SS-CPC90-150
www.goodmanmfg.com
13
h
Eat
k
it
E
lECtRiCal
d
ata
(B
lowER
o
nly
, h
Eat
m
odE
) — 10 t
ons
m
inimum
a
iRflow
foR
E
lECtRiC
h
Eat
Heater Size (kW)
Min. CFM
Down-shot
Min. CFM
Horizontal
15
4,000
4,000
30
4,000
4,000
43
4,000
4,000
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC120***3B***
49
60
EHK3-16
48 / 55
50 / 60
15
3500 - 4500 CFM
EHK3-30
87 / 100
90 / 100
30
3500 - 4500 CFM
EHK3-45
121 / 139
125 / 150
43
4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC120***3H***
50
60
EHK3-16
49 / 57
50 / 60
15
3500 - 4500 CFM
EHK3-30
88 / 102
90 / 110
30
3500 - 4500 CFM
EHK3-45
122 / 141
125 / 150
43
4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC120***4B***
24
30
EHK4-16
27
30
15
3500 - 4500 CFM
EHK4-30
50
50
30
3500 - 4500 CFM
EHK4-45
70
70
43
4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPC0120***7B***
17
20
EHK7-16
22
25
15
3500 - 4500 CFM
EHK7-30
41
45
30
3500 - 4500 CFM
EHK7-45
57
60
43
4000 - 4500 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
kw C
oRRECtion
f
aCtoRs
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.