Manufacturers of Fire Detection Equipment
globalfire.pt
GFE-TCP-WEB -
CONFIGURATION MANUAL - 11/2017
CONFIGURATION: INTERFACE
The interface is supplied with a default configuration, and it's only necessary to take the steps below:
This automatic process requires that DHCP is enabled in local network, which is normally activated on the
router that connects to internet.
1) Take note of ‘Client ID’ and ‘Channel’ values described in interface label.
2)
Turn panel power OFF (including batteries).
3)
Connect 5 way flat cable between interface and panel as per indicated in ‘Connection Diagram’ section of this manual.
4)
Connect interface to local network using RJ45 connector.
5)
Turn panel power ON
6)
Check if red and yellow Led’s are blinking. This behaviour is a visual indication of active communication with server.
7)
Go to chapter ‘Configuration: Webpage’ and insert interface ‘Client ID’ and ‘Channel’ in the corresponding fields.
8)
Optional: Assign a name to installation and press ‘Save’.
9)
Press ‘Connect’ to start communication with panel.
Refer to manual section ‘Manual Configuration: Software’ in case it’s necessary to configure interface manually.
Automatic Configuration
ATTENTION: