SS-CPC90-150
H
eat
K
it
e
lectrical
d
ata
(B
lower
o
nly
, H
eat
M
ode
) — 12½ t
onS
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC150***3B***
65
80
EHK3-16
65
80
15
4000 - 5600
EHK3-30
102
110
30
4300 - 5600
EHK3-45
141
150
43
4500 - 5600
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC150***4B***
31
40
EHK4-16
31
40
15
4000 - 5600
EHK4-30
51
60
30
4300 - 5600
EHK4-45
71
80
43
4500 - 5600
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPC150***7B***
23
30
EHK7-16
24
30
15
4000 - 5600
EHK7-30
43
45
30
4300 - 5600
EHK7-45
59
60
43
4500 - 5600
¹ Minimum Circuit Ampacity (standard drive)
² Maximum Overcurrent Protection device (standard drive)
Kw c
orrection
f
actorS
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.