STEP BY STEP ADVANCED FEATURES CONFIGURATION EXAMPLE 

 

NUMBER OF ADDRESSES TO REPORT FUNCTION 

 

Let's assume that the ADLI V2 FO is to be used with an ORION Conventional Fire Detection Panel with 8 fire detection

 

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

   

 

 

zones, and the desired configuration is to report one address per zone. 
 

STEP 1: 

Remove power from the ORION panel and assure that the module is connected to the panel with 

the 5 way flat cable. 

STEP 2:

 Set D.I.L. Switches 1 to 7 to OFF position and D.I.L. Switch 8 to ON position. 

STEP 3:

 Power up the Panel. The two LEDs flashing alternatively on the module indicates that the module is in 

programming mode. 

STEP 4:

 Set the D.I.L. Switches 1 to 3 to NUMBER OF ADDRESSES REPORT (SW1: ON, SW2: OFF & SW3: OFF). 

STEP 5:

 Set the D.I.L. switches 4 to 7 to EIGHT ADDRESSES (SW4: ON, SW5: ON, SW6: OFF & SW7: OFF). 

STEP 6:

 Set the Switch 8 to OFF position. The Green LED will flash 4 times. The module is now programmed to report to 

the analogue addressable panel with 8 addresses. 

STEP 7: 

Configure the desired address on the ADLI V2 FO and reset the ORION panel. 

 
 

TECHNICAL SPECIFICATIONS 

PRIMARY SUPPLY VOLTAGE - IN 

28.5 V DC nominal - 17 to 30 V DC 

SUPPLY CURRENT 

ADLI V2 FO ORION - 8.6 mA 
ADLI V2 FO LOOP - Ext. Supply: 6.4 mA / Loop: 0.5 mA  

MAX. HUMIDITY / OPERATING TEMPERATURE 

95 % RH Non-Condensing / 0ºC to 40ºC 

DIMENSIONS 

ADLI V2 FO ORION - 135 (L) x 36 (W) x 13 (H) mm 
ADLI V2 FO LOOP - 135 (L) x 36 (W) x 11 (H) mm 

WEIGHT 

20 g 

 
 

 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ADLI V2 FO

Page 1: ...MAIN FEATURES Fast activation response Three status LEDs Remote sound Silence alarms Remote reset Low power consumption Automatic conventional panel recognition Fault and fire status report Different...

Page 2: ...STATUS LEDS GREEN LED This LED will flash every time the addresses associated with the module are polled by the addressable panel YELLOW LED This LED will be lit whenever there is a fault condition a...

Page 3: ...ional panel allowing a faster troubleshooting The table below describes the different analogue values reported to the addressable panel REPORTED ANALOGUE VALUE NORMAL OPERATION 16 ZONE FAULT 4 PANEL F...

Page 4: ...only one address by default but can be configured to assume one address per zone If it is configured to have one address per zone the ADLI V2 FO will assume 2 4 8 consecutive addresses starting from...

Page 5: ...Global Fire Equipment globalfire pt ma_adlifo_01_020000_en_200714 5 www acornfiresecurity com www acornfiresecurity com...

Page 6: ...ress addresses configured will report as ZONE MONITOR UNITS ZMU When the ADLI V2 FO is configured to report with ONE ADDRESS ONLY it will only assume one address on the loop and any fault or fire cond...

Page 7: ...under I O address PROGRAMMING THE ADLI V2 FO In order to program the different functions available use switches 1 through 7 as shown below A The first 3 switches select the function to be programmed B...

Page 8: ...module is in programming mode STEP 4 Set the D I L Switches 1 to 3 to NUMBER OF ADDRESSES REPORT SW1 ON SW2 OFF SW3 OFF STEP 5 Set the D I L switches 4 to 7 to EIGHT ADDRESSES SW4 ON SW5 ON SW6 OFF S...

Reviews: