GFE-TCP-WEB -
CONFIGURATION MANUAL - 11/2017
JUNIOR V4 settings
JUNO NET settings
ORION-PLUS settings
Dataloop is available as default in JUNIOR V4 panel range. If necessary it can be changed in Installation Menu of panel
Diagnostic mode as per below image.
Dataloop is permantly available at CON5 connector in J-NET-CON board.
Dataloop is permanently available at Data-Loop connector.
Additional Notes:
Both JUNIOR V4 & JUNO NET panels should have COMMS parameter set as 'Normal' as per below image.
Panel must be completely OFF when connec ting/disconnecting 5way flat cable otherwise panel and/or interface could
be damaged.
NOTE:
Panel should have firmware 3.09 build001P or higher for enhanced webpage usability.
NOTE:
JUNO NET panels with 4, 7, 10 & 13 Loops require a specific 5-way flat cable lead. Please contact your supplier
requesting it.
JUNO NET panels prior to 2009 with J-NET-CON board version 4.X also require the same specific 5-way flat cable lead.
Please contact your supplier requesting it.
Panels should have firmware 3.09 build001P or higher for enhanced webpage usability.
en54secfse:N ac_flt_latch:Y (pg 1/2)
prot: ADVANCED comms:NRMAL en54:Y
output:DT LOOP
com_flt_ltch:Y
en54secfse:N ac_flt_latch:Y (pg 1/2)
prot: ADVANCED comms:NRMAL en54:Y
output:DT LOOP
com_flt_ltch:Y