background image

18

IO-247A

     12/04

1,000 Btu/ft

3

 is determined by-

Corrected Input = 90,000 - (6,000 X .04) X (90,000 / 1,000)

Corrected Input = 90,000 - (240 X 90)

Corrected Input = 90,000 - 21,600

Corrected Input = 68,400

Using the orifices sized as shown in the table for 6,000 feet (#45),
a meter time of 52.6 seconds is measured. The actual firing rate
of the furnace is

Input = 1,000 (heating value of the gas) X 3600 (constant) / 52.6
(meter time for 1 ft

of gas)

Input = 3,600,000 / 52.6

Input = 68,400 Btu/h

M

ETER

 T

IME

 I

N

 M

INUTES

 

AND

 S

ECONDS

 F

OR

 N

ORMAL

 I

NPUT

R

ATING

 

OF

 F

URNACES

 E

QUIPPED

 F

OR

 U

SE

 W

ITH

 N

ATURAL

G

AS

 A

T

 0 - 2,000 F

EET

 A

LTITUDE

 INPUT

METER 

SIZE

HEAT 

VALUE

HEAT 

VALUE

HEAT 

VALUE

HEAT 

VALUE

 Btu/hr

FT

3

900

1,000

1040

1,100

MIN. SEC.

MIN.SEC

MIN. SEC.

MIN. SEC.

1

1     21

1    30

1     33

1    39

10

 13     30

  15    00

 15     36

 16    30

1

   0     54

1     00

1     03

1    06

10

9     00

  10    10

 10     24

  11    00

1

0     41

0     45

0     47

0     50

10

6     45

7     30

7     48

8     15

1

0     32

0     36

0     37

0     40

10

5     24

6     00

6     14

6     36

1

0     27

0     30

0     31

0     33

10

   4     30

5     00

5     12

5     30

120,000

40,000

60,000

80,000

100,000

In Canada, the series and rating plate input for the furnace apply
to installations up to 2,000 feet (610m) above sea level. Kit 

HA-02

for natural and LP gases is required to convert furnaces from
elevations of 2,000 to 4,500 feet (610m to 1,370m). Canadian
certification applies to the installations of up to 4,500 feet above
sea level. Installations above 4,500 feet are subject to acceptance
by the local authorities having jurisdiction.

Do 

not

 derate the furnace by adjusting the manifold pressure to a

lower pressure than specified on the furnace rating plate.  The
combination of the lower air density and a lower manifold pressure
will prohibit the burner orifice from drawing the proper amount of
air into the burner.  This may cause incomplete combustion,
flashback, and possible yellow tipping.

In some areas the gas supplier may artificially derate the gas in an
effort to compensate for the effects of altitude.  If the gas is artificially
derated, the appropriate orifice size must be determined based
upon the BTU/ft

3

 content of the derated gas and the altitude.  Refer

to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and
information provided by the gas supplier to determine the proper
orifice size.

A different pressure switch may be required at high altitude
regardless of the BTU/ft

3

 content of the fuel used.  Contact your

distributor for a tabular listing of appropriate altitude ranges and
corresponding manufacturer’s pressure switch kits.

P

ROPANE

 G

AS

 C

ONVERSION

WARNING

P

OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF

THE CORRECT CONVERSION KITS ARE NOT INSTALLED. 

T

HE APPROPRIATE KITS

MUST BE APPLIED TO INSURE SAFE AND PROPER FURNACE OPERATION. 

A

LL

CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE

AGENCY.

This unit is configured for natural gas.  The appropriate
manufacturer’s propane gas conversion kit, must be applied for
propane gas installations.  Refer to the “Propane Gas and/or
High Altitude Installations” section for details.

Contact your distributor for a tabular listing of appropriate
manufacturer’s kits for propane gas and/or high altitude installations.
The indicated kits must be used to insure safe and proper furnace
operation.  All conversions must be performed by a qualified
installer, or service agency.

G

AS

 P

IPING

 C

ONNECTIONS

G

ENERAL

CAUTION

T

O AVOID POSSIBLE UNSATISFACTORY OPERATION OR EQUIPMENT DAMAGE

DUE TO UNDERFIRING OF EQUIPMENT, USE THE PROPER SIZE OF

NATURAL/PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE

METER/TANK TO THE FURNACE.

When sizing a trunk line, be sure to include all appliances which
will operate simultaneously when sizing a trunk line.

The gas piping supplying the furnace must be properly sized based
on the gas flow required, specific gravity of the gas, and length of
the run.  The gas line installation must comply with local codes, or
in their absence, with the latest edition of the National Fuel Gas
Code, NFPA 54/ANSI Z223.1.

Natural Gas Capacity of Pipe

In Cubic Feet of Gas Per Hour (CFH)

Length of

Nominal Black  Pipe Size

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)

CFH =

BTUH Furnace Input   
Heating Value of  Gas (BTU/Cubic Foot)

To connect the furnace to the building’s gas piping, the installer
must supply a ground joint union, drip leg, manual shutoff valve,
and line and fittings to connect to gas valve.  In some cases, the
installer may also need to supply a transition piece from 1/2" pipe
to a larger pipe size.

The following stipulations apply when connecting gas piping.  Refer
to Figure 16 for typical gas line connections to the furnace.

• Use black iron or steel pipe and fittings for the building piping.
• Use pipe joint compound on male threads only.  Pipe joint

compound must be resistant to the action of the fuel used.

• Use ground joint unions.

Summary of Contents for AMV8

Page 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Page 2: ...INSTALLATION 13 FIX 1 LINER TERMINATION 13 FIX 2 CHANGE VENTING ARRANGEMENTS 13 FIX 3 REBUILD THE CROWN 13 FIX 4 RELINING 13 VIII Electrical Connections 14 WIRING HARNESS 14 115 VOLT LINE CONNECTIONS...

Page 3: ...7 ANNUAL INSPECTION 27 FILTERS 27 FILTER MAINTENANCE 27 FILTER REMOVAL 27 UPRIGHT FILTER REMOVAL 27 INDUCED DRAFT AND CIRCULATOR BLOWER MOTORS 28 FLAME SENSOR QUALIFIED SERVICER ONLY 28 IGNITER QUALIF...

Page 4: ...mponent failures could result in heating system operational problems TO THE INSTALLER Before installing this unit please read this manual thoroughly to familiarize yourself with specific items which m...

Page 5: ...uring grounding will be discharged 3 Service integrated control module or connecting wiring following the discharge process in step 2 Use caution not to recharge your body with static electricity i e...

Page 6: ...s permitted when installed in the horizontal configuration Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side National Fire Protection Associa...

Page 7: ...nting system are not in operation a Seal any unused openings in the venting system b Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas Code ANSI Z223...

Page 8: ...AM AGE PERSONAL INJURY OR DEATH SUFFICIENT FRESH AIR FO R PROPER COM BUSTION AND VENTILATION OF FLUE G ASES M UST BE SUPPLIED MO ST HOM ES REQ UIRE OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA Improv...

Page 9: ...input rating of all equipment in the enclosure Furnace Water Heater Chimney or Gas Vent NOTE The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total inp...

Page 10: ...W 70 4 Inch 90 4 Inch 115 N A 140 N A MODEL Under some conditions larger vents than those shown above may be required or allowed When an existing furnace is removed from a venting system serving other...

Page 11: ...ter Water Heater Vent Connector Basement Floor F A F Vent Connector Figure 8 Typical Multiple Flue Clay Tile Chimney CHECKLIST SUMMARY This checklist serves as a summary of the items to be checked bef...

Page 12: ...must be removed and replaced Fix 4 Next gently tap the inside of the liner with a Phillips screwdriver If the screwdriver perforates the liner or if the tapping does not sound like metal hitting metal...

Page 13: ...acturer s instructions In some cases a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney For further information on relining see Fix 4 FIX 2 C...

Page 14: ...s that have the junction box located in the include indoor swimming pools and chlorine bleaches paint strippers adhesives paints varnishes sealers waxes which are not yet dried and solvents used durin...

Page 15: ...switch 24 VOLT THERMOSTAT WIRING NOTE Wire routing must not interfere with circulator blower operation filter removal or routine maintenance As a two stage furnace the furnace integrated control modul...

Page 16: ...furnace integrated control module 4 Secure the dehumidistat ground wire typically the green lead to the ground screw on the furnace junction box NOTE Ground wire may not be present on all dehumidista...

Page 17: ...own on the rating plate Overfiring of the furnace can result in premature heat exchanger failure Gas pressures in excess of 13 inches water column can also cause permanent damage to the gas valve IMPO...

Page 18: ...pressure switch kits PROPANE GAS CONVERSION WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO...

Page 19: ...h the left side of the furnace the installer must supply the following fittings starting from the gas valve Straight pipe to reach the exterior of the furnace A ground joint union drip leg and manual...

Page 20: ...9 1 559 50 18 37 79 131 198 376 114 237 448 913 1 417 60 16 35 72 121 187 340 103 217 409 834 1 275 80 13 29 62 104 155 289 89 185 346 724 1 066 100 11 26 55 90 138 255 78 162 307 630 976 125 10 24 48...

Page 21: ...waits call from thermostat NORMAL HEATING SEQUENCE R and W1 or R and W1 W2 thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks Induced draft b...

Page 22: ...blower requires 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor cooling unit run their appropriate spee...

Page 23: ...Installation s gas heating HTG value 1 000 BTU ft3 Obtained from gas supplier Installation s seconds per cubic foot 34 sec ft3 Conversion Factor hours to seconds 3600 sec hr Input Htg value x 3600 sec...

Page 24: ...r the cooling system Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton Most manufacturers recommend an air flow of about 400 CFM per ton Example 2 5 tons X 400 C...

Page 25: ...ormance to be optimized for the particular homeowner s needs O F F O F F 8 7 4 3 2 1 O F F O N 4 3 2 1 O N O F F 4 3 2 1 O N O N 4 3 2 1 Cooling Speed Tap A Cooling Speed Tap B Cooling Speed Tap C Coo...

Page 26: ...ontrol will reset and allow the furnace to resume normal operation WARNING TO PREVENT PREMATURE FAILURE OF HEAT EXCHANGER PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT ADJUST THE LIMIT CONTROL FACTO...

Page 27: ...n determining the cause XVI MAINTENANCE WARNING TO AVOID ELECTRICAL SHOCK INJURY OR DEATH DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE IF YOU MUST HANDLE THE IGNITER HANDLE WITH CARE...

Page 28: ...VENT PERSONAL INJURY OR DEATH DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS CONTACT A QUALIFIED SERVICE AGENT AT ONCE...

Page 29: ...circuit Inspect pressure switch hose Repair if necessary Inspect flue for blockage proper length elbows and termination Correct pressure switch setpoint or contact motion Tighten or correct wiring con...

Page 30: ...spect for proper sensor alignment Check inlet air piping for blockage proper length elbows and termination Compare current gas pressure to rating plate info Adjust as needed Turn power OFF prior to re...

Page 31: ...MIT CONTROL WIRING TO UNIT MUST BE PROPERLY ON S OME M O DE LS IN DU CTO R COI L P R ES SU R E SWI TC H LO W FIR E Y L RD BK WH IN D U CED B R GN D WH WH BK BR RD GN BU BR WH AU XI LIA RY LI M I T C O...

Page 32: ...of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s...

Reviews: