OUTPUT CONFIGURATION
Output will activate when the programmed delay has elapsed. Alternatively an activation period can be programmed during
which the output will be active. The output relay will revert to the OFF position once the time has elapsed.
The table below shows the available functions and correspondent values, as well as the DIL Switch configuration needed to
obtain the desired output configuration:
In order to program the different functions available use Switches 1 through 7 as shown below:
FUNCTION
VALUE
DIL SWITCH
SW1
SW2
SW3
DIL SWITCH
SW4
SW5
SW6
SW7
OUTPUT MODE
FUNCTION
ON
OFF
OFF
NORMAL
(Default)
OFF
OFF
OFF
OFF
TIMED
ON
OFF
OFF
OFF
DELAYED
OFF
ON
OFF
OFF
OUTPUT TIMER
FUNCTION
OFF
ON
OFF
30s
(Default)
OFF
OFF
OFF
OFF
60s
ON
OFF
OFF
OFF
90s
OFF
ON
OFF
OFF
120s
ON
ON
OFF
OFF
150s
OFF
OFF
ON
OFF
180s
ON
OFF
ON
OFF
210s
OFF
ON
ON
OFF
240s
ON
ON
ON
OFF
270s
OFF
OFF
OFF
ON
300s
ON
OFF
OFF
ON
360s
OFF
ON
OFF
ON
420s
ON
ON
OFF
ON
480s
OFF
OFF
ON
ON
540s
ON
OFF
ON
ON
600s
OFF
ON
ON
ON