ADVANCED PROGRAMMABLE FEATURES 

 
PROGRAMMING MODE D.I.L. SWITCH CONFIGURATION 

 
In order to set the module in programming mode first POWER OFF your module then set DIL switches 1 to 7 to OFF and

 

   

 

 

   

 

 

 

 

 

 

 

 

 

 

         

 

 

switch 8 to the ON position, as indicated on the image below. Finally POWER ON your module. 

 

 

Switches 1-7

:

 

Used to select programming parameter and assigned value 

Switch 8

:

 

Programming Mode 

 

When in programming mode the 2 LEDs (Green and Red) will flash alternatively. The unit will remain in programming mode

   

 

 

   

 

 

 

 

 

 

 

 

 

 

   

 

 

while SW 8 is in the ON position. When switch 8 goes from ON to the OFF position the settings indicated on switches 1

 

       

 

 

 

 

   

 

 

   

 

 

 

 

 

 

 

   

through 7 will be recorded on the non-volatile memory of the module. If a new parameter has been accepted, the Green LED

   

   

   

 

 

   

 

     

 

 

 

 

 

 

 

 

will flash 4 times. When programming is not accepted the Red indicator will remain on  for an extra 3 seconds. 
 
 

PROGRAMMABLE OPTIONS 

 

NUMBER OF ADDRESSES TO REPORT  

 

NOTE:

 This configuration will only have effect when the ADLI V2 FO is to be used with an ORION 

Conventional Fire Detection Panel. 

 
This programmable feature allows the user to configure the ADLI V2 FO to report to the addressable panel with only one

 

 

 

 

 

   

 

 

 

 

   

   

 

 

 

 

 

 

address or with one address per zone. The address/addresses configured will report as ZONE MONITOR UNITS (ZMU). 
 
When the ADLI V2 FO is configured to report with

ONE ADDRESS ONLY

, it will only assume one address on the loop and

 

 

 

 

   

   

 

 

 

 

   

 

 

 

 

   

 

 

 

any fault or fire condition present on the conventional panel will be reported on that same address. 
 
If the ADLI V2 FO is configured to report with

2 / 4 / 8 ADDRESSES

, it will assume 2 / 4 / 8 consecutive addresses on the

 

 

 

 

   

   

 

 

         

   

 

           

 

   

 

loop (

e. g.

if the configuration is 4 addresses and the D.I.L. switch addressing is set to address number one, the ADLI V2 FO

 

 

 

 

 

     

 

 

 

 

 

   

   

 

 

 

 

 

 

 

will report on addresses number 1, 2, 3 and 4

), one per each zone of the ORION conventional panel. Any fault or fire

 

 

 

 

       

 

 

 

 

 

   

 

 

 

 

 

   

 

condition present on one of the conventional panel zones will be reported to the addressable panel on it’s associated

 

 

 

   

 

 

 

 

 

 

   

 

 

 

 

 

 

address. Any other conventional panel fault will be reported on the first address set on the D.I.L. switch. 
 

REMOTE RESET / SILENCE SOUNDERS 

 
This programmable feature allows the ORION / ORION-EX V2 panel to be controlled remotely from any of GFE’s analogue

 

 

 

 

 

   

 

 

     

 

 

 

   

 

 

addressable panels, allowing the user to SILENCE / RESOUND Alarms (EVACUATION) and reset the panel from the

 

 

 

 

   

   

 

 

 

 

 

 

 

 

 

addressable panel. 
 
If this function is set to not active, the sounders can still be activated from the addressable panel but it will not be possible to

 

 

   

   

 

 

 

 

 

   

 

 

 

 

 

   

 

   

   

silence the sounder nor perform a remote reset. 
 
This function is ACTIVE by default to ORION panel and NOT ACTIVE by default to ORION-EX V2 panel. 
 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ADLI V2 FO

Page 1: ...MAIN FEATURES Fast activation response Three status LEDs Remote sound Silence alarms Remote reset Low power consumption Automatic conventional panel recognition Fault and fire status report Different...

Page 2: ...STATUS LEDS GREEN LED This LED will flash every time the addresses associated with the module are polled by the addressable panel YELLOW LED This LED will be lit whenever there is a fault condition a...

Page 3: ...ional panel allowing a faster troubleshooting The table below describes the different analogue values reported to the addressable panel REPORTED ANALOGUE VALUE NORMAL OPERATION 16 ZONE FAULT 4 PANEL F...

Page 4: ...only one address by default but can be configured to assume one address per zone If it is configured to have one address per zone the ADLI V2 FO will assume 2 4 8 consecutive addresses starting from...

Page 5: ...Global Fire Equipment globalfire pt ma_adlifo_01_020000_en_200714 5 www acornfiresecurity com www acornfiresecurity com...

Page 6: ...ress addresses configured will report as ZONE MONITOR UNITS ZMU When the ADLI V2 FO is configured to report with ONE ADDRESS ONLY it will only assume one address on the loop and any fault or fire cond...

Page 7: ...under I O address PROGRAMMING THE ADLI V2 FO In order to program the different functions available use switches 1 through 7 as shown below A The first 3 switches select the function to be programmed B...

Page 8: ...module is in programming mode STEP 4 Set the D I L Switches 1 to 3 to NUMBER OF ADDRESSES REPORT SW1 ON SW2 OFF SW3 OFF STEP 5 Set the D I L switches 4 to 7 to EIGHT ADDRESSES SW4 ON SW5 ON SW6 OFF S...

Reviews: