background image

 

 

Global Fire Equipment // 

globalfire.pt 

ma_orionbcmlsc_01_010001_en_180711

 

 

 
STANDBY BATTERY CALCULATION 

 

Battery capacity

 

should be between 2 x 2.4 Ah 12V DC and 2 x 7 Ah 12V DC.

 

 
The battery Ah required for a given installation is calculated from the following formula: 
 

38mA 

Standby time 

required in hours 

divided by 1000 

Alarm & Aux. Supply  

Outputs in Amps 

(sounder & aux. supply load) 

Alarm time in 

hours 

 + 20% 

 
Round the result to the next available battery size. Quiescent current of the panel with everything is found by adding the

 

 

   

 

 

 

 

 

 

   

 

 

 

   

 

 

 

 

standby current of all connected devices to the standby current of the panel (38mA). Consult the manual for the individual

 

     

 

   

 

 

   

 

 

 

 

 

 

 

 

 

devices to confirm the standby current. 
 
 

Troubleshooting - Fault Indications  

 

Troubleshooting work of any fault on the panel should only be carried out by qualified technicians.  

 

General Fault  

The General fault LED is illuminated whenever there is a fault on the system. It is always lit along with at least one other fault 
indicator which gives more detail relating to the fault.  
 

Power Supply Faults - Supply Fault  

Associated with a low voltage (below 20V) present at the input of the power supply or the removal of the main power supply. 
Measure voltage levels and verify electrical mains fuse.  
 

Battery Fault  

This fault is present when there is a voltage below 20 V DC at the battery terminals or if there is a battery charger problem. 
Charger problems can be caused by panel's hardware failure or batteries that have not been connected in the specified 
manner as indicated in this manual, in the installation section. Verify if batteries are properly connected. Measure the voltage 
at the battery terminals and replace if it is below 21V DC. Remember to verify also the main electrical fuse. 
 
 

DON'T SHORT CIRCUIT BATTERY TERMINALS IN ORDER TO VERIFY BATTERY CHARGE ONLY USE 
BATTERIES THAT ARE LEAD ACID VRLA TYPE 12VDC.  

 

Aux Supply Fault  

This fault will show when the voltage at the auxiliary supply output is below 20 Volts DC. This can be caused by the current 
limit for this output being exceeded. This output is limited to 900mA. Other causes for faults at this point are short circuits in 
the wiring or faulty hardware attached to this supply output. Verify voltage, if below the required acceptable level remove 
wiring connected to this output. If voltage now returns to normal this confirms that connected equipment or cable is 
damaged.  
 

Earth Fault  

This FAULT will indicate that there is some level of current leakage between any of the wire conductors and the EARTH 
connections. VERIFY WIRING.  
 

System Fault 

This FAULT indicates that there is a fault at the main processor level. In this particular fault, the panel's main board needs to 
be replaced or repaired. 
 
 
 
 
 
 

 

10 

Summary of Contents for ORION-BCM LSC

Page 1: ...ault detection and notification listed below In addition to local notification status is also reported to addressable system Sounder Circuit Integrity Fault Battery Charger Fault voltage level and cha...

Page 2: ...voltage detector and sounder cabling The panel should be fixed to the wall using the 4 mounting holes provided and No 8 10 countersunk screws Any dust created during the fixing process must be kept o...

Page 3: ...ng If a sounder circuit is not used the EOL resistor should be fitted in the control panel sounder output The sounder circuits are protected against short circuits the electronic fuse will reset when...

Page 4: ...Connect it to C input for activation NOTE EV always activate S1 even if sounders are disabled CONNECTING THE PANEL The mains supply should be routed away from the other cables and enter the control pa...

Page 5: ...re Relay and EV Sounder direct activation non monitored E Auxiliary Supply Output monitored Addressable Interface ADLI BCM Connections The following board is placed inside the box A DIL Switch for add...

Page 6: ...indicate any FAULT condition present on panel DISABLED Used to indicate that the panel has features that have been disabled in Access Level 2 SUPPLY Used to indicate the presence of supply In Access...

Page 7: ...unders Auxiliary Fault Relays is not affected by this action NOTE When reset all LEDs will flash and relays will pulse DISABLEMENTS These buttons are only active at Level 2 access These buttons have a...

Page 8: ...Level 1 General user controls This lower level allows the user to Perform a lamp test Silence Internal buzzer Put the panel into Access Level 2 if in possession of the required access code Level 2 Aut...

Page 9: ...test and confirm LEDs and internal buzzer operation 4 Test each key for correct functioning 5 Test all sounders relays etc for proper operation TESTING FIELD EQUIPMENT Testing Sounders 1 Introduce th...

Page 10: ...fault is present when there is a voltage below 20 V DC at the battery terminals or if there is a battery charger problem Charger problems can be caused by panel s hardware failure or batteries that h...

Page 11: ...y using two external independent switches on the inputs overlap the addressable order the Sounder Output or the Fire Alarm Relay state Example of application Door Holder This implementation has the ab...

Page 12: ...ER CIRCUIT NUMBER OF CIRCUITS 1 END OF LINE RESISTOR VALUE 10K Ohms MONITORING Open and Short Circuit ALARM VOLTAGE 27 5V DC SOUNDER CIRCUIT FUSE 1 1 Amp resettable Electronic Fuse MAX CURRENT AVAILAB...

Page 13: ...lsc_01_010001_en_180711 GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Su...

Reviews: