background image

COMBUSTIBLE WALL CHIMNEY CONNECTOR PASS-THROUGHS

Method A. 12” (304.8 mm) Clearance to Combustible Wall Member: 

Using a minimum thickness 3.5” (89 mm) brick and a 5/8” (15.9 mm) 
minimum wall thickness clay liner, construct a wall pass-through.  The clay 
liner must conform to ASTM C315 (Standard Speci

fi

 cation for Clay Fire 

Linings) or its equivalent. Keep a minimum of 12” (304.8 mm) of brick 
masonry between the clay liner and wall combustibles.  The clay liner 
shall run from the brick masonry outer surface to the inner surface of the 
chimney 

fl

 ue liner but not past the inner surface.  Firmly grout or cement 

the clay liner in place to the chimney 

fl

 ue liner.  

Method B. 9” (228.6 mm) Clearance to Combustible Wall Member: Using 

a 6” (152.4 mm) inside diameter, listed, factory-built Solid-Pak chimney 
section with insulation of 1” (25.4 mm) or more, build a wall pass-through 
with a minimum 9” (228.6 mm) air space between the outer wall of the 
chimney length and wall combustibles.  Use sheet metal supports fastened 
securely to wall surfaces on all sides, to maintain the 9” (228.6 mm) air 
space.  When fastening supports to chimney length, do not penetrate the 
chimney liner (the inside wall of the Solid-Pak chimney).  The inner end of 
the Solid-Pak chimney section shall be 

fl

 ush with the inside of the masonry 

chimney 

fl

 ue, and sealed with a non-water soluble refractory cement.  Use 

this cement to also seal to the brick masonry penetration.

Method C. 6” (152.4 mm) Clearance to Combustible Wall Member: 

Starting with a minimum 24 gauge (.024” [.61 mm]) 6” (152.4 mm) metal 
chimney connector, and a minimum 24 gauge ventilated wall thimble which 
has two air channels of 1” (25.4 mm) each, construct a wall pass-through. 
There shall be a minimum 6” (152.4) mm separation area containing 

fi

 berglass insulation, from the outer surface of the wall thimble to wall 

combustibles.  Support the wall thimble, and cover its opening with a 
24-gauge minimum sheet metal support. Maintain the 6” (152.4 mm) space.  
There should also be a support sized to 

fi

 t and hold the metal chimney 

connector. See that the supports are fastened securely to wall surfaces on 
all sides.  Make sure fasteners used to secure the metal chimney connector 
do not penetrate chimney 

fl

 ue liner.  

Method D.  2” (50.8 mm) Clearance to Combustible Wall Member: Start 

with a solid-pak listed factory built chimney section at least 12” (304 mm) 
long, with insulation of 1” (25.4 mm) or more, and an inside diameter of 8” 
(2 inches [51 mm] larger than the 6” [152.4 mm] chimney connector). Use 
this as a pass-through for a minimum 24-gauge single wall steel chimney 
connector. Keep solid-pak section concentric with and spaced 1” (25.4 
mm) off the chimney connector by way of sheet metal support plates at 
both ends of chimney section.  Cover opening with and support chimney 
section on both sides with 24 gauge minimum sheet metal supports. See 
that the supports are fastened securely to wall surfaces on all sides. Make 
sure fasteners used to secure chimney 

fl

 ue do not penetrate 

fl

 ue liner.

NOTES:
 Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through 

system and the chimney wall, to but not past the inner 

fl

 ue liner face.

 A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a 

fl

 oor, or ceiling.

Summary of Contents for 7000

Page 1: ...WOOD ADD ON 2 WOOD ONLY Installation is to be preformed by a qualified installer SAVE THESE INSTRUCTIONS French version is available for download from the US Stove website http www usstove com La version française est disponible pour téléchargement à partir du site US Stove http www usstove com This unit is certified UL 391 conformes to CAN CSA B366 1 United States Stove Company 227 Industrial Par...

Page 2: ...ementary furnace shall not be connected to the cold air return inlet of the central furnace because a possibility exists of components of the central furnace overheating and causing he central furnace to operate other than as intended Power source not controlled by furnace main disconnect Respect all local and national codes when installing this unit This unit is not to be connected to a chimney f...

Page 3: ... Feet 3 6 cubic feet Door Opening Width x Height 13 6 x 9 8 345mm x 248mm Pyroceramic Glass Door Viewing Width x Height 13 x 10 75 330mm x 273mm Weight lbs 540 SPECIFICATIONS CONGRATULATIONS You ve purchased a heater from North America s oldest manufacturer of wood burning products By heating with wood you re helping to CONSERVE ENERGY Wood is our only Renewable Energy Resource Please do your part...

Page 4: ...tions also apply to a draft inducer if used To prevent flame or smoke spillage the slide baffle must be pulled out and the fuel loading door left cracked for 10 seconds prior to opening door fully Load fuel carefully or damage may result For canadian installations not to be connected to a ductwork that is still connected to another furnace Hot while in operation Keep children clothing and furnitur...

Page 5: ...INSTALLATION The following is a list of tools and materials needed to install your furnace 7 16 socket wrench 5 16 socket Best if using a power drill and a socket bit Pair of pliers or channel locks Power drill with an 1 8 drill bit to install sheet metal screws into connector pipe Sheet metal screws Non combustible floor protector as specified in this manual All chimney and chimney connector comp...

Page 6: ... of this furnace includes supplying electrical power return fresh air ductwork and supply air ductwork This furnace may be installed in three different configurations 1 Stand alone wood furnace 2 Add on wood furnace The furnace also has several additional kits that may be installed GE7B Blower Kit Required GE7FAK Fresh air Kit Optional GE7CAP Cold Air Plenum Optional See kit installation section i...

Page 7: ...Clearance Front 24 610 J Maintenance Clearance Left 24 610 K Maintenance Clearance Right 24 610 L Maintenance Clearance Rear 36 915 J K L H P M Q N R R MAINTENANCE CLEARANCE Dimension Inch mm M Front 16 407 N Flue rear 2 51 P Left 8 204 Q Right 8 204 R Flue Side 2 51 Canadian installations require 18 457mm FLOOR PROTECTOR REQUIREMENTS FLOOR PROTECTOR The furnace must be placed on solid concrete so...

Page 8: ... 2 1 1 The plenums installed to the furnace shall be constructed of metal in accordance with NFPA 90B 2 1 3 When installing this furnace the hot air plenum is to have a minimum height of 24 610mm if the top of the first vertical section is not flush with the top of the first horizontal section of ductwork If the top of the plenum is flush with the top of the first horizontal section of ductwork th...

Page 9: ... in series with an existing furnace The transfer duct between the existing furnace and this furnace must be at least 320in2 The minimum radius on any elbows is 6 Ensure that the installation of the furnace will not allow inversion of the air flow If a divider is installed to separate the supply duct from the existing furnace and the new furnace option 2 the divider must be installed in a manor tha...

Page 10: ...e wiring diagram 8 Connect the damper servo motor wires harness extension to the fan control box and route to the servo motor Route wires behind side access panel 9 If required install the filter into the blower section The filter is not required if installed in series with another furnace because the existing furnace has its own filter COMBUSTION AIR FRESH AIR INSTALLATION If necessary combustion...

Page 11: ...ork Drill a 7 8 hole for the fan limit control sensor rod to pass through into the ductwork The center of the limit control needs to be installed 14 from the rear of the furnace on the left side of the plenum this is viewing the furnace from the rear The hole needs to be drilled 7 5 from the top of the furnace BLOWER FAN WIRING Supply power to the blower fan from an independent 120 Volt circuit Th...

Page 12: ...the draft effect your furnace s performance is directly dependent on an adequate draft from your chimney Do not connect this unit to a chimney flue serving another appliance The following recommendations may be useful for the installation of your chimney It must rise above the roof at least 3 0 9m from the uppermost point of contact The exterior portion should be double or triple wall pipe to ensu...

Page 13: ... professional Make sure there are no cracks loose mortar or other signs of deterioration and blockage Have the chimney cleaned before the furnace is installed and operated When connecting the furnace through a combustible wall to a masonry chimney special methods are needed as explained in the Combustible Wall Chimney Connector Pass Throughs Section ...

Page 14: ...tor and a minimum 24 gauge ventilated wall thimble which has two air channels of 1 25 4 mm each construct a wall pass through There shall be a minimum 6 152 4 mm separation area containing fiberglass insulation from the outer surface of the wall thimble to wall combustibles Support the wall thimble and cover its opening with a 24 gauge minimum sheet metal support Maintain the 6 152 4 mm space Ther...

Page 15: ...per end of the section toward the chimney Any installation with a horizontal run of furnace pipe must conform to NFPA 211 You may contact NFPA National Fire Protection Association and request the latest edition of the NFPA Standard 211 To insure a good draft the total length of the furnace pipe should never exceed 8 to 10 2 4m to 3 04 m Except for cases of vertical installation cathedral roof styl...

Page 16: ...me manufacturer and install the ceiling support package or wall pass through and T section package firestops where needed insulation shield roof flashing chimney cap etc Maintain proper clearance to the structure as recommended by the manufacturer The chimney must be the required height above the roof or other obstructions for safety and proper draft operation ...

Page 17: ...r All logs exceeding 6 in diameter should be split The wood should not be stored directly on the ground Air should circulate through the cord A 24 to 48 air space should be left between each row of logs which should be placed in the sunniest location possible The upper layer of wood should be protected from the elements but not the sides TESTING YOUR WOOD When the furnace is thoroughly warmed plac...

Page 18: ...indling fire can circulate around the logs and close the door Note You may need to add more kindling to help ignite the cordwood 2 Before loading your furnace fully you will want a well established fire in the combustion chamber This typically takes 15 20 minutes HEATING WITH YOUR WOOD FURNACE 1 Spread the fire and coals evenly towards the center of the combustion chamber before loading your furna...

Page 19: ...rge quantity is lost into the atmosphere TO PREVENT CREOSOTE BUILD UP Always burn dry wood This allows clean burns and higher chimney temperatures therefore less creosote deposit Leave the air control full open for about 5 min every time you reload the furnace to bring it back to proper operating temperatures The secondary combustion can only take place if the firebox is hot enough Always check fo...

Page 20: ...ss gasket to make sure you keep it sealed Never wash the glass with a product that may scratch Use a specialized product available in the stores where wood furnaces are sold The glass should be washed only when cold GASKETING It is recommended that you change the door gasket which makes your furnace door air tight once a year in order to insure good control over the combustion maximum efficiency a...

Page 21: ...REPLACEMENT PARTS 23 32 11 10 12 21 31 37 26 36 24 28 25 30 5 17 20 19 15 16 57 38 1 34 13 3 2 33 4 35 39 14 29 27 ...

Page 22: ...PONENTS MUST BE REPLACED USING ORIGINAL MANUFACTURERS PARTS PURCHASED THROUGH YOUR DEALER OR DIRECTLY FROM THE APPLIANCE MANUFACTURER USE OF THIRD PARTY COMPONENTS WILL VOID THE WARRANTY 39 40 41 45 44 42 43 46 56 55 51 54 52 53 39 18 ...

Page 23: ...WARRANTY COMPONENTS MUST BE REPLACED USING ORIGINAL MANUFACTURERS PARTS PURCHASED THROUGH YOUR DEALER OR DIRECTLY FROM THE APPLIANCE MANUFACTURER USE OF THIRD PARTY COMPONENTS WILL VOID THE WARRANTY 22 6 47 50 49 48 7 9 8 9 ...

Page 24: ... Collar 1 24 26871 Air Defl ector 2 25 26947 Side Panel Insulation 2 26 88215 Back Panel Insulation 1 27 610028 Panel Weldment Right 1 28 83884 Insulation Holder 26 29 610030 Panel Weldment Back 1 30 610029 Panel Weldment Left 1 31 88115 Side Gasket 1 2X1 8 Pdm Sponge 58 32 88115 Back Gasket 1 2X1 8 Pdm Sponge 64 Key Number Part Number Description Qty 33 26866 Door Latch 1 34 69997 Ash Pan Door As...

Page 25: ...M orifice size SI liter hour x 39 023 x E 1 21 x t CFM orifice size Imperial gallon hour x 140 000 x E 1 1 x t E Average heat generator efficiency 0 75 t Temperature rise ºC Re Electrical energy input rate kW t Temperature rise ºC Rg Gas input rate kW Eg Efficiency of a typical atmospheric gas furnace 0 7 ...

Page 26: ...eplate attached to the stove When ordering repair parts always give the following information as shown in this list 1 The part number ___________________________________________ 2 The part description ___________________________________________ 3 The model number ___________________________________________ 4 The serial number ___________________________________________ United States Stove Company ...

Page 27: ...__ Reason for Purchase Alternative Heat Main Heat Source Decoration Cost Other _________________________ What was the determining factor for purchasing your new USSC appliance _______ I have read the owner s manual that accompanies this unit and fully understand the Installation Operation and Maintenance of my new USSC appliance Print Name Signature Date Please attach a copy of your purchase recei...

Page 28: ... CUT HERE CUT HERE Fold Here Fold Here United States Stove Company P O Box 151 South Pittsburg TN 37380 Fold Here PLACE STAMP HERE ...

Reviews: