D5091 

- 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition 

G.M. International ISM0110-12 

Ordering Information 

 

Front Panel and Features 

 



SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 6 / 20 yrs (

10% / >10 % of total SIF) for ND load with ND relay 

(terminals 7-8). 



SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 14 / 20 yrs (

10% / >10 % of total SIF) for ND load with NE relay 

(terminals 9-10). 



PFDavg (1 year) 1.59 E-05, SFF 96.35 % for ND load with ND relay. 



PFDavg (1 year) 7.01 E-06, SFF 99.17 % for ND load with NE relay. 



Systematic capability SIL 3. 



Installation in Zone 2 / Division 2. 



1 SPDT contact for 2 different Safety Functions: 

1) SIL 3 for ND load (energized in fail safe state) with ND relay condition (energized in fail safe state) 

2) SIL 3 for ND load (energized in fail safe state) with NE relay condition (de-energized in fail safe state) 



6 A inrush current at 24 Vdc / 250 Vac. 



Line input monitoring in-field DIP Switch selectable. 



Driving input voltage monitoring. 



Input/Output isolation. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system. 



ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, NEPSI, TÜV Certifications. 



TÜV Functional Safety Certification. 



Type Approval Certificate DNV and KR for maritime applications. 



Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards. 

Model: D5091S 

DIN-Rail accessories: Cover and fix MCHP196 

SPDT Output Common 

Terminal block connections 

SAFE AREA 

SPDT Output Normally Open Contact 

SPDT Output Common 

SPDT Output Normally Close Contact 

7

 

8

 

9

 

10

 

+ Input 

1

 

- Input 

2

 

7 8 

9 10 

D5091 

SIL 3 

10 

STS 

Summary of Contents for D5091S

Page 1: ...Module for ND Load with ND or NE Relay condition G M International ISM0110 12 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition DIN Rail and Termination Board Model D5091S D5091...

Page 2: ...ing disabled 45 mA with relay energized and line input monitoring enabled typical Power dissipation 0 85 W with 24 V input voltage relay energized and line input monitoring disabled 1 1 W with 24 V in...

Page 3: ...fail safe state 2 SIL 3 for ND load energized in fail safe state with NE relay condition de energized in fail safe state 6 A inrush current at 24 Vdc 250 Vac Line input monitoring in field DIP Switch...

Page 4: ...d connector SIL3 SPDT Out ND Load 7 8 or 9 10 Relay contact shown in de energized position Terminals 7 8 open terminals 9 10 close SIL3 Safety Function for ND load energized in fail safe state is avai...

Page 5: ...ined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor a d...

Page 6: ...defined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor...

Page 7: ...between the input and output contacts D5091S provides 1 SPDT contact for two different safety functions 1 SIL 3 Safety Function for Normally De Energized load energized in fail safe state is availabl...

Page 8: ...al operation To prevent relay contacts from damaging connect an external protection fuse or similar chosen according to the relay breaking capacity diagram from installation instructions The enclosure...