Addressable Analog Values
The following analog values are the ORION-BCM LSC represent the conditions reported to the Addressable System.
ANALOG VALUE
DESCRIPTION
IO unit (DIL switch address):
21
NORMAL – No Faults present
4
FAULT – Communication with ORION-BCM LSC
2
FAULT – System Fault (Battery, Mains, Earth, etc.) External Supply Fault
Sounder (consecutive address):
17
ACTIVATED – Sounder circuit ON
16
NORMAL – Sounder circuit OFF
8
FAULT – Sounder Circuit Fault (open/short circuit, etc.)
4 (see Note)
FAULT – Communication with ORION-BCM LSC
NOTE:
This status is only reported by the addressable panel. ORION-BCM LSC doesn’t report fault and fault relay is
not activated.
ACCESS LEVELS
There are two levels of Access in the ORION-BCM LSC.
Level 1: General user controls
This lower level allows the user to:
●
Perform a lamp test
●
Silence Internal buzzer
●
Put the panel into Access Level 2 if in possession of the required access code
Level 2: Authorized user controls (AUTH MODE CODE: 2244)
This higher level allows the user to:
●
Silence and Activate sounder circuit
●
Reset after Fault
●
Silence Internal Buzzer
●
Test status LEDs
●
Disable/ Enable the following:
o
Sounders Conventional Output
o
Auxiliary Outputs - Fire/Sounder Relay and Fault Relay
Level 2 Access is gained by entering the code 2244 using the numbered buttons.
NOTE:
If any Fault event have occurred these must be acknowledged by pressing the Buzzer Silence
button
before code entry will be accepted
.
If the code is not completed within 20 seconds of the last key press, the system reverts to Level 1.
Once this mode is entered the GREEN LED (SUPPLY) will flash once every 0.5 seconds.
To exit this mode at any time, press the RESET button. The panel will revert to Access Level 1.