Goodman SSZ 16 SEER Technical Manual Download Page 19

19

PERFORMANCE DATA

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

25,200

18,540

6,660

1,645

80°

24,900

18,553

6,347

1,697

85°

24,600

18,559

6,041

1,749

90°

24,300

18,628

5,672

1,795

95°

24,000

18,690

5,310

1,841

100°

23,400

18,568

4,832

1,880

105°

22,800

18,428

4,372

1,919

110°

21,960

17,824

4,136

1,952

115°

21,120

17,213

3,907

1,986

95°

22,239

18,503

3,736

1,768

TVA Conditions @ 95° OD DB, 75° OD DB. 63° OD WB

SSZ160241A* / CA*F3636*6A*+TXV/ MBE1600**-1
Conditions: 80°F IDB, 67°F IWB @ 875 CFM

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

49,875

36,207

13,668

3,061

80°

49,281

36,231

13,050

3,158

85°

48,688

36,244

12,444

3,255

90°

48,094

36,379

11,715

3,340

95°

47,500

36,499

11,001

3,425

100°

46,313

36,261

10,051

3,497

105°

45,125

35,988

9,137

3,570

110°

43,463

34,808

8,655

3,632

115°

41,800

33,616

8,184

3,695

95°

44,015

36,134

7,881

3,290

SSZ160481A* / CA*F4860*6A*+TXV/ MBE2000**-1
Conditions: 80°F IDB, 67°F IWB @ 1550 CFM

TVA Conditions @ 95° OD DB, 75° OD DB. 63° OD WB

Outdoor

Tem p. ° F.

Total 

Btuh

Se ns ible

Btuh

La tent

Btuh

Total

  W a tts

75°

59,850

41,729

18,121

4,105

80°

59,138

41,757

17,381

4,239

85°

58,425

41,772

16,653

4,374

90°

57,713

41,927

15,786

4,493

95°

57,000

42,066

14,934

4,612

100°

55,575

41,791

13,784

4,712

105°

54,150

41,477

12,673

4,813

110°

52,155

40,116

12,039

4,901

115°

50,160

38,743

11,417

4,988

95°

52,818

41,645

11,173

4,423

T V A Con dition s  @  95° OD DB, 75° OD DB. 63° OD WB

SSZ16 06 01 A* / CA*F4 86 0*6 A*+TXV/ M BE2 00 0* *-1
Conditions: 8 0°F IDB, 6 7°F IW B @  18 00  CFM

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

36,330

25,939

10,391

2,276

80°

35,898

25,956

9,941

2,350

85°

35,465

25,966

9,499

2,424

90°

35,033

26,062

8,970

2,489

95°

34,600

26,149

8,451

2,554

100°

33,735

25,978

7,757

2,609

105°

32,870

25,783

7,087

2,665

110°

31,659

24,937

6,722

2,713

115°

30,448

24,083

6,365

2,760

95°

32,062

25,887

6,175

2,451

TVA Conditions @ 95° OD DB, 75° OD DB. 63° OD WB

SSZ160361A* / CA*F4860*6A*+TXV/ MBE2000**-1
Conditions: 80°F IDB, 67°F IWB @ 1200 CFM

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

42,221

28,720

13,501

2,729

80°

41,718

28,734

12,984

2,817

85°

41,215

28,749

12,467

2,906

90°

40,713

28,850

11,863

2,983

95°

40,210

28,951

11,259

3,061

100°

39,205

28,749

10,456

3,127

105°

38,200

28,546

9,654

3,193

110°

36,792

27,605

9,187

3,250

115°

35,385

26,664

8,721

3,307

95°

37,260

28,662

8,599

2,938

SSZ160601B* / CA*F4860*6A*+TXV/ MBE2000**-1
Conditions: 80°F IDB, 67°F IWB @ 1200 CFM LOW STAGE

TVA Conditions @ 95° OD DB, 75° OD DB. 63° OD WB

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

59,850

41,729

18,121

4,055

80°

59,138

41,751

17,387

4,182

85°

58,425

41,772

16,653

4,309

90°

57,713

41,919

15,794

4,422

95°

57,000

42,066

14,934

4,534

100°

55,575

41,772

13,803

4,629

105°

54,150

41,477

12,673

4,725

110°

52,155

40,110

12,045

4,807

115°

50,160

38,743

11,417

4,890

95°

52,800

41,712

11,088

4,356

SSZ160601B* / CA*F4860*6A*+TXV/ MBE2000**-1
Conditions: 80°F IDB, 67°F IWB @ 1800 CFM HIGH STAGE

TVA Conditions @ 95° OD DB, 75° OD DB. 63° OD WB

Summary of Contents for SSZ 16 SEER

Page 1: ...tion Models listed on page 3 RT6214002r10 February2014 Copyright 2006 2007 2009 2010 2012 2014 Goodman Manufacturing Company L P TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL M...

Page 2: ...re servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Installation and repair of this unit should be performed...

Page 3: ...Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise contact your local E...

Page 4: ...ompressors are inherently more tolerant of small quantities of liquid refrigerant NOTE Even though the compressor section of a Scroll com pressor is more tolerant of liquid refrigerant continued flood...

Page 5: ...ns 3 ton unit Unit is charged with refrigerant for 15 of 3 8 liquid line System charge must be adjusted per Installation Instructions Final Charge Procedure Installation of these units requires the sp...

Page 6: ...connections 4 5 ton units Installer will need to supply 3 4 to 7 8 adapters for suction line connections 3 ton unit Unit is charged with refrigerant for 15 of 3 8 liquid line System charge must be ad...

Page 7: ...0 82 0 73 0 55 0 36 0 85 0 76 0 57 0 37 0 87 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 93 0 83 0 63 0 41 0 94 0 84 0 64 0 41 Del t a T 21 19 16 11 21 20 16 11 21 20 16 11 21 20 16 11 21 19 16 11 20 18 15...

Page 8: ...263 278 289 278 299 316 329 316 340 360 375 356 383 404 422 393 423 447 466 LO PR 114 121 132 141 120 128 140 149 125 133 145 155 131 140 152 162 138 146 160 170 142 151 165 176 MBh 22 2 22 6 23 7 25...

Page 9: ...4 32 7 25 3 26 0 28 2 30 3 S T 0 79 0 71 0 54 0 35 0 82 0 74 0 56 0 36 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 90 0 81 0 61 0 39 0 91 0 81 0 62 0 40 Delta T 21 20 16 11 22 20 16 11 22 20 16 11 22 20...

Page 10: ...282 303 320 334 321 346 365 381 361 389 411 428 399 430 454 473 LO PR 110 117 128 137 117 124 135 144 121 129 141 150 127 135 148 157 133 142 155 165 138 147 160 171 MBh 32 0 32 6 34 2 36 4 31 3 31 9...

Page 11: ...8 34 7 35 8 38 7 41 5 S T 0 81 0 72 0 55 0 35 0 84 0 75 0 57 0 36 0 86 0 77 0 58 0 37 0 89 0 79 0 60 0 39 0 92 0 82 0 62 0 40 0 93 0 83 0 63 0 40 DeltaT 23 21 18 12 23 22 18 12 24 22 18 12 24 22 18 1...

Page 12: ...4 262 277 289 277 298 315 328 316 340 359 374 355 382 403 421 392 422 446 465 LO PR 112 119 130 139 118 126 138 147 123 131 143 152 129 138 150 160 136 144 157 168 140 149 163 173 MBh 43 9 44 8 46 9 5...

Page 13: ...53 8 41 7 42 9 46 4 49 8 S T 0 77 0 69 0 52 0 34 0 80 0 72 0 54 0 35 0 82 0 74 0 56 0 36 0 85 0 76 0 58 0 37 0 88 0 79 0 60 0 38 0 89 0 80 0 60 0 39 Delta T 23 21 17 12 23 21 18 12 23 21 18 12 23 22 1...

Page 14: ...263 278 290 278 300 316 330 317 341 360 376 357 384 405 423 394 424 448 467 LO PR 103 109 120 127 109 116 126 134 113 120 131 140 119 126 138 147 124 132 144 154 129 137 149 159 MBh 52 7 53 7 56 3 60...

Page 15: ...40 5 31 4 32 3 35 0 3 7 5 S T 0 76 0 6 8 0 51 0 33 0 78 0 7 0 0 5 3 0 34 0 80 0 72 0 54 0 3 5 0 8 3 0 74 0 56 0 36 0 8 6 0 77 0 58 0 37 0 87 0 7 8 0 5 9 0 38 Delta T 25 23 19 13 2 6 24 19 13 2 6 24 1...

Page 16: ...304 327 345 360 342 368 389 405 378 407 429 448 LO PR 109 116 126 134 115 122 133 142 119 127 139 148 125 133 146 155 131 140 153 163 136 145 158 168 MBh 39 7 40 5 42 4 45 2 38 8 39 5 41 4 44 1 37 8...

Page 17: ...34 0 80 0 7 2 0 5 4 0 35 0 82 0 74 0 56 0 3 6 0 8 5 0 76 0 58 0 37 0 8 8 0 79 0 60 0 38 0 89 0 8 0 0 6 0 0 39 Delta T 24 22 18 13 2 4 23 18 13 2 5 23 1 8 13 25 23 1 9 1 3 24 22 18 13 2 3 2 1 17 12 16...

Page 18: ...4 391 413 431 4 02 43 2 45 6 476 LO PR 106 113 123 1 31 11 2 11 9 130 1 39 1 17 124 135 14 4 122 1 30 1 42 15 1 12 8 137 149 159 1 33 14 1 15 4 164 MBh 56 3 5 7 3 60 1 64 1 54 9 56 0 5 8 7 6 2 6 5 3 6...

Page 19: ...D DB 75 OD DB 63 OD WB SSZ160601A CA F4860 6A TXV MBE2000 1 Conditions 80 F IDB 67 F IW B 1800 CFM Outdoor Temp F Total Btuh Sensible Btuh Latent Btuh Total Watts 75 36 330 25 939 10 391 2 276 80 35 8...

Page 20: ...urn Air Dry Bulb T emperature F 17 27 Pressures shown are for most popular match indoor unit WITHNO FROSTON OUTDOORCOIL Due to factors like airflow charge indoor coil frost pressures will vary signifi...

Page 21: ...sures w ill vary significantly Liquid service valve pressures should be 20 psig suction access port pressures should be 5 psig of the values listed in this chart 62 52 22 42 47 57 67 Indoor Return Air...

Page 22: ...ture F 17 27 37 32 Pressures show n are for most popular match indoor unit WITH NO FROST ONOUTDOOR COIL Due to factors like airflow charge indoor coil frost pressures will vary significantly Liquid se...

Page 23: ...18 7 17 6 16 9 16 6 15 6 14 8 14 1 13 5 12 8 12 5 12 3 11 6 10 8 10 2 9 3 8 4 COP 4 44 4 29 4 12 3 94 3 81 3 73 3 54 3 34 3 08 2 91 2 75 2 63 2 56 2 36 2 15 1 92 1 69 1 42 EER 15 2 14 7 14 1 13 5 13...

Page 24: ...42 47 57 67 Indoor Return Air Dry Bulb T emperature F High Stage Pressures shown are for most popular match indoor unit WITH NO FROST ON OUTDOOR COIL Due to factors like airflow charge indoor coil fr...

Page 25: ...sic Unit without Auxiliary Heat SSZ160481A CA F4860 6A TXV MBE2000 1 Conditions 1550 CFM 70 F Indoor Air Capacity of Unit With KW of Auxiliary heat capacity btuh c o p 4 8 9 6 14 4 19 2 65 71 65 4 44...

Page 26: ...B CA F4860 6A TXV MBE2000 1 Conditions 1200 CFM 70 F DB LOW STAGE Outdoor Ambient F Basic Unit without Auxiliary Heat Capacity of Unit With KW of Auxiliary heat capacity btuh c o p 4 8 9 6 14 4 19 2 6...

Page 27: ...ht increase will occur in indoor temperature drop Delta T A slight decrease will occur in low and high side pressures and power A properly operating unit should be within plus or minus 2 degrees of th...

Page 28: ...W PINK STRIPE WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE COMPONENT CODE C CONTACTOR CH CRANKCASE HEATER CM OUTDOOR FAN MOTOR COMP C...

Page 29: ...RESSURE SWITCH HVDR HIGH VOLTAGE DEFROST RELAY IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVDR LOW VOLTAGE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF RUN CAPACITOR FOR COMPRESSOR FAN RVC REVER...

Page 30: ...SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH SSZ160 60 1AB AC AD AE Wiring is subject to change always re...

Page 31: ...RMOSTAT DT DISCHARGE THERMOSTAT HPS HIGH PRESSURE SWITCH HVDR HIGH VOLTAGE DEFROST RELAY IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVDR LOW VOLTAGE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF...

Page 32: ...WITCH HVDR HIGH VOLTAGE DEFROST RELAY IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVDR LOW VOLTAGE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF RUN CAPACITOR FOR COMPRESSOR FAN RVC REVERSING VALV...

Page 33: ...FOR COMPRESSOR OPTIONAL CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION OUTDOOR POW ER SUPPLY SEE RATING PLATE WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HI...