German Light Products®
Impression FR10 Bar Quick Start and Safety Manual Rev. A
17
Installing power connectors
If you intend to draw power from convenience receptacles / consumer mains power
sockets, it is possible to install a suitable cord cap / power plug on the supplied power
cord / input cable. If you do this, check that the cord cap / plug is rated minimum
250 V, 16 A, that it has a connection to ground / earth and that it has an integral cable
grip. Follow the cord cap / plug manufacturer’s assembly instructions.
If you need to install a Neutrik powerCON TRUE1 connector on a power cable, follow
the instructions given in the Support area of the Neutrik website at www.neutrik.com.
Respect the color coding used in the supplied power cable and in your local mains
power wiring system. US and EU systems use the color coding shown below:
Live or L
Neutral or N
Ground / Earth or
US system
Black White
Green
EU system
Brown Blue Yellow/green
Connecting multiple fixtures to power in a chain
You can connect fixtures to power in a daisy-chain to simplify your power circuit
layout.
Warning!
Do not connect more than two (2) FR 10 Bar fixtures in total to
power in one chain at 100-120 V, 60 Hz. Do not connect more than four (4)
FR 10 Bar fixtures in total to power in one chain at 200-240 V, 50 Hz.
The power input cable supplied with the fixture is rated 16 A maximum. Add
together the maximum current draw ratings of all the devices that you
intend to connect to power in a daisy chain and do not create a chain with
a total maximum current draw of more than 16 A, or you will create a risk of
fire and electric shock.
To connect fixtures to power in a chain:
Obtain power relay cables that have male and female Neutrik powerCON TRUE1
connectors. Cables must be minimum 14 AWG or 1.5mm
2
, rated minimum 16 A and
suitable for the environment and application.
Connect the power input cable to the Mains IN socket of the first fixture.
If you are operating the FR10 Bar on 100-120 V, 60 Hz AC mains power, you can
connect maximum one FR10 Bar to the mains THRU socket (for a maximum of 2
fixtures total connected together in a chain) using a power relay cable. Do not
connect any devices to the Mains THRU socket of the second fixture.
If you are operating the FR10 Bar on 200-240 V, 50 Hz AC mains power, you can
connect maximum three FR10 Bars to the mains THRU socket (for a maximum of 4
fixtures total connected together in a chain) using power relay cables. Do not
connect any devices to the Mains THRU socket of the fourth fixture.