The table below shows the available functions and correspondent values, as well as the DIL Switch configuration needed to
obtain the desired output configuration.
FUNCTION
VALUE
DIL SWITCH
SW1
SW2
SW3
DIL SWITCH
SW4
SW5
SW6
SW7
INPUT
ACTIVATION MODE
ON
ON
OFF
4K7 CLOSE TO ALARM
(Default)
OFF
OFF
OFF
OFF
SHORT CIRCUIT TO ALARM
ON
OFF
OFF
OFF
OPEN CIRCUIT TO ALARM
OFF
ON
OFF
OFF
4K7 OPEN TO ALARM
ON
ON
OFF
OFF
INPUT DELAYED
ACTIVATION FUNCTION
OFF
OFF
ON
0s
(Default)
OFF
OFF
OFF
OFF
10s
ON
OFF
OFF
OFF
20s
OFF
ON
OFF
OFF
30s
ON
ON
OFF
OFF
40s
OFF
OFF
ON
OFF
50s
ON
OFF
ON
OFF
60s
OFF
ON
ON
OFF
70s
ON
ON
ON
OFF
80s
OFF
OFF
OFF
ON
90s
ON
OFF
OFF
ON
100s
OFF
ON
OFF
ON
110s
ON
ON
OFF
ON
120s
OFF
OFF
ON
ON
130s
ON
OFF
ON
ON
140s
OFF
ON
ON
ON
150s
ON
ON
ON
ON
5