SSZ160601A*
SPLIT SYSTEM HEATING PERFORMANCE
EXPANDED PERFORMANCE DATA
MODEL: SSZ160601A* / CA*F4860*6A* + TXV / MBE2000**-1
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
71.6
67.8
63.8
59.7
57.0
55.2
51.3
47.3
44.9
41.4
38.1
36.0
34.7
31.1
27.6
24.0
20.5
16.8
Delta T
36.9
34.9
32.8
30.7
29.3
28.4
26.4
24.3
23.1
21.3
19.6
18.5
17.8
16.0
14.2
12.4
10.6
8.6
KW
4.73
4.63
4.53
4.44
4.38
4.34
4.25
4.15
4.27
4.16
4.06
4.00
3.96
3.86
3.76
3.66
3.55
3.45
AMPS
21.7
20.0
18.7
17.6
16.9
16.6
15.6
14.8
14.1
13.5
12.8
12.5
12.3
11.6
10.8
10.2
9.3
8.4
COP
4.44
4.29
4.12
3.94
3.81
3.73
3.54
3.34
3.08
2.91
2.75
2.63
2.56
2.36
2.15
1.92
1.69
1.42
EER
15.2
14.7
14.1
13.5
13.0
12.7
12.1
11.4
10.5
9.9
9.4
9.0
8.7
8.1
7.3
6.6
5.8
4.9
HI PR
395
379
364
348
340
334
321
308
295
282
270
264
259
249
240
230
222
214
LO PR
133
124
116
106
101
97
89
79
71
64
56
52
50
43
37
31
27
21
High pressure is measured at the suction service valve ( the larger valve).
AMPS = Outdoor unit amps (comp.+fan)
Low pressure is measured at the gauge port connection.
KW = Total system power
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
*Note: Shaded area is ARI Rating Conditions at 47° outdoor ambient temberature