CONNECTING MORE THAN ONE ORION / ORION EX V2 PANEL 

 
 

ADDRESS D.I.L. SWITCH CONFIGURATION 
 

 

Switches 1-7

: Used to address the module. 

Switch 8

: Not used (Special function on programming mode). 

 

ADDRESS SETTINGS 

 

The ADLI V2 FO can assume from one to eight consecutive addresses depending on the programmed settings (refer to

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

   

ADVANCED PROGRAMMABLE FEATURES section of this manual) and the type of conventional panel that it is connected

 

 

 

   

 

 

 

 

   

 

 

     

 

to, ORION or ORION-EX V2. 
 
If connected to an ORION conventional panel, the ADLI V2 FO assumes only one address, by default, but can be configured

 

     

 

 

 

 

 

 

 

 

 

 

   

 

 

   

 

to assume one address per zone. If it is configured to have one address per zone, the ADLI V2 FO will assume 2 / 4 / 8

 

 

 

 

 

       

   

 

 

 

 

 

 

 

 

 

 

           

consecutive addresses, starting from the address that is set on the D.I.L. switch. Every address set reports to the analogue

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

   

 

 

addressable panel as a ZONE MONITOR UNIT. 
 
If connected to an ORION-EX V2, the ADLI V2 FO assumes, by default, four consecutive addresses, one per each fire

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

detection zone. If the I/O REPORT advanced programmable feature is set to ACTIVE, then the module will assume four

 

   

 

 

 

 

 

   

   

 

 

 

 

 

 

 

additional consecutive addresses reporting as I/O to the analogue addressable panel (four additional details refer to

 

 

 

 

 

   

 

 

 

 

 

 

 

   

ADVANCED PROGRAMMABLE FEATURES section of this manual). 
 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ADLI V2 FO

Page 1: ...MAIN FEATURES Fast activation response Three status LEDs Remote sound Silence alarms Remote reset Low power consumption Automatic conventional panel recognition Fault and fire status report Different...

Page 2: ...STATUS LEDS GREEN LED This LED will flash every time the addresses associated with the module are polled by the addressable panel YELLOW LED This LED will be lit whenever there is a fault condition a...

Page 3: ...ional panel allowing a faster troubleshooting The table below describes the different analogue values reported to the addressable panel REPORTED ANALOGUE VALUE NORMAL OPERATION 16 ZONE FAULT 4 PANEL F...

Page 4: ...only one address by default but can be configured to assume one address per zone If it is configured to have one address per zone the ADLI V2 FO will assume 2 4 8 consecutive addresses starting from...

Page 5: ...Global Fire Equipment globalfire pt ma_adlifo_01_020000_en_200714 5 www acornfiresecurity com www acornfiresecurity com...

Page 6: ...ress addresses configured will report as ZONE MONITOR UNITS ZMU When the ADLI V2 FO is configured to report with ONE ADDRESS ONLY it will only assume one address on the loop and any fault or fire cond...

Page 7: ...under I O address PROGRAMMING THE ADLI V2 FO In order to program the different functions available use switches 1 through 7 as shown below A The first 3 switches select the function to be programmed B...

Page 8: ...module is in programming mode STEP 4 Set the D I L Switches 1 to 3 to NUMBER OF ADDRESSES REPORT SW1 ON SW2 OFF SW3 OFF STEP 5 Set the D I L switches 4 to 7 to EIGHT ADDRESSES SW4 ON SW5 ON SW6 OFF S...

Reviews: