TROUBLESHOOTING
58
Name/Cloud/Phone App
7 Segment Display
User Modifiable Options
Comments
Last 6 Faults
N/A
Views the control last 6 history faults.
Learn Menu
Yes or No.
Resets communication network.
Code Release No
N/A
Views the control firmware revision number and Shared Data number.
Shared Data Revision
N/A
Views the control Shared Data revision number and shared data upload.
Reset To Factory Default
Yes or No.
Reset the furnace setting to factory defaults.
Constant Fan Speed
Adjustable between 25% to + 100% with 10% ingrements.
Default is 25%.
Select the indoor blower airflow at constant fan mode.
Gas Heating Airflow
Adjustable between Min and Max. Min, Max, Step and
Default are defined in Shared Data.
Select the indoor blower airflow multiplier for gas heat operation.
Gas Heat Off Delay
Adjustable between 30 seconds to 180 seconds with 5
seconds increments. Default is 30 seconds.
Selects the indoor blower heat off delay.
Gas Heat On Delay
Adjustable between 5 seconds to 30 seconds with 30
seconds increments. Default is 90 seconds.
Selects the indoor blower heat off delay.
Gas Heat Trim Factor
Adjustable between -10% to +10% with 2% increments.
Default is 0%.
Trims the heating airflow by the selected amount.
Gas Heat Stage Multiplier
Adjustable between Min and Max. Min, Max, Step and
Default are defined in Shared Data.
Selects gas heat stage multiplier
Gas Pressure Test
Yes or No.
Checks gas valve pressure at 100% firing rate.
Function Enable/Disable
Not implemented in the initial
Backup Heat Balance Points
Adjustable between Min and Max. Min, Max, Step and
Default are defined in Shared Data.
This menu only shows up when a communicating Heat Pump is detected.
Comfort Setting
First 5 option values are defined in Shared Data. The 6th
option shall be hard-coded in the firmware with other 5
settings. The default value is Option 1.
Provides the 6 comfort setting options for the furnace staging algorithm
operation, only shows up when ClimateTalk or DataAC T-Stat is not
connected.
Hum On Enable
1 ~ 16 options and the default option is 15.
Provides the 16 humidifier enabling options in different operation
modes.
Ventilation On Time
Adjustable between 0 ~ 60 minutes. The default is 0
minute Off).
Adjusts the ventilation on time and turn it on/off.
DeHum Logic
Hi and Lo. The default is Lo.
Provides the DeHum logic input level for DeHum operation. Only applies
when the legacy 24VAC input is active.
Name/Cloud/Phone App
7 Segment Display
User Modifiable Options
Comments
Tonnage
Adjustable between 1 to 6 ton with 0.1 increments.
Default is 3 ton.
Only visible when communicating outdoor unit is not detected.
Cool Trim Factor
Adjustable between -10% to +10% with 2% increments.
Default is 0%.
Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A(1), B(2), C(3), D(4 or 5)
Select cooling airflow profiles.
Cool On Delay
Adjustable between 5 to 30 seconds with 5 seconds
increments. Default is 5 seconds.
Selects the cooling on delay.
Cool Off Delay
Adjustable between 30 to 120 seconds with 30 seconds
increments. Default is 60 seconds.
Selects the cooling off delay.
Cool Stage Multiplier
Adjustable between 60% to + 100% with 1% increments.
Default is 70%.
Selects stage multiplier for 2-stage OD unit.
Defrost Gas Heat Stage
1 or 2
Selects the gas heat stage for defrost operation.
Compressor Balance Points
Adjustable and defined in Shared Data
Provides the compressor balance point options for HP operation.
HP Trim Factor
Adjustable between -10% to +10% with 2% increments.
Default is 0%.
Trims the heating airflow by the selected amount.
HP On Delay
Adjustable between 5 to 30 seconds with 5 seconds
increments. Default is 5 seconds.
Selects the HP heating on delay.
HP Off Delay
Adjustable between 30 to 120 seconds with 30 seconds
increments. Default is 60 seconds.
Selects the HP heating off delay
HP Stage Multiplier
Adjustable between 70% to 100% with 5% increments.
Default is 70%.
Select stage multiplier for 2-stage OD unit.
Name/Cloud/Phone App
7 Segment Display
User Modifiable Options
Comments
Cool Trim Factor
-10%, -8%,-6%, -4%, -2%, 0%, 2%, 4%, 6%, 8%,10% Trims the cooling airflow by the selected amount.
Cool Airflow Profile
A, B, C, D
Select cooling airflow profiles.
Cool On Delay
5, 10, 20, 30
Selects the cooling on delay.
Furnace
Outdoor AC/HP, Single-Stage AC/HP
ClimateTalk Comm Outdoor 2-Stage AC/HP