Global Fire Equipment //
globalfire.pt
pm_io3ioplusmainsio_01_010003_en_200103
The Table below shows the DIL Switch values in order to configure the ONE ADDRESS MODE configuration.
FUNCTION
VALUE
DIL SWITCH
SW1
SW2
SW3
DIL SWITCH
SW4
SW5
SW6
SW7
ONE ADDRESS
MODE
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
Step by step INPUT configuration example
INPUT ACTIVATION MODE
Let's assume that the desired ONE ADDRESS MODE configuration is ON.
To obtain this configuration the following steps need to be taken:
STEP 1:
Remove power from the module.
STEP 2:
Set DIL Switched 1 to 7 to the OFF position and DIL Switch 8 to the ON position.
STEP 3:
Power up the module. The two LEDs flashing alternatively will indicate that the module is in programming mode.
STEP 4:
Set the DIL Switches 1 to 3 to ONE ADDRESS MODE (SW1: ON, SW2: OFF & SW3: ON).
STEP 5:
Set the DIL Switches 4 to 7 to ON (SW4: ON, SW5: OFF, SW6: OFF & SW7: OFF).
STEP 6:
Set the Switch 8 to the OFF position. The Green LED will flash four times.
The module’s is now programmed to function with one address only.
FACTORY DEFAULT VALUES
In order to clear all programmed values and reset module to factory defaults please execute the following steps:
● First ensure module is set in programming mode, first by placing DIL Switches 1 to 7 to OFF followed by setting
Switch 8 to ON.
● Set all Switches from 1 to 7 to ON.
● Finally reset Switch 8 to the OFF position.