SS-CPH90-150
www.goodmanmfg.com
5
P
roduCt
S
PeCifiCationS
— 10 t
onS
CPH120
XXX3BXXX
CPH120
XXX4BXXX
CPH120
XXX7BXXX
Cooling Capacity
Total BTU/h
118,000
118,000
118,000
Sensible BTU/h
87,300
87,300
87,300
EER / IEER
11.5 / 11.5
11.5 / 11.5
11.5 / 11.5
Decibels
83
83
83
Heating Capacity
BTU/h (47° F)
120,000
120,000
120,000
COP (47°F)
3.4
3.4
3.4
BTU/h (17° F)
56,000
56,000
56,000
COP (17°F)
2.4
2.4
2.4
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
4,000
4,000
4,000
Indoor motor FLA (Cooling)
7.8
3.9
2.5
Horsepower - RPM
2.0/1725
2.0/1725
2.0/1725
Piston Size (Cooling)
0.086
0.086
0.086
Expansion Device
Orifice
Orifice
Orifice
Filter Size
(4) 16" x 24" x 2"
(4) 16" x 24" x 2"
(4) 16" x 24" x 2"
Drain Size (NPT)
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1 & #2 (oz.)
225 / 225
225 / 225
225 / 225
Evaporator Coil Face Area (ft²)
10.2
10.2
10.2
Rows Deep/ Fins per Inch
4 / 14
4 / 14
4 / 14
Belt Drive Evap Fan Data
# of Wheels (D x W)
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt
AX51
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,125
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
7,200
7,200
7,200
Face Area (ft²)
32.4
32.4
32.4
# Coils / Rows Deep - Fins per Inch
2 / 2 - 22
2 / 2 - 22
2 / 2 - 22
Piston Size (Heating)
0.064
0.064
0.064
Compressor
Quantity / Type / Stage
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
Compressor RLA / LRA ea.
16 / 110.0
7.8 / 52.0
5.7 / 38.9
Electrical Data
Voltage/Phase/ Frequency
208-230/3/60
460/3/60
575/3/60
Belt-Driven Standard Max Static
1.4
1.4
1.4
Outdoor Fan RLA ea.
2.40
1.20
0.90
Total Unit Amps
45
22
16
Min. Circuit Ampacity¹
49
24
17
Max. Overcurrent Protection (amps)²
60
30
20
Entrance Power Supply & Control Voltage
Locating Dimple
Operating Weight (lbs)
1285
1285
1285
Ship Weight (lbs)
1310
1310
1310
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.