GM International D1049S Instruction & Safety Manual Download Page 2

 

D1049 

- SIL 3 Digital Output Driver NE Loads Bus Powered 

G.M. International ISM0097-9 

General Description: 

The single channel DIN-Rail Bus Powered Digital Output Isolator, D1049S, is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, 

or other process control devices in Hazardous Area from a driving signal in Safe Area. It can also be used as a controllable supply to power measuring or process control equipment. 
Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries. 
The Safety PLC or DCS driving signal controls the field device through the D1049S, which provides isolation and is capable of monitoring the conditions of the line. 
Short and open circuit diagnostic monitoring, dip-switch selectable, operates irrespective of the channel condition and provides LED indication and NC transistor output signaling. 
When fault is detected output is de-energized until normal condition is restored. 
An override input, dip-switch selectable, is provided to permit a safety system to override the control signal. When enabled, a low input voltage always de-energizes the field device 
regardless of the input signal. 
Three basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market. The selection among the three output characteristics 
is obtained by connecting the field device to a different terminal block. 

Function: 

1 channel I.S. digital output to operate Hazardous Area normally energized loads from contacts, logic levels or driven logics in Safe Area. 

It provides 3 port isolation (input/output/supply). 

Signalling LEDs: 

Power supply indication (green), outputs status (yellow), fault condition (red). 

Field Configurability: 

Line Fault Detection enable or disable and Override Control Input enable or disable. 

EMC: 

Fully compliant with CE marking applicable requirements. 

Functional Safety Management certification:

G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6  

for safety related systems up to and included SIL3. 

 

Characteristics 

Supply:

 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp, 2 A time lag fuse internally protected. 

Current consumption @ 24 V:

 65 mA with 45 mA output typical in normal operation. 

Power dissipation:

 1.1 W with 24 V supply, output energized at 45 mA nominal load. 

Max. power consumption:

 at 30 V supply voltage, 1.8 W. 

Isolation (Test Voltage): 

I.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; I.S. Out/Fault 1.5 KV; I.S. Out/Override 1.5 KV; 

In/Supply 500 V; In/Fault 500 V; In/Override 500 V; Supply/Fault 500 V; Supply/Override 500 V; Fault/Override 500 V. 

Control Input: 

switch contact, logic level reverse polarity protected. 

Trip voltage levels:

 OFF status 

 5.0 V, ON status 

 20.0 V (maximum 30 V). 

Current consumption @ 24 V:

 5 mA. 

Override Input: 

override control signal de-energizes output when enabled by dip-switch. 

Override range:

 

24 Vdc nom (20 to 30 Vdc) to disable (field device controlled by input), 0 to 5 Vdc to de-energize field device, reverse polarity protected. 

Current consumption @ 24 V:

 5 mA. 

Output:

 

45 mA at 13.0 V (21.0 V no load, 174 

 series resistance) at terminals 13-16 Out A. 

45 mA at 10.2 V (21.0 V no load, 236 

 series resistance) at terminals 14-16 Out B. 

45 mA at 8.5 V (21.0 V no load, 275 

 series resistance) at terminals 15-16 Out C. 

Short circuit current: 

 50 mA (55 mA typical). 

Response time: 

 10 ms. 

Frequency response:

 50 Hz 

Fault detection: 

field device and wiring open circuit or short circuit detection dip-switch selectable. When fault is detected output is de-energized until normal condition is restored.

 

Short output detection: 

load resistance 

 50 

 (

 2 mA forcing to detect fault). 

Open output detection: 

load resistance > 10 K

Fault signalling: 

voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition). 

Open-collector rating: 

100 mA at 35 Vdc (

 1.5 V voltage drop). 

Leakage current: 

 50 µA at 35 Vdc. 

Response time: 

 5 ms. 

Compatibility: 

 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions:  

 

Operating:

 temperature limits -20 to + 60 °C, relative humidity max 95 %. 

Storage:

 temperature limits – 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3(1) G Ex nA [ia Ga] IIC T4 Gc, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I 

IECEx: 

Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I, 

FM: 

NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx [ia] IIC  

FMC: 

NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex [ia] IIC  

EAC-EX: 

2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC X, [Ex ia Ma] I X  

UKR TR n. 898: 

2ExnAiaIICT4 X, ExiaI X 

associated apparatus and non-sparking electrical equipment. 

Uo/Voc = 24.8 V, Io/Isc = 147 mA, Po/Po = 907 mW at terminals 13-16 Out A. 

Uo/Voc = 24.8 V, Io/Isc = 108 mA, Po/Po = 667 mW at terminals 14-16 Out B. 

Uo/Voc = 24.8 V, Io/Isc = 93 mA, Po/Po = 571 mW at terminals 15-16 Out C. 

Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals:  

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-15, EN60079-26, 

IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-15, IEC60079-26, 

INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26. 

FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810, ANSI/ISA 12.12.02, ANSI/ISA 60079-0, and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, 

E60079-11, E60079-15. 

C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0,GOST R IEC 60079-11, GOST R IEC 60079-15. 

C

Ц

 16.0034 X conforms to 

ДСТУ

 7113, 

ГОСТ

 22782.5-78, 

ДСТУ

 I

ЕС

 60079-15. 

TUV Certificate No. C-IS-236198-04, SIL 3 conforms to IEC61508:2010 Ed. 2.  

TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

DNV No.A-13778 Certificates for maritime applications.

 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight:

 about 130 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

Technical Data 

2

4

6

8

10

12

14

16

18

20

22

13

V (V)

0

D1049 Output Diagram

Rout 

 174 



(Out A)

10

0

20

30

40

50

10.2

21

8.5

45

Vo 

 21.0 V (no load)

Rout 

 236 



(Out B)

Rout 

 275 



(Out C)

Ilim 

 50 mA

I (mA)

Out A

Out B

Out C

FSM

SIL 3

Summary of Contents for D1049S

Page 1: ...D1049 SIL 3 Digital Output Driver NE Loads Bus Powered ISM0097 9 D1049S INSTRUCTION SAFETY MANUAL SIL 3 Digital Output Driver NE Loads Bus Powered DIN Rail Model D1049S ...

Page 2: ...ent consumption 24 V 5 mA Output 45 mA at 13 0 V 21 0 V no load 174 Ω series resistance at terminals 13 16 Out A 45 mA at 10 2 V 21 0 V no load 236 Ω series resistance at terminals 14 16 Out B 45 mA at 8 5 V 21 0 V no load 275 Ω series resistance at terminals 15 16 Out C Short circuit current 50 mA 55 mA typical Response time 10 ms Frequency response 50 Hz Fault detection field device and wiring o...

Page 3: ...t limited Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 In field programmability by DIP Switch ATEX IECEx FM FM C INMETRO EAC EX UKR TR n 898 TÜV Certifications TÜV Functional Safety Certification Type Approval Certificate DNV for maritime applications High Reliability SMD components Simplified installation using standard DIN Rail and plug in termi...

Page 4: ...evice Cable Parameters D1049 Terminals D1049 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Lo La 1 65 mH Lo La 6 63 mH Lo La 13 2 mH IIB C IIA D IIC A B Lo La 2 9 mH Lo La 11 8 mH Lo La 23 6 mH IIB C IIA D IIC A B Lo La 4 19 mH Lo La 16 7 mH Lo La 33 5 mH IIB C IIA D IIC A B Out C 15 16 Io Isc 147 mA Ii Imax Out A 13 16 Out B 14 16 Io Isc 110 mA Out C 15 16 Io Isc 93 mA...

Page 5: ...ly examined in combination as a system when the above conditions are respected For Division 1 and Zone 0 installations the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept or third party approved for Division 2 installations the configuration of Intrinsically Safe Equipment must be FM approved under non incendive field wiring or Entity Concept or third party a...

Page 6: ...wered which provides the electrical isolation between Supply Input and Output The presence of the input control signal is also indicated by a yellow LED on the front panel In order to interface the majority of field devices available on the market two basic output circuits with different safety parameters outputs A B and C are provided for channel The selection among the three output characteristi...

Page 7: ...detection Replace the series connection of a 1 kΩ load resistor and an ammeter with a current calibrator set to 45 mA This current generator and a voltmeter are connected in parallel to one of the module outputs starting with Out A then going on with Out B and finally proceeding with Out C Supply the D5049S or D1049S mod ule at 24 Vdc and apply a 24 Vdc ON control signal to the module input channe...

Page 8: ...horts Turn on power the power on green led must be lit status led and fault led must were in accordance with condition of the corresponding output line If possible change the status of driving signal and connection line one at time checking the corresponding status and fault leds condition as well as output to be correct The single channel DIN Rail Bus Powered Digital Output Isolator D1049S is sui...

Page 9: ...t used SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled 1 1 ON SW2 IN OUT Operation Used for SIL applications Input high 24 Vdc output energized or Input low 0 Vdc output de energized Input high 24 Vdc output de energized or Input low 0 Vdc output energized Override control input Disabled Enabled 4 4 ON OFF OFF SW2 dip switch configuration 1 2 3 4 ON Not Used SW1 factory setting...