COMMISSIONING 
 
Preparation 

1.

Check sounder cables and ensure all field connections are made. Ensure that all EOL Resistor are fitted to the last 

sounder of each circuit.  
2.

Connect sounder lines to panel 

3.

Remove the mains fuse 

4.

Connect mains supply according to local mains voltage Ensure good earth connection  

5.

Fit batteries (do not connect) 

6.

Insert mains fuse  

7.

Connect batteries - observe correct polarity. 

 
 
 
 

 

 
 
 

Commissioning  

1.

If all is normal only the Green “supply”LED should be illuminated.  

2.

If any Faults are indicated they should be corrected before proceeding. 

3.

Initiate lamp test and confirm LEDs and internal buzzer operation. 

4.

Test each key for correct functioning. 

5.

Test all sounders, relays etc. for proper operation. 

 

 
TESTING FIELD EQUIPMENT 

 

Testing Sounders 

 

1.

 Introduce the Level 2 Access code (2244) 

with the Buzzer OFF

2.

 Initiate sounder pressing Sounders Activate/ Silence  

3.

 Press again to stop 

 
Testing Relay Outputs 

 
With the Addressable system in normal operating mode, activate a Fire Alarm and confirm operation of Fire relays. Test if 
manual button Sounder activation, also activates the Fire relay.  
 
On the Fault Relay test, generate a fault (example: remove the sounder circuit EOL or remove Mains Power) and verify the 
Fault relay operation. 

 
NOTE: 

Communication faults between ORION-BCM LSC and the Addressable System will only be 

signaled at the Addressable panel. Fault relay will not activate if ADLI-BCM is unplugged. 

 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for ORION-BCM LSC

Page 1: ...ault detection and notification listed below In addition to local notification status is also reported to addressable system Sounder Circuit Integrity Fault Battery Charger Fault voltage level and cha...

Page 2: ...voltage detector and sounder cabling The panel should be fixed to the wall using the 4 mounting holes provided and No 8 10 countersunk screws Any dust created during the fixing process must be kept o...

Page 3: ...ng If a sounder circuit is not used the EOL resistor should be fitted in the control panel sounder output The sounder circuits are protected against short circuits the electronic fuse will reset when...

Page 4: ...Connect it to C input for activation NOTE EV always activate S1 even if sounders are disabled CONNECTING THE PANEL The mains supply should be routed away from the other cables and enter the control pa...

Page 5: ...re Relay and EV Sounder direct activation non monitored E Auxiliary Supply Output monitored Addressable Interface ADLI BCM Connections The following board is placed inside the box A DIL Switch for add...

Page 6: ...indicate any FAULT condition present on panel DISABLED Used to indicate that the panel has features that have been disabled in Access Level 2 SUPPLY Used to indicate the presence of supply In Access...

Page 7: ...unders Auxiliary Fault Relays is not affected by this action NOTE When reset all LEDs will flash and relays will pulse DISABLEMENTS These buttons are only active at Level 2 access These buttons have a...

Page 8: ...Level 1 General user controls This lower level allows the user to Perform a lamp test Silence Internal buzzer Put the panel into Access Level 2 if in possession of the required access code Level 2 Aut...

Page 9: ...test and confirm LEDs and internal buzzer operation 4 Test each key for correct functioning 5 Test all sounders relays etc for proper operation TESTING FIELD EQUIPMENT Testing Sounders 1 Introduce th...

Page 10: ...fault is present when there is a voltage below 20 V DC at the battery terminals or if there is a battery charger problem Charger problems can be caused by panel s hardware failure or batteries that h...

Page 11: ...y using two external independent switches on the inputs overlap the addressable order the Sounder Output or the Fire Alarm Relay state Example of application Door Holder This implementation has the ab...

Page 12: ...ER CIRCUIT NUMBER OF CIRCUITS 1 END OF LINE RESISTOR VALUE 10K Ohms MONITORING Open and Short Circuit ALARM VOLTAGE 27 5V DC SOUNDER CIRCUIT FUSE 1 1 Amp resettable Electronic Fuse MAX CURRENT AVAILAB...