background image

25

IO-247A

     12/04

OFF 

100% C FM   

Cooling Dem and  

100% C FM   

1 m in  

50% CFM 

OFF 

½ min 

Profile C ramps up to 82% of the full cooling demand airflow
and operates there for approximately 7 ½ minutes. The motor
then steps up to the full demand airflow.  Profile C also has
a 1 minute/100% OFF delay.

 

100% CFM  

100% CFM  

1 min  

82% CFM 

Cooling Demand

 

7 ½ min 

OFF 

OFF 

Profile D ramps up to 50% of the demand for ½ minute,
then ramps to 82% of the full cooling demand airflow and
operates there for approximately 7 ½ minutes. The motor
then steps up to the full demand airflow.  Profile D has a 1/
2 minute at 50% airflow OFF delay.

 

100% CFM  

50% CFM   

½

 min  

82% CFM 

Cooling Demand 

7 ½ min 

OFF 

OFF 

50% CFM 

½ min 

Ramping Profiles

 

(*indicates factory setting)

 

 8    7    6    5    4     3   2    1 

 



F

 

O  

F

 

 8    7    6    5    4     3   2    1 

 

 

 

O  

F

 

 8    7    6    5    4     3   2    1 

 



F

 

  

 8    7    6    5    4     3   2    1 

 

*

O
N

 
 

 

O
N

 O
N

O
N

Ramping 
Profile 
Tap A

Ramping 
Profile 
Tap B

Ramping 
Profile 
Tap C

Ramping 
Profile 
Tap D

6. Select the heating speed from the heating speed chart in

the Product Data Book applicable for your model*.  The
adjust setting (already established by the cooling speed
selection) determines which set of speeds are available.
The selected speed must provide a temperature rise within
the rise range listed with the particular model.

Example:

The 70 kBtu is set for 990 CFM on cooling,

the “ADJUST” is set to “-” (minus).  The four heating speeds
available are “A Minus”, “B Minus”, “C Minus”, and “D Minus”.
“B Minus” has a rise of 56

°

F for both stages which is within

the 30-60°F rise range for the 70 kBtu.  This setting will
keep electrical consumption to a minimum.  Set the “Heat”
speed DIP switches to “A”.

7. Select the desired “heating” speed tap by positioning

switches 7 and 8 appropriately.  Refer to figure above.  Turn
off power to furnace for a minimum of 10 seconds, allowing
motor to reset and recognize new speed selection.  Turn
on power to furnace.  Verify selected CFM by counting the
green CFM LED blinks.

In general lower heating speeds will: reduce electrical
consumption, lower operating sound levels of the blower, and
increase the outlet air temperature delivered to the home.   The
speeds available allow the blower performance to be optimized
for the particular homeowner’s needs.

O
F
F

O
F
F

8 7

4 3 2 1

O
F
F

O
N

4 3 2 1

O
N

O
F
F

4 3 2 1

O
N

O
N

4 3 2 1

Cooling

Speed
Tap A

Cooling

Speed
Tap B

Cooling

Speed
Tap C

Cooling

Speed
Tap D

*

Cooling Speed Taps

(

*

 indicates factory setting)

O
F
F

O
F
F

8 7

4 3 2 1

O
F
F

O
N

8 7

4 3 2 1

O
N

O
F
F

8 7

4 3 2 1

O
N

O
N

8 7

4 3 2 1

Heating

Speed

Tap A

Heating

Speed

Tap B

Heating

Speed
Tap C

Heating

Speed
Tap D

Heating Speed Taps

(

*

 indicates factory setting)

*

O
F
F

O
F
F

8 7

4 3 2 1

O
F
F

O
N

8 7

4 3 2 1

8

4

7

3 2 1

Normal

+ (Plus)

Adjust

- (Minus)

Adjust

Adjust Taps

(

*

 indicates factory setting)

*

8 7

8 7

8 7

O
N

O
F
F

A

DJUST

 B

LOWER

 H

EAT

 O

FF

 D

ELAY

The integrated control module provides a selectable heat off delay
function. The heat off delay period may be set to 90, 120, 150,180
seconds using the DIP switches or jumper provided on the control
module. The delay is factory shipped at 150 seconds but may be
changed to suit the installation requirements and/or homeowner
preference. Refer to the following figures for switch positions and
corresponding delay times.

Heat Off

Delay

 90 Seconds

ON
ON

1

2

3

Heat Off

Delay

120 Seconds

Heat Off

Delay

150 Seconds

Heat Off

Delay

180 Seconds

ON

OFF

1

2

3

ON

1

2

3

1

2

3

OFF
OFF

Heat Off Delay

(* indicates factory setting)

*

OFF

Heat Off Delay S

C

IRCULATOR

 B

LOWER

 F

AN

 T

IMING

 A

DJUSTMENT

NOTE:  

Items in this section refer to the 

air circulator blower fan

,

NOT to the induced draft blower. The induced draft blower timing
sequence is not adjustable.  The circulator blower fan timing is
adjustable  only on models with optional “heating fan OFF delay”
adjustment pins or switches (Figure 28).  It is NOT adjustable in
any other circumstances.
As shipped, the circulator blower fan will remain on for 150 seconds
after the gas valve closes.  The circulator blower then ramps down
to “OFF” during the 30 seconds following the heat off delay period.
When a call for cooling occurs, the circulator fan comes on and
remains on for 45 seconds after the call for cooling ends. During
normal heating operation, the circulator fan will come on
approximately 37 seconds after the gas valve opens.

O

N

O

F

F

O

N

O

F

F

O

N

O

F

F

O

N

O

F

F

1    

2

1    

2

1    

2

1    

2

90

SECOND

DELAY

120

SECOND

DELAY

150

SECOND

DELAY

180

SECOND

DELAY

Switches viewed in an upflow installation.

 Adjustment Switches

Summary of Contents for AMV8

Page 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Page 2: ...INSTALLATION 13 FIX 1 LINER TERMINATION 13 FIX 2 CHANGE VENTING ARRANGEMENTS 13 FIX 3 REBUILD THE CROWN 13 FIX 4 RELINING 13 VIII Electrical Connections 14 WIRING HARNESS 14 115 VOLT LINE CONNECTIONS...

Page 3: ...7 ANNUAL INSPECTION 27 FILTERS 27 FILTER MAINTENANCE 27 FILTER REMOVAL 27 UPRIGHT FILTER REMOVAL 27 INDUCED DRAFT AND CIRCULATOR BLOWER MOTORS 28 FLAME SENSOR QUALIFIED SERVICER ONLY 28 IGNITER QUALIF...

Page 4: ...mponent failures could result in heating system operational problems TO THE INSTALLER Before installing this unit please read this manual thoroughly to familiarize yourself with specific items which m...

Page 5: ...uring grounding will be discharged 3 Service integrated control module or connecting wiring following the discharge process in step 2 Use caution not to recharge your body with static electricity i e...

Page 6: ...s permitted when installed in the horizontal configuration Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side National Fire Protection Associa...

Page 7: ...nting system are not in operation a Seal any unused openings in the venting system b Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas Code ANSI Z223...

Page 8: ...AM AGE PERSONAL INJURY OR DEATH SUFFICIENT FRESH AIR FO R PROPER COM BUSTION AND VENTILATION OF FLUE G ASES M UST BE SUPPLIED MO ST HOM ES REQ UIRE OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA Improv...

Page 9: ...input rating of all equipment in the enclosure Furnace Water Heater Chimney or Gas Vent NOTE The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total inp...

Page 10: ...W 70 4 Inch 90 4 Inch 115 N A 140 N A MODEL Under some conditions larger vents than those shown above may be required or allowed When an existing furnace is removed from a venting system serving other...

Page 11: ...ter Water Heater Vent Connector Basement Floor F A F Vent Connector Figure 8 Typical Multiple Flue Clay Tile Chimney CHECKLIST SUMMARY This checklist serves as a summary of the items to be checked bef...

Page 12: ...must be removed and replaced Fix 4 Next gently tap the inside of the liner with a Phillips screwdriver If the screwdriver perforates the liner or if the tapping does not sound like metal hitting metal...

Page 13: ...acturer s instructions In some cases a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney For further information on relining see Fix 4 FIX 2 C...

Page 14: ...s that have the junction box located in the include indoor swimming pools and chlorine bleaches paint strippers adhesives paints varnishes sealers waxes which are not yet dried and solvents used durin...

Page 15: ...switch 24 VOLT THERMOSTAT WIRING NOTE Wire routing must not interfere with circulator blower operation filter removal or routine maintenance As a two stage furnace the furnace integrated control modul...

Page 16: ...furnace integrated control module 4 Secure the dehumidistat ground wire typically the green lead to the ground screw on the furnace junction box NOTE Ground wire may not be present on all dehumidista...

Page 17: ...own on the rating plate Overfiring of the furnace can result in premature heat exchanger failure Gas pressures in excess of 13 inches water column can also cause permanent damage to the gas valve IMPO...

Page 18: ...pressure switch kits PROPANE GAS CONVERSION WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO...

Page 19: ...h the left side of the furnace the installer must supply the following fittings starting from the gas valve Straight pipe to reach the exterior of the furnace A ground joint union drip leg and manual...

Page 20: ...9 1 559 50 18 37 79 131 198 376 114 237 448 913 1 417 60 16 35 72 121 187 340 103 217 409 834 1 275 80 13 29 62 104 155 289 89 185 346 724 1 066 100 11 26 55 90 138 255 78 162 307 630 976 125 10 24 48...

Page 21: ...waits call from thermostat NORMAL HEATING SEQUENCE R and W1 or R and W1 W2 thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks Induced draft b...

Page 22: ...blower requires 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor cooling unit run their appropriate spee...

Page 23: ...Installation s gas heating HTG value 1 000 BTU ft3 Obtained from gas supplier Installation s seconds per cubic foot 34 sec ft3 Conversion Factor hours to seconds 3600 sec hr Input Htg value x 3600 sec...

Page 24: ...r the cooling system Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton Most manufacturers recommend an air flow of about 400 CFM per ton Example 2 5 tons X 400 C...

Page 25: ...ormance to be optimized for the particular homeowner s needs O F F O F F 8 7 4 3 2 1 O F F O N 4 3 2 1 O N O F F 4 3 2 1 O N O N 4 3 2 1 Cooling Speed Tap A Cooling Speed Tap B Cooling Speed Tap C Coo...

Page 26: ...ontrol will reset and allow the furnace to resume normal operation WARNING TO PREVENT PREMATURE FAILURE OF HEAT EXCHANGER PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT ADJUST THE LIMIT CONTROL FACTO...

Page 27: ...n determining the cause XVI MAINTENANCE WARNING TO AVOID ELECTRICAL SHOCK INJURY OR DEATH DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE IF YOU MUST HANDLE THE IGNITER HANDLE WITH CARE...

Page 28: ...VENT PERSONAL INJURY OR DEATH DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS CONTACT A QUALIFIED SERVICE AGENT AT ONCE...

Page 29: ...circuit Inspect pressure switch hose Repair if necessary Inspect flue for blockage proper length elbows and termination Correct pressure switch setpoint or contact motion Tighten or correct wiring con...

Page 30: ...spect for proper sensor alignment Check inlet air piping for blockage proper length elbows and termination Compare current gas pressure to rating plate info Adjust as needed Turn power OFF prior to re...

Page 31: ...MIT CONTROL WIRING TO UNIT MUST BE PROPERLY ON S OME M O DE LS IN DU CTO R COI L P R ES SU R E SWI TC H LO W FIR E Y L RD BK WH IN D U CED B R GN D WH WH BK BR RD GN BU BR WH AU XI LIA RY LI M I T C O...

Page 32: ...of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s...

Reviews: