TABLE 11
90 PLUS AIR FLOW PERFORMANCE
CFM @ ESP
MODEL
BLOWER/
SPEED
MOTOR HP
.1
.2
.3
.4
.5
.6
.7
UPFLOW MODELS
(-)GRL-04
11 x 7 /
1
/
2
LOW
805
780
760
720
685
645
605
*M-LO
920
885
850
810
775
730
690
M-HI
1140
1110
1085
1045
1010
950
890
HIGH
1360
1320
1280
1235
1195
1140
1080
(-)GRL-06
11 x 7 /
1
/
2
LOW
770
740
710
675
645
605
570
*M-LO
880
845
815
790
760
715
670
M-HI
1060
1025
990
960
925
880
835
HIGH
1260
1215
1175
1135
1100
1040
985
(-)GRL-09
12 X 11 /
3
/
4
LOW
1235
1210
1185
1150
1120
1075
1035
M-LO
1490
1465
1440
1405
1375
1315
1255
*M-HI
1720
1670
1620
1600
1580
1520
1460
HIGH
2100
2050
2000
1955
1910
1825
1745
* Factory-Set High Heating speed
A = 17
1
⁄
2
" Cabinet Size
B = 21" Cabinet Size
NOTE: Units tested with filters in place.
!
WARNING
GAS FURNACE (DIRECT
DRIVE) INSTRUCTIONS
FOR CHANGING BLOWER
SPEED
DISCONNECT THE ELECTRICAL
SUPPLY TO THE FURNACE
BEFORE ATTEMPTING TO
CHANGE THE BLOWER SPEED.
FAILURE TO DO SO CAN CAUSE
ELECTRICAL SHOCK RESULTING
IN PERSONAL INJURY OR DEATH.
The blower motor is wired for blower
speeds required for normal operation
as shown.
If additional blower speed taps are
available (leads connected to “M1”
and “M2” on the IFC), speeds may be
changed if necessary to fit
requirements of the particular
installation. Reconnect the unused
motor leads to “M1” or “M2.” Check
motor lead color for speed
designation.
Heating speeds should not be
reduced where it could cause the
furnace air temperature to rise to
exceed the maximum outlet air
temperature specified for the unit.
IMPORTANT:
Any combination of
motor taps to the IFC can be used
provided the temperature rise is
within the specified range when in
high or low heat and that there is
enough airflow in the cooling mode.
When changing the motor tap
speeds, the temperature rise must be
checked on both heat speeds and
temperature drop in cooling must be
checked again after the change is
made to ensure that the temperatures
are within the required specified
ranges.
MAINTENANCE
THESE INSTRUCTIONS ARE
INTENDED AS AN AID TO
QUALIFIED SERVICE
PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT
AND OPERATION OF THIS UNIT.
READ THESE INSTRUCTIONS
THOROUGHLY BEFORE
ATTEMPTING INSTALLATION
OR OPERATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS
MAY RESULT IN IMPROPER
INSTALLATION, ADJUSTMENT,
SERVICE OR MAINTENANCE,
POSSIBLY RESULTING IN FIRE,
ELECTRICAL SHOCK, CARBON
MONOXIDE POISONING,
EXPLOSION, PROPERTY
DAMAGE, PERSONAL INJURY
OR DEATH.
TABLE 12
FILTER SIZES
UPFLOW FILTER SIZES
FURNACE
INPUT
BOTTOM
SIDE
QUANTITY
WIDTH
MBTUH
SIZE
SIZE
17
1
/
2
"
45, 60
15
3
/
4
" X 25"
15
3
/
4
" X 25"
1
21"
90
19
1
/
4
" X 25"
15
3
/
4
" X 25"
1
!