Goodman GRL SERIES Installation Instructions Manual Download Page 37

37

90+ HIGH ALTITUDE
INSTRUCTIONS

NATURAL GAS

THE NATIONAL FUEL GAS CODE
(NFGC) GUIDELINES SHOULD BE
FOLLOWED WHEN CONVERTING
THESE FURNACES FOR HIGH
ALTITUDE OPERATION.

ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE
INPUT RATING BE ADJUSTED AND
THAT THE SIZE OF THE BURNER
ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS
HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT) NEED
TO BE CHANGED. THE FOLLOWING
EXAMPLES SHOW HOW TO
DETERMINE IF AN ORIFICE CHANGE
WILL BE NECESSARY AND HOW TO
DETERMINE THE NEW ORIFICE SIZE.

IN CANADA, AS AN ALTERNATE TO
SIZING THE BURNER ORIFICE, THE
MANIFOLD GAS PRESSURE MAY BE
ADJUSTED. THIS METHOD IS
COVERED LATER IN THIS SECTION.
THIS METHOD OF ADJUSTING
MANIFOLD PRESSURE MAY ONLY
BE USED IN CANADIAN
INSTALLATIONS.

34" 90 Plus furnaces installed at high
elevations require the installation of a
high altitude kit for proper operation. The
high altitude kit consists of a high
altitude pressure switch that replaces
the pressure switch attached to the
induced draft blower.

The pressure switch must be installed
at elevations above 5000 ft. Elevations
above 2000 ft. require the furnace to be
de-rated 4% per thousand feet.

The necessary high altitude kits to use
with -GRL furnace models are listed
below:

NOTE: 278 Option Code is available
on -GRL models.

Alternately, furnaces can be ordered
from the factory already converted for
high altitude elevations. The factory
option for high altitude elevations would
be ordered as a 278 option (example; a
90k BTU upflow furnace which is
factory converted for high altitude
elevations would have the model
number -GRL-09EZAJS

278

). These

factory converted furnaces come with a
pressure switch for high-altitude
elevations already attached. Also,
different burner orifices are installed at
the factory which are one drill size
smaller (#51 DMS) than standard -GRL
gas furnaces (#50 DMS). The smaller
orifice is installed to accommodate for
average heating values expected in
most high altitude areas and a required
4% per thousand feet reduction in input
as specified by the 

National Fuel Gas

Code (NFGC). Specific orifices should
always be recalculated for all high
altitude installations as outlined below.
Orifices should be changed, if
necessary, based on gas heating value
and elevation.

NOTE: 

Factory installed orifices are

calculated and sized based on a sea
level Natural Gas heating value of
1075 BTU per cubic ft. Regional
reduced heating values may nullify
the need to change orifices except at
extreme altitudes.

The following are examples of orifice
sizing using the National Fuel Gas
Code Appendix F. For a simplified
estimation of orifice size based on
heating value and elevation, use
Tables 5 and 6, however calculations
are the best method.

Example: 900 BTU/ft

3

Regional

Natural Gas Heating Value

I / H = Q
15000 / 900 = 16.68 ft

3

/hr

I = Sea Level input (per burner):
15000
H = Sea Level Heating Value: 900
Q = 16.68 ft

3

Natural Gas per hour.

From Table F.1 of 

National Fuel Gas

Code Handbook, 2002 (3.5” w.c.
column)
Orifice required at Sea Level: #48

From Table F.4 of 

National Fuel Gas

Code Handbook, 2002
Orifice required at 5000 ft. elevation
(4% de-rate per thousand ft.): #50
Orifice required at 8000 ft. elevation
(4% de-rate per thousand ft.): #51

!

CAUTION

!

CAUTION

Natural Gas Orifice Drill Size (4% per 1000 ft. De-Rate)

IMPORTANT: 90 Plus Models only. Do not use this chart for any 80 Plus Models.

Burner Input (per burner) 15,000 BTU @ Sea Level

Sea level

2000 to

3000 to

4000 to

5000 to

6000 to

7000 to

8000 to

to 1999 ft

2999 ft

3999 ft

4999 ft

5999 ft

5999 ft

7999 ft

8999 ft

47

48

48

49

49

49

50

50

48

49

49

49

50

50

50

51

49

50

50

50

51

51

51

52

50

51

51

51

51

52

52

52

51

51

52

52

52

53

53

53

Annual Avg. Heat

Value (btu per ft

3

)

850

900

1000

1075

1170

TABLE 6

High Altitude Kit

-GRL Furnace Inputs

45,000, 60,000

RXGY-F18

(17” cabinets)

RXGY-F20

90,000 (21”)

HIGH ALTITUDE KIT

Installer must make necessary burner
orifice and pressure switch changes as
indicated in the table below:

-GRL PRESSURE SWITCH CHANGES

INPUT

HIGH ALTITUDE

SET POINT

SET POINT

KIT NO.

HIGH FIRE

LOW FIRE

45,000

RXGY-F18

-1.08

NO CHANGE

60,000

RXGY-F18

-1.08

NO CHANGE

90,000

RXGY-F20

-1.15

NO CHANGE

NOTE:

Orifices are no longer supplied

with kit.

Summary of Contents for GRL SERIES

Page 1: ...92 24161 54 00 INSTALLATION INSTRUCTIONS FOR UPFLOW HIGH EFFICIENCY CONDENSING TWO STAGE GAS FURNACES GRL SERIES...

Page 2: ...air ______ no of elbows intake air ______ ft of pipe exhaust pipe ______ no of elbows exhaust pipe ______ Exhaust Vent Temperature TERMINATIONS DIRECT VENT VERTICAL ______ Intake 12 min above roof sno...

Page 3: ...equipment shipped for sale in California will have labels stating that the product contains and or produces Proposition 65 chemicals Although we have not changed our processes having the same label on...

Page 4: ...as Code NFPA54 and requirements or codes of the local utilities or other authorities having jurisdiction This is available from the following National Fire Protection Association Inc Batterymarch Park...

Page 5: ...OOR AIR REQUIRED FOR COMBUSTION RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55 F 13 C AND 80 F 27 C AND CLEAN FURNACE DUCT WORK AND COMPONENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS AND...

Page 6: ...over the heat exchanger If these are manual dampers they must be equipped to prevent heating or cooling operation unless the damper is in the full heat or cool position 3 IMPORTANT Install the furnac...

Page 7: ...s is recommended in front of all furnaces NOTE Use recommended 24 clearance if accessibility clearances are greater than fire protection clearances UPFLOW FURNACES ARE DESIGN CERTIFIED FOR INSTALLATIO...

Page 8: ...0 1 2 0 111 06 17 1 2 16 11 32 15 5 8 2 15 13 25 32 0 0 0 1 2 0 117 09 21 19 27 32 19 1 8 2 18 1 2 17 9 32 0 0 0 1 2 0 148 A service clearance of at least 24 inches is recommended in front of all fur...

Page 9: ...o air flow This can adversely affect furnace operation BE SURE TO CHECK AIR FLOW IMPORTANT When using outside air design and adjust the system to maintain a return air temperature ABOVE 55 F during th...

Page 10: ...RLY VENT THIS FURNACE CAN CAUSE CARBON MONOXIDE POISONING OR AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE PERSONAL INJURY OR DEATH This furnace removes both sensible and latent heat from the comb...

Page 11: ...opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe 6 After it has been determined that each appliance that remains connected t...

Page 12: ...mpounds increase the dew point temperature of the flue products and are highly corrosive after they condense ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO PR...

Page 13: ...l appliance input rating in the enclosure BTUH Free Area Round Pipe Input Each Opening Size 45 000 11 25 square inches 4 60 000 15 00 square inches 5 90 000 22 50 square inches 6 b Where communicating...

Page 14: ...nput Each Opening Size 45 000 15 00 square inches 4 60 000 16 67 square inches 5 90 000 30 00 square inches 6 b Not less than the sum of the areas of all vent connectors in the confined space If unit...

Page 15: ...OM INDOORS MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE 6 The minimum vent pipe length is 5 feet 7 Extend the exhaust pipe a minimum of 18 from the cabinet before turning vent...

Page 16: ...areas where dripping condensate may cause problems such as above planters patios or adjacent to windows where steam may cause fogging In addition to the minimum clearances listed above the vent locat...

Page 17: ...17 FIGURE 11 OTHER THAN DIRECT VENT TERMINAL CLEARANCES Natural Gas and Propane Installation Code National Fuel Gas Code Canadian Installations US Installations Canadian Installations US Installations...

Page 18: ...inimum clearances to combustibles are maintained between the PVC pipe and other pipes Minimum 3 ft clearance required between combustion air inlet and any other exhaust 5 For horizontal runs where wat...

Page 19: ...rom the wall for models with inputs of 45 000 and 60 000 BTUH Install a 2 in to 11 2 in coupling at the outside wall to prevent pushing the termination back into the wall See Figure 15 Detail A The co...

Page 20: ...ect vent termination kits MAINTAIN 12 IN MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL MAXIMUM OF 24 IN ABOVE ROOF NOTE Support must be field installed to secure termination kit to structure...

Page 21: ...XHAUST PITCHED ROOF INSTALLATIONS NOTES 1 SUPPORT HORIZONTAL PIPE EVERY FOUR FEET 2 WHEN 3 IN PIPE IS USED REDUCE TO 2 IN BEFORE PENETRATING OUTSIDE WALL 3 18 IN MAXIMUM 2 IN DIAMETER PIPE MAY BE USED...

Page 22: ...appliance or clothes dryer to prevent recirculation of the flue gases into the furnace combustion air inlet The only exception to this requirement is the case of multiventing two or more furnaces whi...

Page 23: ...23 FIGURE 17 DIRECT VENT TERMINAL CLEARANCES Natural Gas and Propane Installation Code National Fuel Gas Code Canadian Installations US Installations Canadian Installations US Installations...

Page 24: ...AL POSITION EXHAUST VENT 6 MINIMUM 10 RECOMMENDED MAXIMUM 1 DISTANCE FROM WALL MINIMUM 12 ABOVE GRADE SEE CONCENTRIC VENT INSTALLATION INSTRUCTIONS SEE CONCENTRIC VENT INSTALLATION INSTRUCTIONS TWO PI...

Page 25: ...e connection is a 2 in female PVC pipe fitting extending through the left side of the furnace top plate This opening has a protective cap which should be removed just prior to installing the exhaust p...

Page 26: ...w model only has a new drain system There is a third port on the drain trap marked by a red cap for the hose attached to the induced draft motor Remove plug in inducer drain hose and remove cap off dr...

Page 27: ...elbow pointing through the knockout Connect the 1 2 in pipe and tee as noted above Route the drain hoses behind the control box cut to the appropriate length and connect to the trap with hose clamps...

Page 28: ...P IGNITOR MANIFOLD GAS VALVE UNION DRIP LEG GROMMET IN NORMAL POSITION 4 TO 5 FEET ABOVE FLOOR REQ D BY SOME UTILITIES MANUAL GAS STOP BURNERS UPFLOW line as close to the furnace as possible Always us...

Page 29: ...CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE THE BURNER ORIFICES MAY OR MAY NOT NEED TO BE CHANGED SEE THE SECTION TITLED HIGH ALTITUDE INSTALLATIONS OF THIS BOOK FOR INSTRUCTIONS NOTE Furnace...

Page 30: ...he U Tube manometer 6 Replace the pressure tap plug before turning on the gas Turn on gas and check for leaks If the supply gas line pressure is above these ranges install an in line gas regulator to...

Page 31: ...496 Example LP Input BTU requirement of unit 120 000 Equivalent length of pipe 60 ft 3 4 IPS required 9 Note or adjust the manifold pressure to give A 1 7 w c for natural gas low fire B 4 8 w c for L...

Page 32: ...igure 28 NOTE If grounding screw is not replaced furnace will not operate Flame cannot be sensed THIS FURNACE IS EQUIPPED WITH A BLOWER DOOR SAFETY SWITCH DO NOT DISABLE THIS SWITCH FAILURE TO FOLLOW...

Page 33: ...install the thermostat on an outside wall or where it will be influenced by drafts concealed hot or cold water pipes lighting fixtures radiation from fireplace rays of sun lamps television radios or a...

Page 34: ...rly see Troubleshooting diagram IMPORTANT Only two furnaces on a single thermostat NOTE Furnaces that are twinned cannot share a common return or supply ducts TWO STAGE TWINNING OPERATION USING A SING...

Page 35: ...35 FIGURE 31 UT Electronic Controls 1095 104 IFC TWINNING CONNECTION SINGLE STAGE OPERATION...

Page 36: ...36 FIGURE 32 UT ELECTRONIC CONTROLS 1095 104 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION...

Page 37: ...ed 4 per thousand feet reduction in input as specified by the National Fuel Gas Code NFGC Specific orifices should always be recalculated for all high altitude installations as outlined below Orifices...

Page 38: ...12 600 12 000 11 400 10 800 10 200 9 600 All calculations are performed by using the first three columns of information only Before beginning any calculations determine the individual burner Btu size...

Page 39: ...is acceptable as described in Table 9 The information in Table 9 is based on a heating value of 1000 BTU per cubic feet of natural gas and 2500 BTU per cubic feet of LP gas IMPORTANT Actual input rat...

Page 40: ...f operation with a single stage thermostat a Connect the W terminal on the thermostat to the W2 terminal on the IFC Do not connect any wire to W on IFC when using a single stage thermostat b When ther...

Page 41: ...heat after 1st stage R and W2 thermostat contacts close calling for 2 stage heat The induced draft motor then switches to high speed and the high pressure switch contacts will close The gas valve swit...

Page 42: ...fire and 4 8 W C on low fire at the gas control valve For elevations up to 8 000 feet rating plate inputs apply For high altitudes elevations 5 000 ft and over the orifice spud must be changed SETTIN...

Page 43: ...re from the supply air temperature The difference is the temperature rise 5 Compare the measured temperature rise to the approved temperature rise range listed on the furnace name plate See Figure 37...

Page 44: ...requirements of the particular installation Reconnect the unused motor leads to M1 or M2 Check motor lead color for speed designation Heating speeds should not be reduced where it could cause the fur...

Page 45: ...1 FILTER FILTER SUPPORT ANGLE AE 61883 01 FILTER ROD SUPPORT ANGLE AE 60520 01 JACKET DRILL 2 3 16 DIA HOLES 8 000 4 875 1 531 CUT OUTUSING EMBOSSED ANGLES AS AGU IDE FOR PROPERSI ZE CUT OUT AND DRILL...

Page 46: ...r cleaners are used in the system it is important that the airflow is not reduced to maximize system performance and life Always verify that the system s airflow is not impaired by the filtering syste...

Page 47: ...47 FIGURE 39 TROUBLESHOOTING CHART Go to F Go to I HAZARDOUS VOLTAGE LINE VOLTAGE CONNECTIONS DISCONNECT POWER BEFORE SERVICING SERVICE MUST BE BY A TRAINED QUALIFIED SERVICE TECHNICIAN...

Page 48: ...48 FIGURE 39 TROUBLESHOOTING CHART CONTINUED Go to D Go to D Go to C Go to F 1...

Page 49: ...49 FIGURE 40 WIRING DIAGRAM UPFLOW DOWNFLOW HORIZONTAL BLOWER INDUCED DRAT GAS FIRED FORCED AIR FURNACE TWO STAGE HEAT SINGLE STAGE COOL DIRECT SPARK IGNITION...

Page 50: ...50...

Page 51: ...51...

Page 52: ...52 CM 0206...

Reviews: