Auxiliary Relay Contact Fault 

Provides Fault signal to external devices. Relay NC contact 2A @ 30V DC resistive / 0.25A @ 230V AC resistive. Also 
Active for microprocessor fault. Active until Reset and all faults are cleared. Relay contact will open when any fault is present 
on the system. 
 
The wiring for each output should be terminated in their respective terminals and the cable screens connected to earth. 
 
 

INPUTS 

 
To activate the inputs, a shunt must be made between the Common “C” and the input to be activated by the means of a dry 
contact switch (no voltage).  

 
INPUT “DE” - Fire Relay 

The “DE” input will activate the Fire Relay. Connect it to “C” input for activation. 
 

INPUT “EV” - Sounder Circuit 

The “EV” input will activate the Sounder Circuit. Connect it to “C” input for activation.  
 

NOTE: 

“EV” always activate S1 even if sounders are disabled. 

 

 
CONNECTING THE PANEL 

 
The mains supply should be routed away from the other cables and enter the control panel adjacent to the mains terminal 
block. 
 
Wiring to the Mains supply should only be undertaken by a suitably qualified and competent person 
 
Depending on ORION-BCM load and standby requirements, two 12 volt valve regulated lead acid batteries with the capacity 
up to 7Ah may be fitted in the housing. The batteries should be wired in series (24V) using the supplied link. Take care not to 
short circuit the battery terminals. 
 
Check sounder wiring for continuity. Short or open circuit indications must be rectified before connecting to the control panel. 
All cable testing must be carried out with a Multimeter. 
 

WARNING: Do not use a Megger when devices are connected. 

 
Induced voltage higher than 1 Volt indicates possible cable problems or bad earth connection and must be rectified before 
connection. 
 
 

 

Summary of Contents for ORION-BCM LSC

Page 1: ...ault detection and notification listed below In addition to local notification status is also reported to addressable system Sounder Circuit Integrity Fault Battery Charger Fault voltage level and cha...

Page 2: ...voltage detector and sounder cabling The panel should be fixed to the wall using the 4 mounting holes provided and No 8 10 countersunk screws Any dust created during the fixing process must be kept o...

Page 3: ...ng If a sounder circuit is not used the EOL resistor should be fitted in the control panel sounder output The sounder circuits are protected against short circuits the electronic fuse will reset when...

Page 4: ...Connect it to C input for activation NOTE EV always activate S1 even if sounders are disabled CONNECTING THE PANEL The mains supply should be routed away from the other cables and enter the control pa...

Page 5: ...re Relay and EV Sounder direct activation non monitored E Auxiliary Supply Output monitored Addressable Interface ADLI BCM Connections The following board is placed inside the box A DIL Switch for add...

Page 6: ...indicate any FAULT condition present on panel DISABLED Used to indicate that the panel has features that have been disabled in Access Level 2 SUPPLY Used to indicate the presence of supply In Access...

Page 7: ...unders Auxiliary Fault Relays is not affected by this action NOTE When reset all LEDs will flash and relays will pulse DISABLEMENTS These buttons are only active at Level 2 access These buttons have a...

Page 8: ...Level 1 General user controls This lower level allows the user to Perform a lamp test Silence Internal buzzer Put the panel into Access Level 2 if in possession of the required access code Level 2 Aut...

Page 9: ...test and confirm LEDs and internal buzzer operation 4 Test each key for correct functioning 5 Test all sounders relays etc for proper operation TESTING FIELD EQUIPMENT Testing Sounders 1 Introduce th...

Page 10: ...fault is present when there is a voltage below 20 V DC at the battery terminals or if there is a battery charger problem Charger problems can be caused by panel s hardware failure or batteries that h...

Page 11: ...y using two external independent switches on the inputs overlap the addressable order the Sounder Output or the Fire Alarm Relay state Example of application Door Holder This implementation has the ab...

Page 12: ...ER CIRCUIT NUMBER OF CIRCUITS 1 END OF LINE RESISTOR VALUE 10K Ohms MONITORING Open and Short Circuit ALARM VOLTAGE 27 5V DC SOUNDER CIRCUIT FUSE 1 1 Amp resettable Electronic Fuse MAX CURRENT AVAILAB...