D1049
- SIL 3 Digital Output Driver NE Loads Bus Powered
G.M. International ISM0097-9
3
Ordering information
Power Bus and DIN-Rail accessories:
DIN rail anchor MCHP065
DIN rail stopper MOR016
Terminal block male MOR017
Terminal block female MOR022
D1049
1 2 3 4
16
15
14
13
5 6 7 8
PWR ON
STATUS
FAULT
Front Panel and Features
SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 12 / 20 yrs (
≤
10% / >10 % of total SIF).
PFDavg (1 year) 8.32 E-06, SFF 98.90 %.
SIL 3 Systematic capability
Output to Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
Bus powered for NE loads.
Short and open circuit line diagnostic monitoring with LED, transistor output.
Output short circuit proof and current limited.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1.
In-field programmability by DIP Switch.
ATEX, IECEx, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV for maritime applications.
High Reliability, SMD components.
Simplified installation using standard DIN-Rail and plug-in terminal blocks.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
+ Output A for Solenoid Valve
Terminal block connections
HAZARDOUS AREA
SAFE AREA
+ Output B for Solenoid Valve
+ Output C for Solenoid Valve
- Output for Solenoid Valve
13
14
15
16
+ Output Transistor Fault
1
- Output Transistor Fault
2
+ Power Supply 24 Vdc
3
- Power Supply 24 Vdc
4
+ Input for Control
5
- Input for Control
6
+ Input for Override
7
- Input for Override
8
Model:
D1049S
Power Bus enclosure
/B