SmartBox
®
4 / SmartBox
®
4
PRO
24 / 32
part no. 28 400 57 c
Comm-
and
Parameter
Description
Standard /
default value
#H=
Text 0 –
40
characters
max.
Header-Text
, introducing every SMS message. Tank
monitoring
#P=
10,30,15,07
(always enter 4
values as 2-
digit figures,
preceded by 0 if
necessary!)
Fill level message points:
[from..to]
Number 1 =
Percentage increment for new
message, e.g. report fill level
after every 10%.
10,
[01..99] %
Number 2 =
Period of days for new message,
e.g. send a report on the system
min. every 30 days. Or indicate
number of hours with xxh. Add
‘h’ to indicate a number of hours.
30,
[01..99] Tg
[01h..24h]
Number 3 =
’Critical limit value’ in per cent,
i.e. if the value falls below the
limit, an alarm message is sent.
15,
[00..99] %
Number 4 =
Interval of days for repeating the
message on limit value.
07,
[01..31] days
[01h..24h]
5. Value:
10,30,15,07,
0
,5,0
Number 5 =
0 Triggers a limit value report as
soon as one of the tanks
reaches the reserve level.
1 Triggers a limit value report
only when all of the tanks reach
the reserve level.
0
[0 or 1]
6. Value:
10,03,15,07,
0,
5
,0
Number 6 =
Percentage for increase in
content, that triggers a fuelling
report, e.g. 5%
5
[01..99] %
7. Value:
10,03,15,07,
0,5,
0
Number 7 =
1 or 0. With 1, in a fuelling case
a message with the initial value
is displayed.
0
[0 oder 1]
#Pn=
#P
Change
parameters
individually
The above
#P
parameters can also be set
individually: e.g.
#P6=8
or
#P2=36h
#A1=
Configure alarm
1: 0, "Text"
Configuration:
0 (alarm, when contact closed)
1 (alarm, when contact open)
Additional text:
e.g.:
Boiler cold
(max. 15 characters)
0, system fault