6
D5014
- SIL 3 Repeater Power Supply
G.M. International ISM0103-3
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4
Connections for Duplication of 2 wires Transmitter Input
Restriction on specifications for 2 wires Transmitter Input:
Bidirectional communication for Smart Transmitter is provided only on channel 1
The minimum supply voltage available for Transmitter (Vtx) is 14 V at 20 mA input
The safety parameters must be changed in: Uo/Voc = 27 V, Io/Isc = 93 mA, Po/Po = 623 mW
Terminals 7-10
Uo/Voc = 27 V
Io/Isc = 93 mA
Po/Po = 623 mW
IIC
IIB
IIA
0.090
0.705
2.330
4.1
16.6
33.2
57.0
228.3
456.6
Group
Cenelec
Lo/Ro
(µH/
Ω
)
Lo/La
(mH)
Co/Ca
(µF)
I
iaD
3.750
0.705
54.5
16.6
749.1
228.3
=
=
=
5 +
6 -
1
2
RL
mA
+
-
HHT
Source I
Out 1 (SIL 3)
3
4
RL
mA
+
-
Source I
Out 2 (SIL 3)
7
11
10
12
8
9
MODEL D5014D Duplicator
+
-
Termination
board
connector
Power Bus
=
=
=
=
=
=
=
Supply 24 Vdc
+
-
HHT
2 Wire Tx
I
?
In 1
mA
+
V
Source V
Sink I
+
-
+
-
RL
mA
+
V
Source V
Sink I
+
-
+
-
RL
Safety Description