The Table below shows the DIL Switch values in order to configure the ONE ADDRESS MODE configuration. 

 

 

 

FUNCTION 

VALUE 

DIL SWITCH 

SW1 

SW2 

SW3 

DIL SWITCH 

SW4 

SW5 

SW6 

SW7 

ONE ADDRESS 

MODE 

ON 

OFF 

ON 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

ON 

OFF 

OFF 

OFF 

 
 

Step by step INPUT configuration example 

 

INPUT ACTIVATION MODE 

Let's assume that the desired ONE ADDRESS MODE configuration is ON.  
To obtain this configuration the following steps need to be taken: 
 

STEP 1: 

Remove power from the module. 

STEP 2:

 Set DIL Switched 1 to 7 to the OFF position and DIL Switch 8 to the ON position. 

STEP 3:

 Power up the module. The two LEDs flashing alternatively will indicate that the module is in programming mode. 

STEP 4:

 Set the DIL Switches 1 to 3 to ONE ADDRESS MODE (SW1: ON, SW2: OFF & SW3: ON). 

STEP 5:

 Set the DIL Switches 4 to 7 to ON (SW4: ON, SW5: OFF, SW6: OFF & SW7: OFF). 

STEP 6:

 Set the Switch 8 to the OFF position. The Green LED will flash four times. 

The module’s is now programmed to function with one address only.

 

 

 

FACTORY DEFAULT VALUES 

 

In order to clear all programmed values and reset module to factory defaults please execute the following steps: 
● First ensure module is set in programming mode, first by placing DIL Switches 1 to 7 to OFF followed by setting 

Switch 8 to ON. 

● Set all Switches from 1 to 7 to ON. 
● Finally reset Switch 8 to the OFF position. 
 

 

GLOBAL FIRE EQUIPMENT S.A. 

 

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL 

Tel: +351 289 896 560  •  Sales: [email protected]  •  Technical Support: [email protected]  •  

www.globalfire.pt

 

 

Summary of Contents for IO-ISO

Page 1: ...Mode When in programming mode the 2 LEDs will flash alternatively The unit will remain in programming mode while SW 8 is in the ON position When Switch 8 goes from ON to the OFF position the settings...

Page 2: ...ed to obtain the desired output configuration In order to program the different functions available use Switches 1 through 7 as shown below FUNCTION VALUE DIL SWITCH SW1 SW2 SW3 DIL SWITCH SW4 SW5 SW6...

Page 3: ...ule s Output is now programmed with a delay of 30s which is the default Output Timer value OUTPUT TIMER FUNCTION Now that the module s output is programmed to have a 30s delay let s assume that desire...

Page 4: ...trigger FAULT 3 OPEN CIRCUIT TO ALARM Open Circuit OC Activation This mode is constantly monitoring the 22k EOL in case of OC it will trigger ALARM in case of SC it will trigger FAULT 4 4K7 OPEN TO A...

Page 5: ...ON MODE ON ON OFF 4K7 CLOSE TO ALARM Default OFF OFF OFF OFF SHORT CIRCUIT TO ALARM ON OFF OFF OFF OPEN CIRCUIT TO ALARM OFF ON OFF OFF 4K7 OPEN TO ALARM ON ON OFF OFF INPUT DELAYED ACTIVATION FUNCTIO...

Page 6: ...nd DIL Switch 8 to the ON position STEP 3 Power up the module The two LEDs flashing alternatively will indicate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to INPUT DELAY...

Page 7: ...cate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to ONE ADDRESS MODE SW1 ON SW2 OFF SW3 ON STEP 5 Set the DIL Switches 4 to 7 to ON SW4 ON SW5 OFF SW6 OFF SW7 OFF STEP 6...

Reviews: