Step by step INPUT configuration example 

 

INPUT ACTIVATION MODE 

Let's assume that the desired INPUT ACTIVATION MODE configuration is SHORT CIRCUIT TO ALARM.  
To obtain this configuration the following steps need to be taken:

 

 
STEP 1: 

Remove power from the module. 

STEP 2:

 Set DIL Switched 1 to 7 to the OFF position and DIL Switch 8 to the ON position. 

STEP 3:

 Power up the module. The two LEDs flashing alternatively will indicate that the module is in programming mode. 

STEP 4:

 Set the DIL Switches 1 to 3 to INPUT ACTIVATION MODE (SW1: ON, SW2: ON & SW3: OFF). 

STEP 5:

 Set the DIL Switches 4 to 7 to SHORT CIRCUIT TO ALARM (SW4: ON, SW5: OFF, SW6: OFF & SW7: OFF). 

STEP 6:

 Set the Switch 8 to the OFF position. The Green LED will flash four times. 

The module’s is now programmed to trigger an alarm when a short circuit is applied to the input.

 

 
 
INPUT DELAYED ACTIVATION FUNCTION 

Let’s assume that a delayed input with a 70 seconds delay is needed. 
In order to configure the timer, the following steps need to be taken:

 

 
STEP 1: 

Remove power from the module. 

STEP 2:

 Set DIL Switched 1 to 7 to the OFF position and DIL Switch 8 to the ON position. 

STEP 3:

 Power up the module. The two LEDs flashing alternatively will indicate that the module is in programming mode. 

STEP 4:

 Set the DIL Switches 1 to 3 to INPUT DELAYED ACTIVATION FUNCTION (SW1: OFF, SW2: OFF & SW3: ON). 

STEP 5:

 Set the DIL Switches 4 to 7 to 70s (SW4: ON, SW5: ON, SW6: ON & SW7: OFF). 

STEP

 

6:

 Set the Switch 8 to the OFF position. The Green LED will flash 4 times. 

The module’s Output Timer is now programmed to 120s. 

 
 
INPUT LED BEHAVIOUR  

The LED associated with each Input operates as follows: 
 

 

INPUT LED 

OFF 

INPUT OFF 

ON 

INPUT ON 

FLASHING 

DURING ACTIVATION DELAY 

 
In order to record new parameter value in the non-volatile memory, reset Switch 8 to the OFF position. 
 

 
ONE ADDRESS MODE (3 I/O PLUS 2 and 3 Channel only) 

 
There is a

ONE ADDRESS MODE

available for 3 I/O PLUS 2 and 3 Channel. In this mode, the module will monitor all inputs

     

 

 

 

 

   

 

   

   

   

 

 

 

 

 

   

 

but respond only with one address to the Addressable Panel. The module will report as follows: 
 

FAULT:

 If any of the inputs has a Short or Open circuit fault present the module will report analogue value 4 to the 

Panel. 

ALARM:

 If any of the inputs has been activated, the module will repost analogue value 64 to the Panel. 

● If there is no Faults or Alarms present, the module will report analogue value 16 to the Panel. 
● If an output activation as been sent by the Panel all 3 outputs will activate. 

 

Summary of Contents for IO-ISO

Page 1: ...Mode When in programming mode the 2 LEDs will flash alternatively The unit will remain in programming mode while SW 8 is in the ON position When Switch 8 goes from ON to the OFF position the settings...

Page 2: ...ed to obtain the desired output configuration In order to program the different functions available use Switches 1 through 7 as shown below FUNCTION VALUE DIL SWITCH SW1 SW2 SW3 DIL SWITCH SW4 SW5 SW6...

Page 3: ...ule s Output is now programmed with a delay of 30s which is the default Output Timer value OUTPUT TIMER FUNCTION Now that the module s output is programmed to have a 30s delay let s assume that desire...

Page 4: ...trigger FAULT 3 OPEN CIRCUIT TO ALARM Open Circuit OC Activation This mode is constantly monitoring the 22k EOL in case of OC it will trigger ALARM in case of SC it will trigger FAULT 4 4K7 OPEN TO A...

Page 5: ...ON MODE ON ON OFF 4K7 CLOSE TO ALARM Default OFF OFF OFF OFF SHORT CIRCUIT TO ALARM ON OFF OFF OFF OPEN CIRCUIT TO ALARM OFF ON OFF OFF 4K7 OPEN TO ALARM ON ON OFF OFF INPUT DELAYED ACTIVATION FUNCTIO...

Page 6: ...nd DIL Switch 8 to the ON position STEP 3 Power up the module The two LEDs flashing alternatively will indicate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to INPUT DELAY...

Page 7: ...cate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to ONE ADDRESS MODE SW1 ON SW2 OFF SW3 ON STEP 5 Set the DIL Switches 4 to 7 to ON SW4 ON SW5 OFF SW6 OFF SW7 OFF STEP 6...

Reviews: