P
roduCt
S
PeCifiCationS
P
roduCt
S
PeCifiCationS
SS-CPH90-150
www.goodmanmfg.com
23
H
eat
k
it
e
leCtriCal
d
ata
— 12½ t
onS
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor for 480V Units
Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage, use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
kw C
orreCtion
f
aCtorS
Model and
Heat Kit Usage
MCA
¹
at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH150***3B***
65
80
EHK3-16
110
110
15
4000 - 5600
EHK3-30
155
175
30
4300 - 5600
EHK3-45
194
200
43
4500 - 5600
Model and
Heat Kit Usage
MCA
¹
at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH150***4B***
31
40
EHK4-16
54
60
15
4000 - 5600
EHK4-30
76
80
30
4300 - 5600
EHK4-45
96
100
43
4500 - 5600
Model and
Heat Kit Usage
MCA
¹
at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH150***7B***
23
30
EHK7-16
42
45
15
4000 - 5600
EHK7-30
61
70
30
4300 - 5600
EHK7-45
77
80
43
4500 - 5600
¹ Minimum Circuit Ampacity (standard drive)
² Maximum Overcurrent Protection device (standard drive)