GM International D1049S Instruction & Safety Manual Download Page 8

 

D1049 

- SIL 3 Digital Output Driver NE Loads Bus Powered 

G.M. International ISM0097-9 

D1049 is an isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/ Non Hazardous Locations or 
Zone 2, Group IIC, Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 
Hazardous Area/Hazardous Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) 
within the specified operating temperature limits Tamb -20 to +60 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1049 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1049 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

 

Start-up 

 

Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. 
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. 
Turn on power, the “power on” green led must be lit, “status” led and fault led must were in accordance with condition of the corresponding output line. 
If possible change the status of driving signal and connection line one at time checking the corresponding status and fault leds condition as well as output to be correct. 

The single channel DIN-Rail Bus Powered Digital Output Isolator, D1049S, is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, or 
other process control devices in Hazardous Area from a driving signal in Safe Area. It can also be used as a controllable supply to power measuring or process control equipment. 
Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508) in safety related systems for high risk industries. 
The Safety PLC or DCS driving signal controls the field device through the D1049S, which provides isolation and is capable of monitoring the conditions of the line. 
Short and open circuit diagnostic monitoring, dip-switch selectable, operates irrespective of the output condition and provides LED indication and NC transistor output signaling. 
When fault is detected output is de-energized until normal condition is restored. 
An override input, dip-switch selectable, is provided to permit a safety system to override the control signal. When enabled, a low input voltage always de-energizes the field device 
regardless of the input signal. 
Three basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market. The selection among the three output characteristics 
is obtained by connecting the field device to a different terminal block. 
Presence of supply power, output status, as well as integrity or fault condition of device and connecting line are displayed by signaling LEDs (green for power, yellow for status, red for fault). 

Operation 

 

 

D1049 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Must not use or generate

more than 250 Vrms or Vdc

Unclassified Locations

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

-

16

Intrinsically 

Safe Equipment

+

15

14

13

+

+
+

+

+

14

-

+

16

15

+

13

8

-

4

3

-

+

7

+

+

-

Control 

Equipment

Control 

Equipment

Power Supply

Control 

Equipment

+

-

Non-incendive

Equipment

5
6

1
2

4

3

2

1

-

+

-

+

7
8

+

-

6

5

-

+

Control 

Equipment

Power Supply

Control 

Equipment

Control 

Equipment

D1049 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Summary of Contents for D1049S

Page 1: ...D1049 SIL 3 Digital Output Driver NE Loads Bus Powered ISM0097 9 D1049S INSTRUCTION SAFETY MANUAL SIL 3 Digital Output Driver NE Loads Bus Powered DIN Rail Model D1049S ...

Page 2: ...ent consumption 24 V 5 mA Output 45 mA at 13 0 V 21 0 V no load 174 Ω series resistance at terminals 13 16 Out A 45 mA at 10 2 V 21 0 V no load 236 Ω series resistance at terminals 14 16 Out B 45 mA at 8 5 V 21 0 V no load 275 Ω series resistance at terminals 15 16 Out C Short circuit current 50 mA 55 mA typical Response time 10 ms Frequency response 50 Hz Fault detection field device and wiring o...

Page 3: ...t limited Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 In field programmability by DIP Switch ATEX IECEx FM FM C INMETRO EAC EX UKR TR n 898 TÜV Certifications TÜV Functional Safety Certification Type Approval Certificate DNV for maritime applications High Reliability SMD components Simplified installation using standard DIN Rail and plug in termi...

Page 4: ...evice Cable Parameters D1049 Terminals D1049 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Lo La 1 65 mH Lo La 6 63 mH Lo La 13 2 mH IIB C IIA D IIC A B Lo La 2 9 mH Lo La 11 8 mH Lo La 23 6 mH IIB C IIA D IIC A B Lo La 4 19 mH Lo La 16 7 mH Lo La 33 5 mH IIB C IIA D IIC A B Out C 15 16 Io Isc 147 mA Ii Imax Out A 13 16 Out B 14 16 Io Isc 110 mA Out C 15 16 Io Isc 93 mA...

Page 5: ...ly examined in combination as a system when the above conditions are respected For Division 1 and Zone 0 installations the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept or third party approved for Division 2 installations the configuration of Intrinsically Safe Equipment must be FM approved under non incendive field wiring or Entity Concept or third party a...

Page 6: ...wered which provides the electrical isolation between Supply Input and Output The presence of the input control signal is also indicated by a yellow LED on the front panel In order to interface the majority of field devices available on the market two basic output circuits with different safety parameters outputs A B and C are provided for channel The selection among the three output characteristi...

Page 7: ...detection Replace the series connection of a 1 kΩ load resistor and an ammeter with a current calibrator set to 45 mA This current generator and a voltmeter are connected in parallel to one of the module outputs starting with Out A then going on with Out B and finally proceeding with Out C Supply the D5049S or D1049S mod ule at 24 Vdc and apply a 24 Vdc ON control signal to the module input channe...

Page 8: ...horts Turn on power the power on green led must be lit status led and fault led must were in accordance with condition of the corresponding output line If possible change the status of driving signal and connection line one at time checking the corresponding status and fault leds condition as well as output to be correct The single channel DIN Rail Bus Powered Digital Output Isolator D1049S is sui...

Page 9: ...t used SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled 1 1 ON SW2 IN OUT Operation Used for SIL applications Input high 24 Vdc output energized or Input low 0 Vdc output de energized Input high 24 Vdc output de energized or Input low 0 Vdc output energized Override control input Disabled Enabled 4 4 ON OFF OFF SW2 dip switch configuration 1 2 3 4 ON Not Used SW1 factory setting...

Reviews: