B l u e C o n n e c t   –   C o n f i g u r i n g   t h e   M o d u l e s

 

 

 

 

GO Systemelektronik GmbH  Faluner Weg 1    24109 Kiel     Germany  Tel.: +49 431 58080-0 

Fax: -58080-11 

Page 10 / 26 

 

 

 

www.go-sys.de    

                    [email protected]

 

4 Configuring the BlueConnect Modules with the Program Modbus Tool.exe  

This chapter describes the operation of the BlueConnect configuration program Modbus Tool.exe of 

GO Systemelektronik with the article number 420 6500 in 

software version 1.07

. For example, you can use it 

(depending  on the type of module and sensor) to read out sensor information, assign a Modbus address, 

calibrate the sensor and display measurement values.   

On older Sensor and Bus Modules without slide switches, the Modbus (RS485) and the CAN bus can be 

terminated.

 1

 

  The 

configuration of the Bus Module

 is done automatically. The exception here are older bus  

modules, see 

4.11 Configuring Older Bus Modules

The 

configuration of the Bus Module Turbidity flow through

 is done at the BlueBox and is not  

described here. 

  The calibration of the Sensor Modules can also be done via the menu operation on the BlueBox  

and with the BlueBox PC Software. 

  The calibration of the Current Modules can also be done via the menu operation on the BlueBox  

and with the BlueBox PC Software. 

  The 

configuration of the RS232 Module

 is done via DIP switches. 

see 

3.2 Cable Connections, Switch Positions and LEDs

 there 

RS232 Modul

 

  Decimal separator is the comma. 

The program is executable under Windows 7 and newer. An Installation is not necessary, the program starts 

when Modbus Tool.exe is called up. 
The program automatically detects the connected modules with their sensors. 
Modbus Tool.exe is included with every BlueConnect Module.

 2

 

In the program windows, the internal designations of the modules are used: 

 

pH + Temp. = BlueConnect pH | ISE + Temp. = BlueConnect ISE |  

| ORP + Temp. = BlueConnect Redox |  

 

| Oxygen = BlueConnect O2 | Conductivity = Conductivity | Oil in Water = BlueTrace Oil in Water |  

| Turbidity = BlueTrace Turbidity | 

 

| Current Input Module = BlueConnect Current In | Current Output Module = BlueConnect Current Out |  

 

4.1 Preparation 

In order for your PC to communicate with a Modbus sensor, 
you need a 

converter from RS485 to USB

 and 

driver software

As an example, here is the Modbus USB

3

 converter of GO Sys-

temelektronik (Article No. 486 S810) with the driver software 
at: 

https://ftdichip.com/drivers/d2xx-drivers there „D2XX Drivers“ 

The driver software creates a virtual COM Port in the Windows 
system – in this example "USB Serial Port (COM

n

)". 

Converter Slot X1 

connected with

 

BlueConnect Module Slot X3 

In case of communication problems: 

 

Check the earthing of the converter. 

 

Install the latest driver software. 

Board of the converter module 

 

Opening the converter housing: see 

3.1 Opening the Module Housing 

                                                                    

1

  see also 

3.2 Cable Connections, Switch Positions and LEDs

 there 

Notes on termination of older BlueConnect Modules

 

2

  If not, contact GO Systemelektronik.                                                                                                                      

3

 USB 2.0 and newer 

 Earth the converter. 

Summary of Contents for BlueConnect

Page 1: ...Version of this manual 2 3 en www go sys de Manual BlueConnect Modules...

Page 2: ...ird parties about all identified dangers which could arise from the interaction between hardware and soft ware and from the use of other components Effective product observance is only possible with a...

Page 3: ...onfiguring Older Bus Modules 19 5 Modbus Address Overview of the Sensor Modules 20 Appendix A Interior Cover Stickers 24 Appendix B EU Declaration of Conformity 26 1 Introduction This manual describes...

Page 4: ...via CAN bus BlueConnect Modules are available in four basic variants as Sensor Module Bus Module Current Module and RS232 Module The necessary settings are made with a PC using the enclosed BlueConnec...

Page 5: ...0 x 85 mm Weight 0 35 kg IP protection code IP66 Ambient temperature 10 to 45 C Interfaces depending on version CAN bus Protocol is subset of CAN 2 0 Modbus Modbus RTU via serial interface RS485 RS232...

Page 6: ...ions and LEDs The module specific assignment is shown on the sticker on the inside of the housing cover Both the CAN bus and the Modbus are terminated at the factory Exception see next but one page No...

Page 7: ...de info go sys de Current Output Module 2x 4 20 mA RS232 Module RS232 Setting the COM Port with the DIP switches A B C D COM1 COM2 COM3 COM4 COM5 COM6 LED Functions LED Power Supply voltage is present...

Page 8: ...es the termination of CAN bus and Modbus is done via the configuration program Modbus Tool exe see 4 7 Configuring Older Bus Modules Older modules are not terminated at the factory If there is no poss...

Page 9: ...the BlueBox R1 Slot X07 YE GN WH TR RD GN RD GN BN OR BK WH BN BK BU RD PK WH BN BN GY BU BK WH WH BN O2 BU O2 BK BK PE pH pH IN 2 IN 1 IN IN OUT OUT PE GND Power TX RX TX RX PE GND Power RX TX GND Po...

Page 10: ...ere RS232 Modul Decimal separator is the comma The program is executable under Windows 7 and newer An Installation is not necessary the program starts when Modbus Tool exe is called up The program aut...

Page 11: ...CON Ports existing on your computer Here you must select the correct COM Port for communication with the converter The program detects the connected BlueConnect Module Via Change COM Port you can chan...

Page 12: ...s These value pairs are taken as points in a coordinate system The curve of a 1 to 5 Order polynomial is placed through these points as accurately as possible this is how the calibration polyno mial i...

Page 13: ...sfer activated Measure After first opening the calibration view the calibration table has only one row Click the cursor on the first row pushbutton As long as the row pushbutton is active the current...

Page 14: ...a window for entering the storage path of a csv file After the file has been created the recording of the measurement values into the csv file starts The button changes to At the bottom right of the p...

Page 15: ...ficient O2 Calibration coefficients the displayed values are from the Calibration function see 4 4 The Calibration Window Coefficient Temperature Only visible with Sensor Modules Factory calibration c...

Page 16: ...Start 2 Hold the oxygen sensor in the air 2 Wait at least 10 minutes until the displayed values are stable 3 Click on 100 Calibration 4 The calibration is completed Note Decimal separator is the comm...

Page 17: ...s the displayed values are from the Calibration function see 4 4 The Calibration Window Writes the input settings into the module memory Settings that have not yet been saved are marked in red Note De...

Page 18: ...ings that have not yet been saved are marked in red Current Output 1 Current Output 1 For test purposes you can enter input values here By clicking on the module outputs the corresponding current valu...

Page 19: ...der BlueConnect Bus Modules the newer ones are terminated with slide switches on the board see 3 2 Cable Connections Switch Positions and LEDs there also Notes on termination of older BlueConnect Modu...

Page 20: ...04 Baud rate 0 2 0 9600 8N1 Short R 0x05 Production date ddmmyyyy Date Short x 2 R Address Parameter name Range Meaning Data type Authorisation 0x14 A0 0 0xffffffff Cal Coefficient 32 Bit Float R W 0x...

Page 21: ...d rate 0 2 0 9600 8N1 Short R 0x05 Production date ddmmyyyy Date Short x 2 R Address Parameter name Range Meaning Data type Authorisation 0x14 A0 0 0xffffffff Cal Coefficient A0 32 Bit Float R W 0x16...

Page 22: ...rate 0 2 0 9600 8N1 Short R 0x05 Production date ddmmyyyy Date Short x 2 R Address Parameter name Range Meaning Data type Authorisation 0x14 A0 0 0xffffffff Cal Coefficient A0 32 Bit Float R W 0x16 A1...

Page 23: ...d rate 0 2 0 9600 8N1 Short R 0x05 Production date ddmmyyyy Date Short x 2 R Address Parameter name Range Meaning Data type Authorisation 0x14 A0 0 0xffffffff Cal Coefficient A0 32 Bit Float R W 0x16...

Page 24: ...n e c t I n t e r i o r C o v e r S t i c k e r s GO Systemelektronik GmbH Faluner Weg 1 24109 Kiel Germany Tel 49 431 58080 0 Fax 58080 11 Page 24 26 www go sys de info go sys de Appendix A Interior...

Page 25: ...B l u e C o n n e c t I n t e r i o r C o v e r S t i c k e r s GO Systemelektronik GmbH Faluner Weg 1 24109 Kiel Germany Tel 49 431 58080 0 Fax 58080 11 Page 25 26 www go sys de info go sys de...

Page 26: ...E U D e c l a r a t i o n o f C o n f o r m i t y GO Systemelektronik GmbH Faluner Weg 1 24109 Kiel Germany Tel 49 431 58080 0 Fax 58080 11 Page 26 26 www go sys de info go sys de Appendix B EU Decla...

Reviews: