Global Fire Equipment IO-ISO Programming Manual Download Page 2

 

 

Global Fire Equipment // 

globalfire.pt 

pm_io3ioplusmainsio_01_010003_en_200103

 

 

 

OUTPUT CONFIGURATION 

 
Output will activate when the programmed delay has elapsed. Alternatively an activation period can be programmed during 
which the output will be active. The output relay will revert to the OFF position once the time has elapsed. 

 

 
The table below shows the available functions and correspondent values, as well as the DIL Switch configuration needed to 
obtain the desired output configuration: 

 

 

 
In order to program the different functions available use Switches 1 through 7 as shown below: 
 

FUNCTION 

VALUE 

DIL SWITCH 

SW1 

SW2 

SW3 

DIL SWITCH 

SW4 

SW5 

SW6 

SW7 

OUTPUT MODE 

FUNCTION 

ON 

OFF 

OFF 

NORMAL 

(Default) 

OFF 

OFF 

OFF 

OFF 

TIMED 

ON 

OFF 

OFF 

OFF 

DELAYED 

OFF 

ON 

OFF 

OFF 

OUTPUT TIMER 

FUNCTION 

OFF 

ON 

OFF 

30s 

(Default) 

OFF 

OFF 

OFF 

OFF 

60s 

ON 

OFF 

OFF 

OFF 

90s 

OFF 

ON 

OFF 

OFF 

120s 

ON 

ON 

OFF 

OFF 

150s 

OFF 

OFF 

ON 

OFF 

180s 

ON 

OFF 

ON 

OFF 

210s 

OFF 

ON 

ON 

OFF 

240s 

ON 

ON 

ON 

OFF 

270s 

OFF 

OFF 

OFF 

ON 

300s 

ON 

OFF 

OFF 

ON 

360s 

OFF 

ON 

OFF 

ON 

420s 

ON 

ON 

OFF 

ON 

480s 

OFF 

OFF 

ON 

ON 

540s 

ON 

OFF 

ON 

ON 

600s 

OFF 

ON 

ON 

ON 

 

 

Summary of Contents for IO-ISO

Page 1: ...Mode When in programming mode the 2 LEDs will flash alternatively The unit will remain in programming mode while SW 8 is in the ON position When Switch 8 goes from ON to the OFF position the settings...

Page 2: ...ed to obtain the desired output configuration In order to program the different functions available use Switches 1 through 7 as shown below FUNCTION VALUE DIL SWITCH SW1 SW2 SW3 DIL SWITCH SW4 SW5 SW6...

Page 3: ...ule s Output is now programmed with a delay of 30s which is the default Output Timer value OUTPUT TIMER FUNCTION Now that the module s output is programmed to have a 30s delay let s assume that desire...

Page 4: ...trigger FAULT 3 OPEN CIRCUIT TO ALARM Open Circuit OC Activation This mode is constantly monitoring the 22k EOL in case of OC it will trigger ALARM in case of SC it will trigger FAULT 4 4K7 OPEN TO A...

Page 5: ...ON MODE ON ON OFF 4K7 CLOSE TO ALARM Default OFF OFF OFF OFF SHORT CIRCUIT TO ALARM ON OFF OFF OFF OPEN CIRCUIT TO ALARM OFF ON OFF OFF 4K7 OPEN TO ALARM ON ON OFF OFF INPUT DELAYED ACTIVATION FUNCTIO...

Page 6: ...nd DIL Switch 8 to the ON position STEP 3 Power up the module The two LEDs flashing alternatively will indicate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to INPUT DELAY...

Page 7: ...cate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to ONE ADDRESS MODE SW1 ON SW2 OFF SW3 ON STEP 5 Set the DIL Switches 4 to 7 to ON SW4 ON SW5 OFF SW6 OFF SW7 OFF STEP 6...