Goodman CPH COMMERCIAL SS-CPH90-150 User Manual Download Page 3

P

roduCt

 S

PeCifiCationS

P

roduCt

 S

PeCifiCationS

SS-CPH90-150

  

www.goodmanmfg.com 

3

P

roduCt

 S

PeCifiCationS

 — 7½ t

onS

CPH090 

XXX3BXXX

CPH090 

XXX4BXXX

CPH090 

XXX7BXXX

Cooling Capacity

Total BTU/h

90,000

90,000

90,000

Sensible BTU/h

65,700

65,700

65,700

EER / IEER

11.5 / 11.2

11.5 / 11.2

11.5 / 11.2

IPLV

12.30

12.30

12.30

Decibels

83

83

83

AHRI Reference #s

3000984

3000984

3000984

Heating Capacity

BTU/h / COP (47° F)

90,000 / 3.5

90,000 / 3.5

90,000 / 3.5

BTU/h / COP (17° F)

55,500 / 2.4

55,500 / 2.4

56,500 / 2.4

Evaporator Motor / Coil

Motor Type

Belt Drive

Belt Drive

Belt Drive

Indoor Nominal CFM

3,000

3,000

3,000

Indoor Motor FLA (Cooling)

7.8

3.9

2.5

Horsepower - RPM

2.0 - 1725

2.0 - 1725

2.0 - 1725

Piston Size (Cooling)

0.076

0.076

0.078

Filter Size

16" x 24" x 2"

16" x 24" x 2"

16" x 24" x 2"

Drain Size (NPT)

¾"

¾"

¾"

R-410A Refrigerant Charge: Cir #1 / #2 (oz.)

215 / 215

215 / 215

200 / 200

Evaporator Coil Face Area (ft²)

10.2

10.2

10.2

Rows Deep / Fins per Inch

4 / 16

4 / 16

4 / 16

Belt Drive Evap Fan Data

# of Wheels (D x W)

1  (15" x 12")

1  (15" x 12")

1  (15" x 12")

Motor Sheave / Blower Sheave

VL40 / AK74

VL40 / AK74

VL40 / AK74

Belt 

AX51

AX51

AX51

Condenser Fan / Coil
Quantity of Condenser Fan Motors

2

2

2

Horsepower - RPM

¼ - 1090

¼ - 890

¼ - 1075

Fan Diameter / # Fan Blades

22 / 4

22 / 4

22 / 4

Outdoor Expansion Device

0.052

0.052

0.055

Outdoor Nominal CFM

7,600

7,600

7,600

Face Area (ft²) 

32.4

32.4

32.4

# Coils / Rows Deep - Fins per Inch

2 / 2 - 20

2 / 2 - 20

2 / 2 - 20

Piston Size (Heating)

0.052

0.052

0.055

Compressor
Quantity / Type / Stage

2 / Scroll / 1

2 / Scroll / 1

2 / Scroll / 1

Compressor RLA  / LRA

13.1 / 83.1

6.1 / 41.0

4.4 / 33.0

Electrical Data

Voltage / Phase / Frequency

208-230 / 3 / 60

460 / 3 / 60

575 / 3 / 60

Indoor Blower HP / FLA

1.5 / 5.0

1.5 / 2.5

2 / 2.5

Outdoor Fan HP / FLA

¼ / 1.4

¼ / 0.8

¼ / 0.6

Total Unit Amps

36.9

17.7

12.5

Min. Circuit Ampacity¹

40

19

13.6

Max. Overcurrent Protection (amps)²

50

25

15

Entrance Power Supply & Control Voltage

Locating Dimple

Operating Weight (lbs)

1135

1135

1135

Ship Weight (lbs)

1175

1175

1175

¹  Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

²   May use fuses or HACR-type circuit breakers of the same size as noted.

Note:

 Always check the S&R plate for electrical data on the unit being installed.

Summary of Contents for CPH COMMERCIAL SS-CPH90-150

Page 1: ...utility entry AHRI Certified ETL Listed Cabinet Features Heavy gauge galvanized steel cabinet with UV resistant powder paint finish Full Perimeter Rail Curb Fit CPH Commercial up to 11 5 EER up to 3 5...

Page 2: ...ns 400 400 000 BTU h 025 25 kW 075 75 kW X No Op ons A Down ow Economizer Voltage Supply Fan Drive Type Motors 1 208V 1 Phase 4 460V 3 Phase B Belt Drive 2 220 240V 1 Phase 50 Hz 5 380 415V 3 Phase 50...

Page 3: ...or Sheave Blower Sheave VL40 AK74 VL40 AK74 VL40 AK74 Belt AX51 AX51 AX51 Condenser Fan Coil Quantity of Condenser Fan Motors 2 2 2 Horsepower RPM 1090 890 1075 Fan Diameter Fan Blades 22 4 22 4 22 4...

Page 4: ...15 x 12 Motor Sheave Blower Sheave VL40 AK74 VL40 AK74 VL40 AK74 Belt AX51 AX51 AX51 Condenser Fan Coil Quantity of Condenser Fan Motors 2 2 2 Horsepower RPM 1 4 1 090 1 4 890 1 4 1 075 Fan Diameter...

Page 5: ...15 x 15 1 15 x 15 Motor Sheave Blower Sheave VL40 AK74 VL40 AK74 VL40 AK74 Belt AX51 AX51 AX51 Condenser Fan Coil Quantity of Condenser Fan Motors 2 2 2 Horsepower RPM 1 075 1 075 1 125 Fan Diameter F...

Page 6: ...er Sheave VL40 AK66 VL40 AK66 VL40 AK66 Condenser Fan Coil Quantity of condenser Fan Motors 2 2 2 Horsepower RPM 1 075 1 075 1 075 Fan Diameter Fan Blades 22 3 22 3 22 3 Outdoor Nominal CFM 7 200 7 20...

Page 7: ...99 91 81 73 65 57 53 51 43 37 32 28 22 CPH120 Outdoor Ambient Temperature 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 5 10 MBh 150 8 142 8 134 4 125 6 120 0 116 3 108 0 99 6 87 7 81 0 74 6 70 4 67 8...

Page 8: ...0 77 0 58 0 38 0 89 0 79 0 60 0 39 0 91 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 96 0 86 0 65 0 42 T 20 19 15 11 21 19 16 11 21 19 16 11 21 19 16 11 20 19 15 11 19 18 14 10 kW 6 24 6 36 6 55 6 75 6 69 6 8...

Page 9: ...4 414 445 470 490 Lo PR 106 113 123 131 112 119 130 139 116 124 135 144 122 130 142 151 128 136 149 159 133 141 154 164 85 3375 MBh 92 9 94 7 99 2 105 8 90 7 92 5 96 8 103 3 88 6 90 3 94 5 100 9 86 4...

Page 10: ...0 86 0 77 0 58 0 37 0 88 0 79 0 59 0 38 0 91 0 81 0 61 0 39 0 94 0 84 0 64 0 41 0 95 0 85 0 64 0 41 T 20 19 15 11 20 19 15 11 20 19 15 11 21 19 16 11 20 19 15 11 19 17 14 10 kW 7 24 7 38 7 59 7 81 7 7...

Page 11: ...1 421 453 478 499 LO PR 104 111 121 128 110 117 127 136 114 121 132 141 120 127 139 148 126 134 146 155 130 138 151 161 85 3820 MBh 105 3 107 3 112 4 119 9 102 8 104 8 109 8 117 1 100 4 102 3 107 1 11...

Page 12: ...1 109 4 112 6 121 9 130 8 103 9 107 0 115 8 124 3 96 3 99 1 107 3 115 1 S T 0 84 0 76 0 57 0 37 0 88 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 93 0 83 0 63 0 40 0 96 0 86 0 65 0 42 0 97 0 87 0 66 0 42 T 20...

Page 13: ...7 435 468 494 516 Lo Pr 105 112 122 130 111 118 129 137 115 123 134 143 121 129 141 150 127 135 147 157 131 140 152 162 85 4500 MBh 121 8 124 1 130 0 138 7 118 9 121 2 127 0 135 5 116 1 118 4 124 0 13...

Page 14: ...0 56 0 36 0 85 0 76 0 57 0 37 0 88 0 78 0 59 0 38 0 91 0 81 0 62 0 40 0 92 0 82 0 62 0 40 T 23 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 23 21 17 12 21 20 16 11 kW 10 55 10 77 11 11 11 46 11 36 11...

Page 15: ...0 497 518 LO PR 98 105 114 122 104 111 121 129 108 115 126 134 114 121 132 140 119 127 138 147 123 131 143 152 85 4725 MBh 150 7 153 6 160 9 171 6 147 2 150 0 157 1 167 6 143 7 146 4 153 4 163 6 140 2...

Page 16: ...ndard Belt Drive Horizontal ESP In H2 O Turns Open 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 1 3625 701 1 08 3309 660 0 86 0 3 3815 797 1 44 3468 747 1 11 3...

Page 17: ...Belt Drive Horizontal ESP In H2 O Turns Open 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 1 3475 698 1 05 3159 657 0 83 0 3 3665 794 1 41 3318 744 1 08 3027 7...

Page 18: ...367 995 2 41 3845 954 1 91 1 4 4550 1064 2 83 4290 1042 2 56 3913 1006 2 13 1 6 4327 1087 2 73 3990 1057 2 37 1 8 4652 1148 3 33 4023 1105 2 58 2 4306 1162 3 05 Standard Belt Drive Horizontal ESP In H...

Page 19: ...izontal ESP in W C Turns Open 0 1 2 3 4 5 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 2 5570 2 27 4935 1 70 4584 1 36 0 4 5871 3 20 5639 2 77 5307 2 31 4902 1 88 4637 1 55 4178 1 19 0 6 5610 3 0...

Page 20: ...4 16 42 45 15 3000 3375 CFM EHK4 30 64 70 30 3000 3375 CFM EHK4 45 84 90 43 3000 3375 CFM Model and Heat Kit Usage MCA at 208 240V MOP amps at 208 240V Actual kW at 240V Recommended Airflow Range CPH0...

Page 21: ...amps at 575V Actual kW at 575V Recommended Airflow Range Downshot Recommended Airflow Range Horizontal CPH102 7B 17 20 EHK7 16 36 40 15 3400 3825 CFM 3400 3825 CFM EHK7 30 55 60 30 3400 3825 CFM 3400...

Page 22: ...MOP amps at 208 240V Actual kW at 240V Recommended Airflow Range CPH120 3B 49 60 EHK3 16 81 94 90 100 15 3500 4500 CFM EHK3 30 122 139 125 150 35 3500 4500 CFM EHK3 45 154 178 175 200 43 4000 4500 CF...

Page 23: ...Model and Heat Kit Usage MCA at 208 240V MOP amps at 208 240V Actual kW at 240V Recommended Airflow Range CPH150 3B 65 80 EHK3 16 110 110 15 4000 5600 EHK3 30 155 175 30 4300 5600 EHK3 45 194 200 43...

Page 24: ...TURN SUPPLY 5 3 8 7 1 2 6 1 2 99 1 8 61 3 4 Y NOTE For horizontal discharge remove the supply and return duct covers and place them over the vertical discharge return and supply openings Install with...

Page 25: ...proper unit operation Leave a total clearance of 75 on the main control panel side of the unit for possible removal of fan shaft coil electric heat and gas furnace Leave a clearance of 48 on all other...

Page 26: ...ior to installing the unit Duct work dimensions are shown in Roof Curb Installation Instructions Manual Refer to the Roof Curb Installation Instructions for proper curb installation Curbing must be in...

Page 27: ...ocating and mounting the curb and package unit Duct work must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimet...

Page 28: ...mbers 0907 and below Wiring is subject to change Always refer to the wiring diagram or the unit for the most up to date wiring Warning High Voltage Disconnect all power before servicing or installing...

Page 29: ...numbers 0907 and below Wiring is subject to change Always refer to the wiring diagram or the unit for the most up to date wiring Warning High Voltage Disconnect all power before servicing or installin...

Page 30: ...YL RD T1 T3 T2 COMP2 WH BL BL BL BK T1 T3 T2 C RD EM BK OR BL BK 2 0 8 2 4 0 4 6 0 5 7 5 3 6 0 BK BC BK F RCCF2 C BK BL BR RD PU CMC T1 T2 L1 L2 OR C F 3 2 1 9 6 8 7 4 5 WH YL PU WH BL BL Y Y2 WH GR...

Page 31: ...LE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY 4 FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE EBTDR CC1 DC EBTDR TB1 HPS1 LPS1 LOW VOLTAGE LINE VOLTAGE FIELD WIRING LOW VOLTAGE OPTI...

Page 32: ...BK T1 T3 T2 C RD EM BK OR BL BK 2 0 8 2 4 0 4 6 0 5 7 5 3 6 0 BK BC BK F RCCF2 C BK BL BR RD PU CMC T1 T2 L1 L2 OR C F 3 2 1 9 6 8 7 4 5 WH YL PU WH BL BL Y Y2 WH GR PU YL OR TB1 RD BR H T O R W2 T Y1...

Page 33: ...PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY 4 FOR TWO STAGE OPERATION REMOVE W1 TO W2 JUMPER WIRE EBTDR CC1 DC EBTDR TB1 HPS1 LPS1 LOW VOLTAGE LINE VOLTAGE FIELD WIRING LOW VOLTAGE OPTION...

Page 34: ...0 Downflow Economizer 7 10 tons DNECONHP150 Downflow Economizer 12 tons DNSQRRND90 Downflow Square to Round Adapter 20 Round 7 tons Electric Heat Kits HSKT090 High Static Kit for 7 ton CPH AA 8 ton CP...

Page 35: ...Product Specifications SS CPH90 150 www goodmanmfg com 35 Notes...

Page 36: ...H90 150 Goodman Manufacturing Company L P reserves the right to discontinue or change at any time specifications or designs without notice or without incurring obligations 2010 Goodman Manufacturing C...

Reviews: