ADVANCED PROGRAMMABLE FEATURES
PROGRAMMING MODE D.I.L. SWITCH CONFIGURATION
In order to set the module in programming mode first POWER OFF your module then set DIL switches 1 to 7 to OFF and
switch 8 to the ON position, as indicated on the image below. Finally POWER ON your module.
Switches 1-7
:
Used to select programming parameter and assigned value
Switch 8
:
Programming Mode
When in programming mode the 2 LEDs (Green and Red) will flash alternatively. The unit will remain in programming mode
while SW 8 is in the ON position. When switch 8 goes from ON to the OFF position the settings indicated on switches 1
through 7 will be recorded on the non-volatile memory of the module. If a new parameter has been accepted, the Green LED
will flash 4 times. When programming is not accepted the Red indicator will remain on for an extra 3 seconds.
PROGRAMMABLE OPTIONS
NUMBER OF ADDRESSES TO REPORT
NOTE:
This configuration will only have effect when the ADLI V2 FO is to be used with an ORION
Conventional Fire Detection Panel.
This programmable feature allows the user to configure the ADLI V2 FO to report to the addressable panel with only one
address or with one address per zone. The address/addresses configured will report as ZONE MONITOR UNITS (ZMU).
When the ADLI V2 FO is configured to report with
ONE ADDRESS ONLY
, it will only assume one address on the loop and
any fault or fire condition present on the conventional panel will be reported on that same address.
If the ADLI V2 FO is configured to report with
2 / 4 / 8 ADDRESSES
, it will assume 2 / 4 / 8 consecutive addresses on the
loop (
e. g.
if the configuration is 4 addresses and the D.I.L. switch addressing is set to address number one, the ADLI V2 FO
will report on addresses number 1, 2, 3 and 4
), one per each zone of the ORION conventional panel. Any fault or fire
condition present on one of the conventional panel zones will be reported to the addressable panel on it’s associated
address. Any other conventional panel fault will be reported on the first address set on the D.I.L. switch.
REMOTE RESET / SILENCE SOUNDERS
This programmable feature allows the ORION / ORION-EX V2 panel to be controlled remotely from any of GFE’s analogue
addressable panels, allowing the user to SILENCE / RESOUND Alarms (EVACUATION) and reset the panel from the
addressable panel.
If this function is set to not active, the sounders can still be activated from the addressable panel but it will not be possible to
silence the sounder nor perform a remote reset.
This function is ACTIVE by default to ORION panel and NOT ACTIVE by default to ORION-EX V2 panel.