Global Fire Equipment ADLI V2 FO Programming Manual Download Page 1

 

 

Global Fire Equipment // 

globalfire.pt 

ma_adlifo_01_020000_en_200714

 

 
 

ADLI V2 FO 

Addressable Loop Interface 

 

INSTALLATION / PROGRAMMING MANUAL

 

 

 

GENERAL DESCRIPTION 

 

The ADLI FO V2 is an addressable loop fibre optic interface which allows a conventional ORION / ORION-EX V2

 

 

 

   

 

 

 

 

 

 

 

   

 

   

 

 

panel to be integrated in any of GFE’s analogue addressable systems, allowing the addressable panel to monitor

   

 

   

   

 

 

 

 

 

 

 

   

 

and control the status of the conventional panel.

An 8 way DIL switch is provided to set the module’s address and to

 

 

 

   

 

 

 

   

 

 

   

   

 

 

 

 

   

configure the advanced features. 

 

There are two assemblies of the ADLI V2 FO:

ADLI V2 FO LOOP

and

ADLI V2 FO ORION

. Every ORION / ORION-EX V2

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

panel has to be equipped with one ADLI V2 FO ORION and every link that connects to the loop has to be equipped with one

 

   

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

     

 

 

 

ADLI V2 FO LOOP.  

 
 

MAIN FEATURES 

● Fast activation response 
● Three status LEDs 
● Remote sound / Silence alarms 
● Remote reset 
● Low power consumption 
● Automatic conventional panel recognition 
● Fault and fire status report 
● Different analogue values for zone, panel and supply faults for easier troubleshooting 
● Programmable number of addresses to report (for ORION conventional panel) 
● Programmable extinguishing, pre-release delay, sounder and disablements status report 

using 4 additional addresses reporting as I/Os (ORION-EX V2 panel only) 

   
 

IMPORTANT SAFETY NOTES 

 

● This equipment must only be installed and maintained by a suitably qualified and technically competent person. 

● A basic knowledge and training in the installation of Fire and Extinguish Detection systems is assumed. 

● The fire detection system should be designed by a suitably qualified person with reference to the local Regulations 

and Guidance from the Fire Officer where applicable. 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ADLI V2 FO

Page 1: ...MAIN FEATURES Fast activation response Three status LEDs Remote sound Silence alarms Remote reset Low power consumption Automatic conventional panel recognition Fault and fire status report Different...

Page 2: ...STATUS LEDS GREEN LED This LED will flash every time the addresses associated with the module are polled by the addressable panel YELLOW LED This LED will be lit whenever there is a fault condition a...

Page 3: ...ional panel allowing a faster troubleshooting The table below describes the different analogue values reported to the addressable panel REPORTED ANALOGUE VALUE NORMAL OPERATION 16 ZONE FAULT 4 PANEL F...

Page 4: ...only one address by default but can be configured to assume one address per zone If it is configured to have one address per zone the ADLI V2 FO will assume 2 4 8 consecutive addresses starting from...

Page 5: ...Global Fire Equipment globalfire pt ma_adlifo_01_020000_en_200714 5 www acornfiresecurity com www acornfiresecurity com...

Page 6: ...ress addresses configured will report as ZONE MONITOR UNITS ZMU When the ADLI V2 FO is configured to report with ONE ADDRESS ONLY it will only assume one address on the loop and any fault or fire cond...

Page 7: ...under I O address PROGRAMMING THE ADLI V2 FO In order to program the different functions available use switches 1 through 7 as shown below A The first 3 switches select the function to be programmed B...

Page 8: ...module is in programming mode STEP 4 Set the D I L Switches 1 to 3 to NUMBER OF ADDRESSES REPORT SW1 ON SW2 OFF SW3 OFF STEP 5 Set the D I L switches 4 to 7 to EIGHT ADDRESSES SW4 ON SW5 ON SW6 OFF S...