Goodman GCH9 Installation Instructions Manual Download Page 20

20

U

PRIGHT

 D

RAIN

 T

RAP

 M

OUNTING

 (L

EFT

 

OR

 R

IGHT

 S

IDE

 P

ANEL

)

1. Insert drain tubes into drain trap and position the drain trap

against the side panel.  

NOTE:

  Drain tubes must reach the

bottom of the drain trap.

2. Secure drain trap to side panel at the mounting holes

(dimples or crosshairs on counterflow models) located
below the grommet drain holes.

3. Attach PVC drain line to drain trap outlet with either a 90°

elbow or coupling.

H

ORIZONTAL

 I

NSTALLATIONS

R

IGHT

 S

IDE

 D

OWN

Horizontal installations with the right side down require that the
drain hoses be connected to the right side front cover drain port
and the rubber elbow drain port.

NOTE:

  On counterflow models, relocation of the front cover pressure

switch hose is required.

Make connections as follows:

1. Remove the rubber plug from the coil front cover drain port.

Counterflow furnaces

Relocate the front cover pressure switch hose connection
from the left side pressure tap to the right (down) side tap.
The pressure switch hose must be connected to the down
side to guard against blocked drain conditions.   Cut hose
to appropriate length to minimize sagging.  Plug left
(unused) pressure tap with plug removed from right side.

2. Secure Hose A to front cover drain tap with a red hose clamp.

Route hose to rear right (down) side panel grommet holes.

HOSE A

HOSE B

SIDE PANEL

GROMMET

HOLES

GREEN

HOSE

CLAMP

(3 PLACES)

TUBE 1

RIGHT

SIDE

 PANEL

TUBES 2

RUBBER ELBOW

DRAIN PORT

FRONT
COVER

PRESSURE 

TAP

RED HOSE

CLAMP

SILVER HOSE

CLAMP

Horizontal Connections - Right Side Down

(Upflow Shown, Counterflow Similar)

3. Cut 1/4 inch from the end of the drain port on the rubber

elbow and discard.

4. Insert Tube 1 into rubber elbow drain port and secure with

a silver hose clamp. Angle tube outward toward front of
furnace.

5. Cut 17 3/4 inches from the long end (end opposite the

bend) of Hose B, discarding the 17 3/4 inch piece and
saving the part with the bend.

6. Secure remaining end of Hose B to exposed end of Tube 1

with a green hose clamp.  Route hose to front right down
side panel grommet holes.

7. Cut 5 1/2 inches straight length from the long end (end with

the taper) of each Tube 2. Save the 5 1/2 inch long pieces
and discard the pieces with the bend.

8. Insert approximately one inch of each Tube 2 through the

right down side panel grommet holes.  Secure tubes to
Hose A and Hose B using green hose clamps.  Ensure
hoses and tubes maintain a downward slope for proper
drainage and are not kinked or bound.

For details concerning mounting of the drain trap, refer to 

Section

X, Condensate Drain Lines and Drain Trap - Horizontal Drain Trap
Mounting (left or right side panel).

L

EFT

 S

IDE

 D

OWN

Horizontal installations with the left side panel down will require
drain hoses to be connected to the left side front cover drain port
and the side drain port on the rubber elbow.

1. Remove the rubber plug from the coil front cover left (down)

side drain port.

2. Relocate the front cover pressure switch hose connection

from the right side (as shipped) pressure tap to the left
(down) side tap.  The pressure switch hose must be
connected to the down side to guard against blocked drain
conditions.  Cut hose to appropriate length to minimize
sagging.  Plug right (unused) pressure tap with plug
removed from left side.

3. Secure Hose A to front cover drain port with a red hose

clamp. Route hose to rear left (down) side panel grommet
holes.  

NOTE:

  For left side drainage, grommets must be

relocated to left side panel.

LEFT SIDE

 PANEL

FRONT COVER

DRAIN PORT

SIDE PANEL

GROMMET

HOLES

DRAIN TRAP

TUBE(S) 2

GREEN HOSE

CLAMPS

(3 PLACES)

HOSE A

HOSE B

INDUCED

DRAFT BLOWER

DRAIN PORT

FRONT

COVER

PRESSURE

TAP

RED HOSE CLAMP

Horizontal Connections - Left Side Down

(Upflow Shown, Counterflow Similar)

4. Remove the rubber cap from the side drain port on the

rubber elbow.

5. Secure the short end of Hose B to rubber elbow side drain

port using a green hose clamp. 

NOTE:

  For left side drainage,

route hose to far left (down) side panel grommet holes.

NOTE: 

Horizontal left side connections (when using new

side port drain elbow) does not require connecting a hose
to the induced draft blower housing.

6. Cut 5 1/2 inches straight length from the long end (end with

a taper) of each Tube 2. Save the 5 1/2 inch long pieces and
discard the pieces with the bends.

7. Insert approximately one inch of each Tube 2 through left

side panel grommet hole.  Secure tubes to Hose A and
Hose B with a green hose clamps.   

NOTE:

  Tube must

reach bottom of trap.  Ensure hoses and tubes maintain a
downward slope for proper drainage and that they are not
kinked or binding.

For details concerning mounting of the drain trap, refer to 

Section

X, Condensate Drain Lines and Drain Trap - Horizontal Drain Trap
Mounting (left or right side panel).

Summary of Contents for GCH9

Page 1: ...tall the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of s...

Page 2: ...ER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 14 STANDARD FURNACE CONNECTIONS 14 ALTERNATE FURNACE CONNECTIONS 14 NON DIRECT VENT SINGLE PI...

Page 3: ...XVIII Troubleshooting 32 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 32 DIAGNOSTIC CHART 32 FAULT RECALL 32 RESETTING FROM LOCKOUT 32 XIX Maintenance 32 ANNUAL INSPECTION 32 FILTERS 32 BURNERS 33 INDUCED...

Page 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty cer tificate in a safe location for future reference If additional informatio...

Page 5: ...e Pipe Connection Alternate 15 Rubber Elbow 16 Induced Draft Blower 17 Electrical Connection Inlets Alternate 18 Coil Front Cover Pressure Tap 19 Coil Front Cover Drain Port 20 Drain Line Penetrations...

Page 6: ...The input rate and temperature rise are set per the furnace rating plate 100 outside air is provided for combustion air requirements during construction Temporary ducting can be used II SAFETY II SAF...

Page 7: ...ly air opening and the combustible floor Exposure to contaminated combustion air will result in safety and performance related problems Do not install the furnace where the combustion air is exposed t...

Page 8: ...tions of use g If improper venting is observed during any of the above tests the common venting system must be corrected halogen type refrigerants cleaning solutions such as perchloroethylene printing...

Page 9: ...ipping heavily insulated caulked vapor barrier etc addi tional air may need to be provided using the methods described in 5 3 3 b or 5 3 4 Space Unconfined For purposes of this Code a space whose volu...

Page 10: ...directly with an additional room s of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space The total input of all gas utilization equipment installed...

Page 11: ...ropriate in stallation positions ductwork connections and resulting airflow arrangements VII HO VII HO VII HO VII HO VII HORIZO RIZO RIZO RIZO RIZONT NT NT NT NTAL APPLI AL APPLI AL APPLI AL APPLI AL...

Page 12: ...s require an orifice change to compensate for the energy content difference between natural and propane gas High altitude installations may require both a pressure switch and an orifice change These c...

Page 13: ...nt flue pipe and a combustion air intake pipe Refer to the appropriate section for details concerning piping size length number of elbows furnace connections and terminations MATERIALS AND JOINING MET...

Page 14: ...rd against inadvertent blockage COMBUSTION AIR PIPE DIRECT VENT INSTALLATIONS On upflow units secure the combustion air intake pipe directly to the air intake coupling On counterflow units secure the...

Page 15: ...LT IN LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES INCLUDING CARBON MONOXIDE 7 Upflow and Counterflow units For upright installations externally mount the rubber elbow to the ven...

Page 16: ...r of elbows in the piping system Pipe Size 4 inc 2 3 4 5 6 7 8 045_3 2 68 65 62 59 56 53 50 070_3 2 68 65 62 59 56 53 50 070_4 2 46 43 40 2 16 13 10 3 68 65 62 59 56 53 50 090_5 3 68 65 62 59 56 53 50...

Page 17: ...ter pipe can be used in place of 2 diameter pipe 4 Increased Clearance Configurations using 2 45 deg Long Sweep elbows should be considered equivalent to one 90 deg elbow VENT FLUE AND COMBUSTION AIR...

Page 18: ...furnace NOTE If the alternate vent flue outlet is utilized in an upright installation the drain trap and drain connections must be located on the same side as the alternate vent flue outlet In horizon...

Page 19: ...Hose B with green hose clamps Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding For details concerning mounting of the drain trap refer to S...

Page 20: ...ht down side panel grommet holes Secure tubes to Hose A and Hose B using green hose clamps Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or bound For details...

Page 21: ...must be sized in accordance with the maximum overcurrent pro tection specified on the unit rating plate An electrical disconnect must be provided at the furnace location NOTE Line polarity must be ob...

Page 22: ...Blower pressure switch is powered anytime the pressure switch is closed and provides 24 VAC humidifier control Remove the yellow wire and connect the supplied brown jumper wire to the pressure switch...

Page 23: ...plying the furnace must be properly sized based on the gas flow required specific gravity of the gas and length of the run The gas line installation must comply with local codes or in their absence wi...

Page 24: ...ctors and semi rigid tubing against physical and thermal damage when installed Ensure aluminum alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry...

Page 25: ...ne gas leak Rust can reduce the level of odorant in propane gas Do not rely on your sense of smell Contact a local propane gas supplier about installing a gas detecting warning system If the presence...

Page 26: ...uipped with means to prevent operation of either unit unless the damper is in the full heat or cool position When the furnace is installed without a cooling coil it is recom mended that a removable ac...

Page 27: ...bility of flue gases escaping through the drain system FURNACE OPERATION Purge gas lines of air prior to startup Be sure not to purge lines into an enclosed burner compartment Check for leaks using an...

Page 28: ...NT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR...

Page 29: ...rtially open position 2 Place thermometers in the return and supply ducts as close to the furnace as possible Thermometers must not be influenced by radiant heat by being able to see the heat exchange...

Page 30: ...MODE DIP SWITCH IS SET TO 2 STG POSITION The normal operational sequence in sequence is as follows R and W thermostat contacts close initiating a call for heat Integrated control module performs safet...

Page 31: ...Y CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION GENERAL A number of safety circuits are employed to ensure safe and proper furnace...

Page 32: ...e least recent fault RESETTING FROM LOCKOUT Furnace lockout results when a furnace is unable to achieve igni tion after three attempts during a single call for heat It is character ized by a non funct...

Page 33: ...AME SENSOR QUALIFIED SERVICER ONLY Under some conditions the fuel or air supply can create a nearly invisible coating on the flame sensor This coating acts as an insulator causing a drop in the flame...

Page 34: ...E LEA RE LEA RE LEAVIN VIN VIN VIN VING AN INST G AN INST G AN INST G AN INST G AN INSTALL ALL ALL ALL ALLA A A A ATI TI TI TI TIO O O O ON N N N N Cycle the furnace with the thermostat at least three...

Page 35: ...kage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked p...

Page 36: ...e due to improper gas pressure or combustion air Induced draft blower and circulator blower runs continuously No furnace operation Integrated control module diagnostic LED is flashing FIVE 5 flashes F...

Page 37: ...NT COVER PRESSURE SWITCH N O C GY BK PLUG CONNECTION FIELD SPLICE SWITCH TEMP OR 24V THERMOSTAT CONNECTIONS GR GND 115 VAC 24 VAC BLOWER COMPARTMENT DOOR SWITCH OPEN WHEN DOOR OPEN DOOR SWITCH BK GND...

Reviews: