CONNECTING MORE THAN ONE ORION / ORION EX V2 PANEL
ADDRESS D.I.L. SWITCH CONFIGURATION
Switches 1-7
: Used to address the module.
Switch 8
: Not used (Special function on programming mode).
ADDRESS SETTINGS
The ADLI V2 FO can assume from one to eight consecutive addresses depending on the programmed settings (refer to
ADVANCED PROGRAMMABLE FEATURES section of this manual) and the type of conventional panel that it is connected
to, ORION or ORION-EX V2.
If connected to an ORION conventional panel, the ADLI V2 FO assumes only one address, by default, but can be configured
to assume one address per zone. If it is configured to have one address per zone, the ADLI V2 FO will assume 2 / 4 / 8
consecutive addresses, starting from the address that is set on the D.I.L. switch. Every address set reports to the analogue
addressable panel as a ZONE MONITOR UNIT.
If connected to an ORION-EX V2, the ADLI V2 FO assumes, by default, four consecutive addresses, one per each fire
detection zone. If the I/O REPORT advanced programmable feature is set to ACTIVE, then the module will assume four
additional consecutive addresses reporting as I/O to the analogue addressable panel (four additional details refer to
ADVANCED PROGRAMMABLE FEATURES section of this manual).
4