The table below shows the available functions and correspondent values, as well as the DIL Switch configuration needed to

 

 

 

 

 

 

 

 

 

   

   

 

 

 

 

   

obtain the desired output configuration. 
 

 

 

 
 

FUNCTION 

VALUE 

DIL SWITCH 

SW1 

SW2 

SW3 

DIL SWITCH 

SW4 

SW5 

SW6 

SW7 

INPUT 

ACTIVATION MODE 

 

ON 

 

ON 

OFF 

4K7 CLOSE TO ALARM 

(Default) 

OFF 

OFF 

OFF 

OFF 

SHORT CIRCUIT TO ALARM 

ON 

OFF 

OFF 

OFF 

OPEN CIRCUIT TO ALARM

 

OFF 

ON 

OFF 

OFF 

4K7 OPEN TO ALARM 

ON 

ON 

OFF 

OFF 

INPUT DELAYED 

ACTIVATION FUNCTION 

OFF 

OFF 

ON 

0s 

(Default) 

OFF 

OFF 

OFF 

OFF 

10s 

ON 

OFF 

OFF 

OFF 

20s 

OFF 

ON 

OFF 

OFF 

30s 

ON 

ON 

OFF 

OFF 

40s 

OFF 

OFF 

ON 

OFF 

50s 

ON 

OFF 

ON 

OFF 

60s 

OFF 

ON 

ON 

OFF 

70s 

ON 

ON 

ON 

OFF 

80s 

OFF 

OFF 

OFF 

ON 

90s 

ON 

OFF 

OFF 

ON 

100s 

OFF 

ON 

OFF 

ON 

110s 

ON 

ON 

OFF 

ON 

120s 

OFF 

OFF 

ON 

ON 

130s 

ON 

OFF 

ON 

ON 

140s 

OFF 

ON 

ON 

ON 

150s 

ON 

ON 

ON 

ON 

 
 
 
 

 

Summary of Contents for IO-ISO

Page 1: ...Mode When in programming mode the 2 LEDs will flash alternatively The unit will remain in programming mode while SW 8 is in the ON position When Switch 8 goes from ON to the OFF position the settings...

Page 2: ...ed to obtain the desired output configuration In order to program the different functions available use Switches 1 through 7 as shown below FUNCTION VALUE DIL SWITCH SW1 SW2 SW3 DIL SWITCH SW4 SW5 SW6...

Page 3: ...ule s Output is now programmed with a delay of 30s which is the default Output Timer value OUTPUT TIMER FUNCTION Now that the module s output is programmed to have a 30s delay let s assume that desire...

Page 4: ...trigger FAULT 3 OPEN CIRCUIT TO ALARM Open Circuit OC Activation This mode is constantly monitoring the 22k EOL in case of OC it will trigger ALARM in case of SC it will trigger FAULT 4 4K7 OPEN TO A...

Page 5: ...ON MODE ON ON OFF 4K7 CLOSE TO ALARM Default OFF OFF OFF OFF SHORT CIRCUIT TO ALARM ON OFF OFF OFF OPEN CIRCUIT TO ALARM OFF ON OFF OFF 4K7 OPEN TO ALARM ON ON OFF OFF INPUT DELAYED ACTIVATION FUNCTIO...

Page 6: ...nd DIL Switch 8 to the ON position STEP 3 Power up the module The two LEDs flashing alternatively will indicate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to INPUT DELAY...

Page 7: ...cate that the module is in programming mode STEP 4 Set the DIL Switches 1 to 3 to ONE ADDRESS MODE SW1 ON SW2 OFF SW3 ON STEP 5 Set the DIL Switches 4 to 7 to ON SW4 ON SW5 OFF SW6 OFF SW7 OFF STEP 6...

Reviews: