I/O REPORT
NOTE:
This configuration will only have effect when the ADLI V2 FO is to be used with an ORION-EX V2
Conventional Extinguishing Panel.
This programmable feature allows the user to configure the ADLI V2 FO to report the state of ORION-EX V2’s
S1 sounder, Pre-release delay, REM and general disablement LED
, using four additional consecutive
addresses reporting as Input/Outputs (I/O) to the addressable address.
An Output activation command from the addressable panel to the first I/O (S1 sounder) will activate the
evacuation on the ORION-EX V2 conventional panel.
This allows, if more than one conventional panel is connected to an addressable panel though an ADLI V2 FO
module, to activate an evacuation individually on each conventional panel via, e.g., a call point activating a I/O
group containing the S1 sounder I/O address.
PROGRAMMING THE ADLI V2 FO
In order to program the different functions available use switches 1 through 7 as shown below:
A –
The first 3 switches select the function to be programmed.
B –
Switches 4 through 7 select the value for the function to be programmed.
The table below shows the available functions and correspondent values, as well as the D.I.L. Switch configuration needed
to obtain the desired Output configuration:
FUNCTION
VALUE
DIL SWITCH
SW1
SW2
SW3
DIL SWITCH
SW4
SW5
SW6
SW7
NUMBER OF
ADDRESSES TO
REPORT
(ORION PANEL
ONLY)
ON
OFF
OFF
ONE ADDRESS
(Default)
OFF
OFF
OFF
OFF
TWO ADDRESSES
(to be used
with ORION 2 ZONES)
ON
OFF
OFF
OFF
FOUR ADDRESSES
(to be
used with ORION 4 ZONES)
OFF
ON
OFF
OFF
EIGHT ADDRESSES
(to be
used with ORION 8 ZONES)
ON
ON
OFF
OFF
REMOTE RESET /
SILENCE SOUNDERS
OFF
ON
OFF
NOT ACTIVE
(Default for ORION-EX V2)
OFF
OFF
OFF
OFF
ACTIVE
(Default for ORION)
ON
OFF
OFF
OFF
I/O REPORT
(ORION-EX V2
PANEL ONLY)
ON
ON
OFF
DO NOT REPORT I/Os
(Default)
OFF
OFF
OFF
OFF
REPORT I/Os
ON
OFF
OFF
OFF
7