D5212
- SIL 2 Quadruple Repeater Power Supply
G.M. International ISM0361-3
2
General Description:
The quadruple channel Repeater Power Supply D5212Q provides a fully floating DC supply for energizing conventional 2-wire 0/4-20 mA transmitters located in Hazardous Area, and
repeats the current in Safe Area to drive a load in applications requiring SIL 2 level (according to IEC 61508:2010) in safety related systems for high risk industries.
Function:
4 channels I.S. analog input for 2-wire loop powered transmitters (or separately powered inputs, only for channels 1 and 2), providing isolation between input, output and supply, and
current source output signals. The module is fully configurable to achieve any desired input/output combination: any number of outputs can be independently linked to each input.
Output function can be configured as: adder, subtractor, low/high selector. An optically coupled open-drain alarm output with user-settable trip point is also provided.
Modbus RTU RS-485 output is available on Bus connector to interface digital device.
Configurability:
Totally software configurable (no jumpers or switches), by PC via USB with PPC5092 adapter and related configurator software or by RS485 Modbus output, in order to choose: input
signal range, linear or reverse output signal, alarm trip point, low, high, window or fault repeater alarm mode, hysteresis, delay time.
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards, in Safe Area or in Zone 2.
Technical Data
Characteristics
Supply:
24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits
≤
5 Vpp, 2 A time lag fuse internally protected.
Current consumption @ 24 V:
200 mA max. with 20 mA input/output for 4 channels.
Power dissipation:
2.75 W max. with 24 V supply voltage and 20 mA input/output for 4 channels.
Isolation (Test Voltage):
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Out/Supply 500 V; I.S. In/Alarm 1.5 KV; Supply/Alarm 500 V; Out/Alarm 500 V.
Input:
0/4 to 20 mA (2 wire Tx current limited at
≈
25 mA) and separately powered inputs (only for channels 1 and 2).
Transmitter line voltage:
14.5 V typical at 20 mA with max. 20 mVrms ripple, 14.0 V minimum.
Integration time:
500 ms.
Resolution / Visualization:
1
μ
A.
Fault:
Out-of-range (burnout) fault detection can be enabled or disabled. Any analog output can be programmed to detect fault condition forcing downscale or highscale. Alarm can be
programmed to detect fault condition. Fault conditions are also signalled via Power Bus or Termination Board and by a red LED on the front panel (one for each channel).
Out-of-range:
low and high separated trip point values are fully programmable.
Output:
0/4 to 20 mA, on max. 300
Ω
load source mode, current limited at about 25 mA.
Response time:
100 ms max. (10 to 90 % step change).
Output ripple:
≤
20 mVrms on 250
Ω
.
Modbus Output:
for parameter configuration and burnout / fault indication. Modbus RTU protocol up to 57.6 Kbit/s with RS-485 connection on Power Bus connector.
Alarm:
Trip point range:
within rated limits of the input sensors.
Output:
voltage free SPST photoMOS: 100 mA, 60 Vdc (
≤
1 V voltage drop).
Performance:
Ref. Conditions 24 V supply, 250
Ω
loads, 23 ± 1 °C ambient temperature.
Calibration accuracy:
≤
± 0.05 % of full scale on inputs and outputs.
Linearity error:
≤
± 0.05 % of full scale on inputs and outputs.
Supply voltage influence:
≤
± 0.02 % of full scale for a min to max supply change.
Load influence:
≤
± 0.02 % of full scale for a 0 to 100 % load resistance change.
Temperature influence:
≤
± 0.01% of input full scale and
≤
± 0.005 % of output full scale for a 1 °C change.
Compatibility:
CE mark compliant, conforms to Directives:
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating:
temperature limits -40 to + 70 °C, relative humidity 95 %, up to 55 °C.
Storage:
temperature limits -45 to + 80 °C.
Max altitude:
2000 m a.s.l.
Safety Description:
ATEX:
II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I;
IECEx:
Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I,
UL:
NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, AEx nA [ia Ga] IIC T4 Gc
C-UL:
NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, Ex nA [ia Ga] IIC T4 Gc X
EAC-EX:
2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC, [Ex ia Ma] I
CCC:
Ex nA [ia Ga] IIC T4 Gc, [Ex ia Ga] IIC, [Ex iaD]
associated apparatus and non-sparking electrical equipment.
Uo/Voc = 24.1 V, Io/Isc = 86 mA, Po/Po = 516 mW at terminals 13-14, 15-16, 17-18, 19-20.
Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 21-22, 23-24.
Ui/Vmax = 30 V at terminals 21-22, 23-24.
Ii/Imax = 128 mA at terminals 21-22, 23-24.
Ci = 2.1 nF, Li = 0 nH at terminals 21-22, 23-24.
Um = 250 Vrms, -40 °C
≤
Ta
≤
70 °C.
Approvals:
DEMKO 18 ATEX 2017X conforms to EN60079-0, EN60079-11, EN60079-15; IECEx ULD 18.0013X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15,
UL 121201 for UL and CSA C22.2 60079-0, CSA C22.2 60079-11, CSA C22.2 60079-15 CSA C22.2 No. 213 for C-UL.
RU C-IT.EX01.B.00018/19 conforms to GOST 31610.0,GOST 31610.11, GOST 31610.15.
CCC 2020322316000978 conforms to GB3836.1, GB3836.4; GB3836.8, GB12476.1, GB12476.4.
DNV No. TAA00001U0 and KR No.MIL20769-EL002 for maritime applications.
SIL 2 conforms to IEC61508:2010 Ed.2.
Mounting:
EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus or on customized Termination Board.
Weight:
about 120 g.
Connection:
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm
2
.
Location:
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4 installation.
Protection class:
IP 20.
Dimensions:
Width 22.5 mm, Depth 123 mm, Height 120 mm.