278 300 316 330 317 341 360 376 357 384 405 423 394 424 448 467 LO PR 103 109 120 127 109 116 126 134 113 120 131 140 119 126 138 147 124 132 144 154 129 137 149 159 MBh 52 7 53 7 56 3 60...

Page 15: ...40 5 31 4 32 3 35 0 3 7 5 S T 0 76 0 6 8 0 51 0 33 0 78 0 7 0 0 5 3 0 34 0 80 0 72 0 54 0 3 5 0 8 3 0 74 0 56 0 36 0 8 6 0 77 0 58 0 37 0 87 0 7 8 0 5 9 0 38 Delta T 25 23 19 13 2 6 24 19 13 2 6 24 1...

Page 16: ...304 327 345 360 342 368 389 405 378 407 429 448 LO PR 109 116 126 134 115 122 133 142 119 127 139 148 125 133 146 155 131 140 153 163 136 145 158 168 MBh 39 7 40 5 42 4 45 2 38 8 39 5 41 4 44 1 37 8...

Page 17: ...34 0 80 0 7 2 0 5 4 0 35 0 82 0 74 0 56 0 3 6 0 8 5 0 76 0 58 0 37 0 8 8 0 79 0 60 0 38 0 89 0 8 0 0 6 0 0 39 Delta T 24 22 18 13 2 4 23 18 13 2 5 23 1 8 13 25 23 1 9 1 3 24 22 18 13 2 3 2 1 17 12 16...

Page 18: ...4 391 413 431 4 02 43 2 45 6 476 LO PR 106 113 123 1 31 11 2 11 9 130 1 39 1 17 124 135 14 4 122 1 30 1 42 15 1 12 8 137 149 159 1 33 14 1 15 4 164 MBh 56 3 5 7 3 60 1 64 1 54 9 56 0 5 8 7 6 2 6 5 3 6...

Page 19: ...D DB 75 OD DB 63 OD WB SSZ160601A CA F4860 6A TXV MBE2000 1 Conditions 80 F IDB 67 F IW B 1800 CFM Outdoor Temp F Total Btuh Sensible Btuh Latent Btuh Total Watts 75 36 330 25 939 10 391 2 276 80 35 8...

Page 20: ...urn Air Dry Bulb T emperature F 17 27 Pressures shown are for most popular match indoor unit WITHNO FROSTON OUTDOORCOIL Due to factors like airflow charge indoor coil frost pressures will vary signifi...

Page 21: ...sures w ill vary significantly Liquid service valve pressures should be 20 psig suction access port pressures should be 5 psig of the values listed in this chart 62 52 22 42 47 57 67 Indoor Return Air...

Page 22: ...ture F 17 27 37 32 Pressures show n are for most popular match indoor unit WITH NO FROST ONOUTDOOR COIL Due to factors like airflow charge indoor coil frost pressures will vary significantly Liquid se...

Page 23: ...18 7 17 6 16 9 16 6 15 6 14 8 14 1 13 5 12 8 12 5 12 3 11 6 10 8 10 2 9 3 8 4 COP 4 44 4 29 4 12 3 94 3 81 3 73 3 54 3 34 3 08 2 91 2 75 2 63 2 56 2 36 2 15 1 92 1 69 1 42 EER 15 2 14 7 14 1 13 5 13...

Page 24: ...42 47 57 67 Indoor Return Air Dry Bulb T emperature F High Stage Pressures shown are for most popular match indoor unit WITH NO FROST ON OUTDOOR COIL Due to factors like airflow charge indoor coil fr...

Page 25: ...sic Unit without Auxiliary Heat SSZ160481A CA F4860 6A TXV MBE2000 1 Conditions 1550 CFM 70 F Indoor Air Capacity of Unit With KW of Auxiliary heat capacity btuh c o p 4 8 9 6 14 4 19 2 65 71 65 4 44...

Page 26: ...B CA F4860 6A TXV MBE2000 1 Conditions 1200 CFM 70 F DB LOW STAGE Outdoor Ambient F Basic Unit without Auxiliary Heat Capacity of Unit With KW of Auxiliary heat capacity btuh c o p 4 8 9 6 14 4 19 2 6...

Page 27: ...ht increase will occur in indoor temperature drop Delta T A slight decrease will occur in low and high side pressures and power A properly operating unit should be within plus or minus 2 degrees of th...

Page 28: ...W PINK STRIPE WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE COMPONENT CODE C CONTACTOR CH CRANKCASE HEATER CM OUTDOOR FAN MOTOR COMP C...

Page 29: ...RESSURE SWITCH HVDR HIGH VOLTAGE DEFROST RELAY IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVDR LOW VOLTAGE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF RUN CAPACITOR FOR COMPRESSOR FAN RVC REVER...

Page 30: ...SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH SSZ160 60 1AB AC AD AE Wiring is subject to change always re...

Page 31: ...RMOSTAT DT DISCHARGE THERMOSTAT HPS HIGH PRESSURE SWITCH HVDR HIGH VOLTAGE DEFROST RELAY IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVDR LOW VOLTAGE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF...

Page 32: ...WITCH HVDR HIGH VOLTAGE DEFROST RELAY IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVDR LOW VOLTAGE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF RUN CAPACITOR FOR COMPRESSOR FAN RVC REVERSING VALV...

Page 33: ...FOR COMPRESSOR OPTIONAL CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION OUTDOOR POW ER SUPPLY SEE RATING PLATE WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HI...

Reviews: