Error Meaning
Action
E 4
Internal data error, the stored data
are incorrect
Software error
Send electronic test device to the
manufacturer to be checked.
E 5
The system is already pressurised
when the device is switched on
Test hose not ventilated
Ventilate the test hose of the electronic test
device (loosen, open, unpressurised state).
Calibration error
System error
Send electronic test device to the
manufacturer to be checked.
Does not generate a new test
number
After the test has been completed, press
the Test button to terminate the test.
CALIBRATION AND FUNCTION CHECK
The electronic test device must be calibrated every 12 months.
During calibration the pressure sensor is checked and adjusted, if necessary, and the
functions of the electronic test device are checked.
Accordingly, the manufacturer recommends that the electronic test device be checked
regularly (annually). For this purpose, the complete Leak Check LPG PRO system case with
all accessories must be sent to the manufacturer GOK Regler- und Armaturen-Gesellschaft
mbH & Co. KG, Obernbreiter Straße 2 - 18, 97340 Marktbreit / GERMANY.
LIST OF ACCESSORIES
Product name
Order no.
Calibration of the test device
58 803 00
MAINTENANCE
Apart from cleaning (with a dry cloth only), the electronic test device requires no care or
maintenance.
No liquids or external pressure must get into the test hose for the
test device. This would destroy the pressure sensor of the electronic test device.
REPAIRING THE PRINTER
PIN control on the printer
If the PIN is adjusted during
printer maintenance, it must
be reset according to layout
opposite:
ON
position: push white
pins:1, 3, 4, and 7
upward
SHUT-DOWN
If the electronic test device and printer are not being used or are being stored unattended,
both main switches must be in the OFF position.
If the electronic test device and printer are being stored for some time, they must be stored in
a suitable cool, dry place. Storage temperature should not exceed 30°C.