SmartBox
®
4 / SmartBox
®
4
PRO
part no. 28 400 57 c
25 / 32
Comm-
and
Parameter
Description
Standard /
default value
#G=
0 - 101
Activate credit information:
9
0=
OFF, no credit information, contract
card or other prepaid card
1=
ON for prepaid card T-Mobile (*100#
- in Germany DE)
2=
ON for prepaid card Vodafone (**100#
- in Germany)
9=
SMS counter (recommended for
contract SIM-card!)
101=
ON for Prepaid-Card O
2
(*101# in DE)
#Ni=
Enter name for
tank i
#N1
=Name Tank1 (the name of the tank can
have up to 16 characters)
#N1=… to
#N4=…
#LG=
Language
#LG
=0 sets language to ’German’, 1 to ’English’
2 to ’French’
#LG=0,#LG=1
or #LG=2
#TMPn=
Temperature
limit value n =
tank number
Set temperature limit value in °C e.g.:
#TMP1=18#TMP2=5#TMP3=-10#TMP4=-99
Value -99 = Deactivation
The lower deviation causes a temperature
alarm in alarm chain
#TA1...#TAn
-99
[-99..99] °C
#I2
#I3
#I4
Delete tank: The tank with this number is
deleted from the tank registry. The tank
numbers behind this move up one place.
(The previous command
#I
deleted all tanks).
only
SmartBox
®
4
#I98
Remote reset:
Cold start command for
processor and modem
#R
Quick additional inquiry
addressed in
between to the inquiring mobile phone, e.g. by
the driver of the tank truck.
Read command
to trigger an info SMS to the
inquiring mobile phone. The day counters for
the standard info SMS to the headquarter will
run on.
#M
Same as
#R
, but day counters are reset (
#P
).
This is useful e.g. if the tank is to be monitored
all the time by manual inquiry only.
#C
Query configuration
Query device configuration: Header; SW
version; main destination no.; reporting points;
serial no. of the device; field strength; credit
mode; SMS counter; Temp. limit value if set
with
#TMP1 - #TMP4
Format:
Header; Parameter; V6.00;
004917619808000; 10,2,40,2,0,5; 9308; 2; 9;
123; TMP=-99